| 2007-06-23 16:29:29 | *** UNSAT *** |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT PLANS WITH A COMPLETE LAYOUT OF |
| | ALL EXISTING ELECTRICAL SERVICE EQUIPMENT AT THIS |
| | BUILDING. PLEASE INDICATE ALL MAINS, DISCONNECTS ETC. |
| | AT THIS TIME AS THE LOCATION OF THESE ITEMS ARE NOT |
| | CLEAR, NO REVIEW OF LOCATIONS CAN BE DONE. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC 230.70,230.71,230.72, 225.31-225.39, 702.11 PLEASE |
| | SEE MISSING DISCONNECTING MEANS AS REQUIRED. THIS IS |
| | BASED ON NO INFORMATION PROVIDED. |
| | |
| | 2) NOTE: PLEASE SUBMIT A COMPLETE SURVEY WITH ALL |
| | SETBACKS ON PLANS FOR EQUIPMENT ETC. |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES FOR |
| | THIS. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE KNOW IF THIS IS INDEED IN A FLOOD ZONE, |
| | THE ELEVATION OF UNIT WILL NEED TO BE ON PLANS. PLEASE |
| | KNOW THAT AN ELEVATION CERTIFICATE WILL BE REQUIRED |
| | BEFORE FINAL. |
| | |
| | 4) NOTE: PLEASE SEE LOAD CALCULATIONS MENTIONS 2-WORK |
| | STATIONS AND CONTRACT MENTIONS THREE. THE LOAD ON THE |
| | GENERATOR IS NOT OF A CONCERN HOWEVER PLEASE CORRELATE |
| | FOR RECORD SETS OF PLANS. |
| | FBC 106.1.2 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |