| 2007-11-05 09:10:24 | CONSTRUCTION SERVICES DEPARTMENT |
| | 200 SECOND STREET, 3RD FLOOR, |
| | WEST PALM BEACH, FLORIDA33401 |
| | TEL:561-805-6713FAX:561-805-6731 |
| | |
| | JAMES JOHNSTON, |
| | BUILDING PLAN EXAMINER II |
| | E-MAIL:JJOHNSTON @WPB.ORG |
| | |
| | |
| | PERMIT NO 07050952 |
| | PROJECT NORTHWOOD HOLDINGS |
| | ADDRESS439 NORTHWOOD DRIVE |
| | DATE NOVEMBER 2, 2007 |
| | |
| | |
| | BUILDINGPLANREVIEW |
| | |
| | FLORIDA BUILDING CODES 2004 W REVISIONS |
| | |
| | FLORIDA STATUE713.13NOTICE OF COMMENCEMENT |
| | FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION. |
| | |
| | IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED |
| | WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL |
| | AND VOID. |
| | SUBMIT THE NOTICE AT THE TIME OF PERMIT ISSUANCE |
| | AND POST A COPY AT THE JOB SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | COMMENT-FOR YOUR INFORMATION |
| | |
| | |
| | 1 |
| | FLORIDA ADMINISTRATIVE CODE61G15-23.002 SEAL, |
| | SIGNATURE AND DATE SHALL BE AFFIXED. |
| | (2)IF PRACTICING THROUGH A DULY AUTHORIZED |
| | ENGINEERING |
| | BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME |
| | AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING |
| | BUSINESS ON EACH SHEET. |
| | |
| | COMMENT |
| | A. PROVIDE THE CERTIFICATE OF AUTHORIZATION NUMBER |
| | IN THE TITLE BLOCK FOR THE BUSINESS |
| | |
| | B THE BUSINESS ADDRESS ON FILE WITH THE STATE OF |
| | FLORIDA |
| | DBPRDOES NOT MATCH THE ADDRESS IN THE TITLE BLOCK. |
| | PLEASE NOTIFY THE STATE AND PROVIDE THE CORRECT |
| | INFORMATION |
| | |
| | |
| | 2 |
| | FLORIDA ADMINISTRATIVE CODE61G1-16.002 |
| | DOCUMENTS SIGNED AND SEALED |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONALAND BEING |
| | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT WITH THE DATE. |
| | |
| | COMMENT-DESIGNEROF RECORD MUST ACKNOWLEDGE |
| | THE PRODUCT APPROVALS FOR ACCEPTANCE OF USE ON THIS |
| | PROJECT WITH A STATEMENT THAT ?THEY HAVE REVIEWED THE |
| | PRODUCT APPROVAL FOR COMPLIANCE WITH THIS PROJECT AND |
| | FOUND IT ACCEPTABLE FOR THE INTENDED USE? |
| | |
| | |
| | 3 |
| | FLORIDA STATUE471.025ENGINEER SEAL |
| | ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, OR |
| | |
| | DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND |
| | BEING FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS |
| | PROVIDED TO THE OWNER OR THE OWNER'S REPRESENTATIVE |
| | SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED |
| | WITH SAID SEAL. |
| | SUCH SIGNATURE, DATE, AND SEAL SHALL BE EVIDENCE OF THE |
| | |
| | AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED. |
| | |
| | COMMENT |
| | THEENGINEER CANNOT SEAL DOCUMENTS (PRODUCT |
| | APPROVALS) THAT WERE NOT PREPARED BY THE ENGINEER. |
| | PLEASE SUBMIT NEW PRODUCT APPROVALS WITH THE STATEMENT |
| | |
| | THEY HAVE REVIEWED THE PRODUCT FOR COMPLIANCE |
| | WITH THIS PROJECT AND FOUND IT ACCEPTABLE |
| | FOR ITS INTENDED USE |
| | |
| | 4 |
| | PRODUCT APPROVALS REQUIRED |
| | FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3 |
| | REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS |
| | SUBMIT TWO COPIES OF EACH APPROVAL WITH |
| | FLORIDA PRODUCT APPROVAL COVER |
| | |
| | COMMENT-SUBMIT THE FLORIDA PRODUCT APPROVAL WITH |
| | THE MIAMI-DADE PRODUCT APPROVAL |
| | ROOF SYSTEM |
| | METAL ROOF PANELS |
| | |
| | |
| | 5 |
| | FBC BUILDING11-4.1.5 ACCESSIBLE BUILDINGS: ADDITIONS. |
| | |
| | EACH ADDITION TO AN EXISTING BUILDING OR FACILITY SHALL |
| | |
| | BE REGARDED AS AN ALTERATION. EACH SPACE OR ELEMENT |
| | ADDED TO THE EXISTING BUILDING OR FACILITY SHALL |
| | COMPLY |
| | WITH THE APPLICABLE PROVISIONS. |
| | COMMENT |
| | PROVIDE A DETAIL OF THE ACCESSIBLE ROUTEBETWEEN THE |
| | FRONT OF THE BUILDING AND THE SIDEWALK. |
| | |
| | |
| | 6 |
| | FBC BUILDING2304.6.1 WOOD STRUCTURAL PANEL |
| | SHEATHING. |
| | WHERE WOOD STRUCTURAL PANEL SHEATHING IS USED AS |
| | THE EXPOSED FINISH ON THE EXTERIOR OF OUTSIDE WALLS, |
| | IT SHALL HAVE AN EXTERIOR EXPOSURE DURABILITY |
| | CLASSIFICATION |
| | |
| | COMMENT |
| | PROVIDE THE INFORMATION FOR THE 1/2? PLYWOOD |
| | SHEATHING ON THE BACK OF THE PARAPETWALL FOR |
| | CLASSIFICATION DURABILITY, PREVENTING LEAKAGE AT THE |
| | SEAMS, |
| | TYPE OF EXPOSED FASTENER AND FINISH FOR EXPOSED |
| | SHEATHING AND RUST PREVENTION. |
| | TYPE OF SCREW AND FINISH BEING USED TO FASTEN 2? X 4? |
| | MEMBER HORIZONTALLY |
| | |
| | |
| | 7 |
| | FBC BUILDING2512 EXTERIOR PLASTER |
| | |
| | COMMENT |
| | PROVIDE THE STUCCO SYSTEM TO BE USED ON THE FRONT |
| | PARAPET WALL AS DEFINED IN THIS SECTION, INCLUDING |
| | THE TYPE OF METAL LATH AND PAPER, TYPE OF CEMENT, |
| | TYPE AND NUMBER OF APPLIED COATS, TYPE OF FASTENER, |
| | SPACING OF FASTENER |
| | |
| | |
| | |
| | 8 |
| | FBC BUILDING2211.2.2.2 WOOD STRUCTURAL PANEL |
| | SHEATHING |
| | |
| | COMMENT |
| | IDENTIFY THE TYPE OF 22 GAUGE METAL STUD USED FOR |
| | STRUCTURAL SUPPORT AND THE HORIZONTAL WIND LOAD OF |
| | THE PARAPET WALL. |
| | |
| | |
| | |
| | 9 |
| | FBC BUILDINGSECTION 1503 |
| | PROVIDE THE ROOF COVERING SYSTEM TO BE USED FOR THE |
| | METAL ROOF SYSTEM AND THE RE-SURFACING OF THE EXISTING |
| | ROOF. |
| | PROVIDE FLASHING AND PITCH PAN DETAILS |
| | |
| | |
| | |
| | |
| | 10 |
| | FBC BUILDING15.00 |
| | |
| | COMMENT |
| | THE ROOF PITCH 1/1DOES NOT EXIST |
| | PLEASE SEE THE RISE AND RUN CHART PROVIDED WITH THIS |
| | CRITIQUE |
| | |
| | 11 |
| | THE ITEMS LISTED BELOR ARE THE PLAN REVIEWERS |
| | PREVIOUS COMMENTS NOT ADDRESSED |
| | |
| | |
| | 1 NOTED |
| | 2 NOTED |
| | 3 NOT IN COMPLIANCE |
| | 4 NOTED |
| | 5 NOTED |
| | 6 COMPLIED |
| | 7 COMPLIED |
| | 9 COMPLIED |
| | 10 COMPLIED |
| | 11 COMPLIED |
| | 12 COMPLIED |
| | 13 COMPLIED |
| | 14 COMPLIED |
| | 15 SEE NOTES |
| | 16 COMPLIED |
| | 17 NOT IN COMPLIANCE |
| | 18 COMPLIED NEED FLORIDA PRODUCT APPROVALS |
| | 19 SEE NOTES |
| | 20 SEE NOTES |
| | 21 COMPLIED |
| | 22 OUT-SWING DOOR NEEDS PROTECTION |
| | 23 COMPLIED |
| | 24 NOT IN COMPLIANCE |
| | 25 NOT IN COMPLIED |
| | 26 NOT IN COMPLIANCE |
| | 27 COMPLIED |
| | 28 NOTED |