| 2007-07-16 16:43:17 | 3301 ELECTRONIC WAY |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07050992 |
| | ADD: 3301 ELECTRONIC WAY |
| | CONT: SHAFFER ELECTRICAL |
| | TEL: (954)868-9411 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)) GENERATOR SLAB & ANCHOR REQUIREMENTPLEASE |
| | PROVIDE SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS |
| | WITH THE INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE |
| | OF FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE |
| | REQUIRES WITHOUT LOADREDUCTION.SECOND, PROVIDE |
| | INFORMATION ON THE SLAB, THICKNESS, WIDTH AND LENGTH, |
| | IF WIREMESH, FIBER MESH OR IF STEEL REBAR WILL BEUSED. |
| | THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | 4) 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING INFORMATION |
| | RELATED TO WIND SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 5) PROVIDE FLOOD ZONE ELEVATION CERTIFICATE FOR NEW |
| | CONSTRUTION WITH BASE FLOOD ELEVATION, CITY CODE |
| | REQUIRES AN ADDITIONAL 6". |
| | |
| | |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |