2007-06-28 11:01:18------------------DENIED---------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH NFPA
 110-02
  
 1. PLEASE INDICATE IN SITE PLAN THE LOCATION OF NEAREST
 OPENINGS IN THE BUILDING, AND THE DISTANCE TO THE
 GENERATOR, INCLUDING: DOORS, WINDOWS, SIFFIT VENTS, AIR
 INTAKES.
  
 2. PLEASE PROVIDE ACTUA ELEVATIONS SHOWING THE
 ELEVATION OF THE GENERATOR TO BE ABOVE THE BASE FLOOD
 ELEVATION. ALSO, SLAB SHALL RAISE THE GENERATOR MINIMUM
 6" ABOVE GRADE LEVEL PER NFPA 110-7.4.1.1.
  
 3. PLEASE INDICATE ON PLAN THE DISTANCE OF THE
 GENERATOR FROM THE BUILDING AND PROVIDE WALL
 CONSTRUCTION TYPE TO VERIFY PROPER CLEARANCE FROM
 COMBUSTIBLES. ALSO, PLEASE PROVIDE MINIMUM REQUIRED
 CLEARANCE FOR SERVICE, MAINTENANCE AND INSPECTION PER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS, WHICH WERE
 NOT INCLUDED WITH THIS APPLICATION.
  