Plan Review Notes
Plan Review Notes For Permit 07050992
Permit Number 07050992
Review Stop Z
Sequence Number 1
Notes
Date Text
2007-06-26 08:21:46PLANNING AND ZONING ***FAILED***
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PROVIDE A SIGNED AND SEALED SURVEY THAT WAS CREATED
 WITHIN A YEAR.
  
 3. PROVIDE SETBACKS FROM THE GENERATOR TO THE NORTH AND
 WEST PROPERTY LINES.PURSUANT TO SECTION 94-305(4)
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK. WINDOW AIR-CONDITIONING UNITS MAY
 NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED SIDE
 SETBACK.
  
 4. PURSUANT TO SECTION 94-444 (B) ALL GENERATORS AND
 TANKS SHALL BE SCREENED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL. WALLS
 SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT
 TWO-FOOT INTERVALS. PROVIDE DETAILS/CROSS SECTIONS
 ACCORDINGLY ON PLANS.
  