| 2007-06-20 21:03:50 | *** UNSAT*** |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE TO STATE ALL THE RELEVANT CODES |
| | AS ADOPTED BY THE STATE OF FLORIDA AS OF DECEMBER 8TH, |
| | 2006. |
| | PLEASE SEE THE FOLLOWING AT A MINIMUM MUST BE STATED. |
| | SOME CODES STATED NEVER EXISTED.(2003 NEC) |
| | |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 (DONE ON COVER ALTHOUGH REQUIRED ON |
| | ELECTRICAL SHEETS) |
| | 2002 NFPA-72 |
| | |
| | ** PLEASE BE AWARE OF ANY POSSIBLE CODES FROM OTHER |
| | TRADES. |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| | FOR BOTH THE ARCHITECT, FIRM AS WELL AS THE ENGINEER |
| | AND ENGINEERING FIRM. |
| | PLEASE SEE MISSING THE PRINTED NAMES FOR DESIGNERS. |
| | PLEASE SEE THE PRINTED LICENSE NUMBERS FOR DESIGNERS. |
| | PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBERS FOR BOTH FIRMS. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 FOR |
| | ENGINEERS AND 61G1-16.004 FOR ARCHITECT FIRM.. PLEASE |
| | SEE FLORIDA STATUTES 471.023 FOR ENGINEERS AND 481.219 |
| | FOR ARCHITECT FIRM. |
| | |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT THIS COMMENT IS MADE BY ANY OTHER TRADE |
| | REVIEWER(S). |
| | |
| | 2) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE |
| | FBC HAS NOT BEEN MET. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ARE |
| | NOTE SEALED BY THE DESIGNER OF RECORD. PLEASE BE SURE |
| | TO SIGN, DATE AND SEAL CALCULATIONS. |
| | 13-103.1.1.1 |
| | ** PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON |
| | SECOND SHEET AS REQUIRED. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT |
| | CORRELATE WITH PLANS. |
| | PLEASE SEE THE LIGHTING FIXTURE TYPES DO NOT MATCH. |
| | PLEASE SEE THE WATTAGE ON FIXTURES DOES NOT MATCH |
| | PLEASE SEE THE NUMBER OF EACH FIXTURE ALSO DOES MATCH. |
| | PLEASE SEE 13-415.2.ABC.1.2 FOR REQUIRED TRACK LIGHTING |
| | CALCULATIONS AND FIGURES. |
| | ** PLEASE SEE THE FBC 13-415.1.AB.1.1, 13-415.2 AND |
| | TABLES FOR METHOD *B*. PLEASE VERIFY METHOD *B*. PLEASE |
| | SEE THE REQUIRED LIGHTING CONTROLS ARE NOT SHOWN ON |
| | PLANS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE INDICATE TIME FOR SCHEDULING IF A LIGHTING |
| | CONTROL SYSTEM IS INSTALLED ALONG WITH ALL OVER RIDE |
| | DEVICE TIMES. |
| | PLEASE SEE OF OCCUPANCY SENSOR TYPE DEVICES ARE USED, |
| | PLEASE LIST THE MAXIMUM TIMES PER SECTIONS ABOVE. IF |
| | TIMER TYPE DEVICES ARE USED PLEASE LIST MAXIMUM |
| | TIMES.(4HRS). |
| | ** AS DESIGNS WERE NOT SHOWN ON PLANS FOR REVIEW A |
| | COMPLETE REVIEW OF THESE ITEMS CAN NOT BE DONE AT THIS |
| | TIME. |
| | |
| | 3) NOTE: PLEASE SEE ELECTRICAL EQUIPMENT IS BEING NOTED |
| | IN STORAGE ROOM WHICH IS NOT PERMITTED. PLEASE SEE |
| | 110.26, 408.7, 240.24 ETC. |
| | THIS MAY NOT BE STORAGE ROOM. |
| | |
| | 4) NOTE: PLEASE SEE RISER SHOWS A NEW PANEL ON THE |
| | SECONDARY SIDE OF THE TRANSFORMER HOWEVER THE NOTE ON |
| | THE RISER MENTIONS EXISTING CONDUCTORS TO REMAIN. AS |
| | THE EXISTING PANEL, MAIN CIRCUIT BREAKER SIZE AND |
| | CONDUCTORS WAS NOT GIVEN IT CAN NOT BE DETERMINED IF |
| | THE EXISTING CONDUCTORS ARE OF SUFFICIENT SIZE TO |
| | TERMINATE IN THE 100AMP BREAKER AS SHOWN ON NEW PANEL. |
| | PLEASE SEE 240.21, 310.16, 240.4. |
| | PLEASE PROVIDE MORE INFORMATION. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 5) NOTE: PLEASE SEE 220.53 FOR MINIMUM LOADS TO BE |
| | FIGURED FOR SHOW WINDOW RECEPTACLES. PLEASE ADJUST |
| | SERVICE CALCULATIONS. |
| | |
| | 6) NOTE: PLEASE SEE THE EMERGENCY AND EXIT LIGHTS SHALL |
| | BE CIRCUITED TO THE LOCAL BRANCH CIRCUIT IN THAT AREA. |
| | PLEASE SEE 700.12F. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS |