| 2007-06-27 08:11:55 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY |
| | OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | _XX_2.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN |
| | PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE |
| | DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A |
| | DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ENGINEER |
| | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED |
| | ORIGINALS FAC61G15-23.002. |
| | |
| | 2ND REVIEW - ORIGINALS REQUIRED.ONE WAS A PHOTOCOPY. |
| | |
| | |
| | _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE |
| | OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT. |
| | |
| | 2ND REVIEW - A SIMILAR FORM WAS SUBMITTED BUT DOES NOT |
| | INLUDE SHUTTER MOUNTING TYPE.CODE COMPLIANCE CANNOT |
| | BE DETERMINED. |
| | |
| | _XX_5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.THE FL |
| | STATE PRODUCT APPROVAL IS EXPIRED, 2001 CODE RATHER |
| | THAN 2004.PLEASE PRINT A CURRENT APPROVAL.IF ONE IS |
| | NOT AVAILABLE, PLEASE ADVISE. |
| | |
| | 2ND REVIEW - NOT ADDRESSED.IN ORDER FOR A LOCAL |
| | PRODUCT APPROVAL TO BE ISSUED, PLEASE SUBMIT THE LETTER |
| | FROM THE ENGINEER WHICH WAS PROVIDED TO MIAMIDADE |
| | STATING THAT THE CALCULATIONS ARE IN ACCORDANCE WITH |
| | FBC2004.NO 33% INCREASE FOR STEEL ALLOWED. |
| | |