Plan Review Notes
Plan Review Notes For Permit 07050991
Permit Number 07050991
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-23 09:19:54-----------------DENIED-------------------
  
 1. PLEASE SHOW ALL NEW STORAGE TANKS AND EQUIPMENT TO
 BE SECURED PER THE WIND LOAD REQUIREMENTS OF FBC 1609
 WITH A WIND LOAD IMPORTANCE FACTOR OF 1.15 AS
 DETERMINED BY FBC TABLE 1604.5 IN ACCORDANCE WITH FBC,M
 301.13.
  
 2. ADDRESS SHOWN ON TITLE BLOCK FOR ENGINEERING FIRM DO
 NOT MATCH DBPR RECORDS UNDER THE CERTIFICATE OF
 AUTHORIZATION. PLEASE UPDATE STATE RECORDS OR CORRECTLY
 SHOW ENGINEERING FIRM ADDRESS ON PLANS PER FAC RULE
 61G15-23.002.
  