Plan Review Notes
Plan Review Notes For Permit 07050992
Permit Number 07050992
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-08-16 22:41:24*****DENIED*****
  
  
 1.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED WITH COMPLIANCE WITH NFPA
 110.
  
 2.EQUIPMENT USING GAS AND RELATED GAS PIPING SHALL BE
 IN ACCORDANCE WITH NFPA 54.
  
 3.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE
 GENERATOR.
  
 4.PROVIDE PROPER SETBACKS TO PROPERTY LINES AND AT
 LEAST 10' DISTANCE TO BUILDING OPENINGS.
  
 5.PROVIDE MANUFACTURE SPEC SHEETS FOR THE EQUIPMENT.
  
 6.DETAIL HOW THE EQUIPMENT WILL BE PROTECTED FROM
 VEHICULAR AND / OR MECHANICAL DAMAGE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  