| Plan Review Notes For Permit 07050992 |
| Permit Number |
07050992 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-16 22:41:24 | *****DENIED***** | | | | | | | | | 1.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY | | | POWER SHALL BE INSTALLED WITH COMPLIANCE WITH NFPA | | | 110. | | | | | | 2.EQUIPMENT USING GAS AND RELATED GAS PIPING SHALL BE | | | IN ACCORDANCE WITH NFPA 54. | | | | | | 3.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE | | | GENERATOR. | | | | | | 4.PROVIDE PROPER SETBACKS TO PROPERTY LINES AND AT | | | LEAST 10' DISTANCE TO BUILDING OPENINGS. | | | | | | 5.PROVIDE MANUFACTURE SPEC SHEETS FOR THE EQUIPMENT. | | | | | | 6.DETAIL HOW THE EQUIPMENT WILL BE PROTECTED FROM | | | VEHICULAR AND / OR MECHANICAL DAMAGE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|