| 2007-06-23 09:19:54 | -----------------DENIED------------------- | | | | | | 1. PLEASE SHOW ALL NEW STORAGE TANKS AND EQUIPMENT TO | | | BE SECURED PER THE WIND LOAD REQUIREMENTS OF FBC 1609 | | | WITH A WIND LOAD IMPORTANCE FACTOR OF 1.15 AS | | | DETERMINED BY FBC TABLE 1604.5 IN ACCORDANCE WITH FBC,M | | | 301.13. | | | | | | 2. ADDRESS SHOWN ON TITLE BLOCK FOR ENGINEERING FIRM DO | | | NOT MATCH DBPR RECORDS UNDER THE CERTIFICATE OF | | | AUTHORIZATION. PLEASE UPDATE STATE RECORDS OR CORRECTLY | | | SHOW ENGINEERING FIRM ADDRESS ON PLANS PER FAC RULE | | | 61G15-23.002. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|