| Plan Review Notes For Permit 07050992 |
| Permit Number |
07050992 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-28 11:01:18 | ------------------DENIED--------------------- | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH NFPA | | | 110-02 | | | | | | 1. PLEASE INDICATE IN SITE PLAN THE LOCATION OF NEAREST | | | OPENINGS IN THE BUILDING, AND THE DISTANCE TO THE | | | GENERATOR, INCLUDING: DOORS, WINDOWS, SIFFIT VENTS, AIR | | | INTAKES. | | | | | | 2. PLEASE PROVIDE ACTUA ELEVATIONS SHOWING THE | | | ELEVATION OF THE GENERATOR TO BE ABOVE THE BASE FLOOD | | | ELEVATION. ALSO, SLAB SHALL RAISE THE GENERATOR MINIMUM | | | 6" ABOVE GRADE LEVEL PER NFPA 110-7.4.1.1. | | | | | | 3. PLEASE INDICATE ON PLAN THE DISTANCE OF THE | | | GENERATOR FROM THE BUILDING AND PROVIDE WALL | | | CONSTRUCTION TYPE TO VERIFY PROPER CLEARANCE FROM | | | COMBUSTIBLES. ALSO, PLEASE PROVIDE MINIMUM REQUIRED | | | CLEARANCE FOR SERVICE, MAINTENANCE AND INSPECTION PER | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS, WHICH WERE | | | NOT INCLUDED WITH THIS APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|