| 2007-06-23 19:35:48 | *** UNSAT*** |
| | |
| | ** PLEASE KNOW AS PLANS WERE NOT SUBMITTED WITH ALL |
| | COMPLETED INFORMATION FOR CODE COMPLIANCE REVIEW THERE |
| | MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| | |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 3) NOTE PLEASE SEE THE PLANS MAY NOT BE DONE BY A |
| | *DESIGNER* WHO IS NOT LICENSED UNDER FS 481 OR 471. |
| | PLEASE SEE THE STATEMENT FROM THE ENGINEER DOES NOT |
| | COVER THE DESIGNER AS SHOWN ON TITLE BLOCKS PER THE |
| | LAWS UNDER THE FLORIDA STATUTES. IF THERE ARE ANY |
| | FURTHER QUESTIONS ON THIS PLEASE CONTACT THE STATE |
| | LEGAL COUNSEL TO THE BOARD OF ARCHITECTS AS WELL AS THE |
| | FLORIDA BOARD OF ENGINEERS. |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND TRADES WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER TRADE(S). |
| | |
| | 4) NOTE: PLEASE SEE THE SCOPE OF WORK IS UNCLEAR AS THE |
| | TITLE BLOCKS AND LOCATIONS ON PLANS INDICATE THIS AS A |
| | RESIDENCE YET THE PLANS AND LOCATION ARE ALSO |
| | COMMERCIAL STORES. |
| | PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR CHANGE IN |
| | OCCUPANCY, PLEASE SUBMIT ELECTRICAL PLANS AND SHOW ALL |
| | NEW AND EXISTING WHICH ALREADY COMPLIES OR WILL COMPLY |
| | WITH THE CODES ABOVE. |
| | PLEASE SEE FBC ADMIN SECTION 106.1, 106.3.5.1.2, 106.2 |
| | |
| | 5) NOTE: PLEASE SEE NEC , 215.3, 215.5, 230.70, 230.71, |
| | 230.76, 230.79, 240.4, 310.16, 408.4, 600.5, 220.12, |
| | 220.14, 220.42, 220.44, ETC. |
| | |
| | 6) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS AS |
| | LIGHTING INFORMATION NEEDS TO COMPLY WITH THE ENERGY |
| | CODE. |
| | 13-415.1.AB.1.1, 13-415.1.C, 13-415.2 ETC. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |