| 2007-07-16 11:01:53 | 439 NORTHWOOD RD, LOT 261 07050952 |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07050952 |
| | ADD: 439 NORTHWOOD RD |
| | CONT: KDN CONSTRUCTION SERVICES, LLC |
| | TEL: (561)662-1002 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL.S. S. 713.13 NOTICE OF COMMENCEMENT, TO BE |
| | FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF |
| | THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE FL |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS |
| | A RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | NEITHER THE PERMIT APPLICATION NOR THE PLAN INDICATES |
| | THIS IS A CHANGE OF OCCUPANCY. SITE PLAN INDICATES THIS |
| | IS A RESIDENCY WHILE SHEET 1 INDICATES IT IS A DETACHED |
| | GARAGE W/ LOFT? IT APPEARS THAT THIS IS A CHANGE OF |
| | OCCUPANCY FROM A RESIDENCE TO POSSIBLY BUSINESS OR |
| | MERCANTILE? PLEASE PROVIDE ADDITIONAL INFORMATION. |
| | 106.1.2. |
| | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT |
| | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT WAS |
| | DESIGNED. |
| | 2004 FBC BUILDING W/ 2006 AMENDMENTS |
| | 2004 EXISTINGBUILDING CODE W? 2006 AMENDMENTS LIST TO |
| | WHAT LEVEL OF ALTERATIONS WILL BE COMPLETED UNDER THIS |
| | PERMIT? |
| | EXISTING BUILDING CODE : CHAPTER 8 CHANGE OF OCCUPANCY |
| | : CHAPTER 9 ADDITIONS |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED. |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT. |
| | H) TOTAL SQ FT UNDER ROOF |
| | |
| | 4) 109.3.10* IMPACT OF CONSTRUCTION.ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY |
| | THE APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED |
| | TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE |
| | FINAL INSPECTION. |
| | |
| | 5) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION |
| | TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 6) SHEET 4 INDICATES TWO SEPARATE UNITS LOT 26 & 27, |
| | WITH A COMMON WALL. THIS IS A SHARED BEARING WALL OR |
| | FIRE WALL BETWEEN TWO LOTS OR PROPERTIES REQUIRING |
| | RATINGS OF WALL AND ROOFDECKING . 705.1 WHERE A FIRE |
| | WALL ALSO SEPARATES GROUPS THAT ARE REQUIRED TO BE |
| | SEPARATED BY A FIRE BARRIER WALL, THE MOST RESTRICTIVE |
| | REQUIREMENTS OF EACH SEPARATION SHALL APPLY. FIRE WALLS |
| | LOCATED ON LOT LINES SHALL ALSO COMPLY WITH SECTION |
| | 503.2 . SUCH FIRE WALLS (PARTY WALLS) SHALL PROVIDE A |
| | 4-HOUR FIRE-RESISTANCE RATING AND SHALL BE CONSTRUCTED |
| | WITHOUT OPENINGS. |
| | |
| | 7)FIRE WALLS OR PARTY WALLS,705.5 HORIZONTAL |
| | CONTINUITY. |
| | FIRE WALLS SHALL BE CONTINUOUS FROM EXTERIOR WALL TO |
| | EXTERIOR WALL AND SHALL EXTEND AT LEAST 18 INCHES (457 |
| | MM) BEYOND THE EXTERIOR SURFACE OF EXTERIOR WALLS. |
| | EXCEPTIONS: |
| | 1.FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT |
| | THE INTERIOR SURFACE OF COMBUSTIBLE EXTERIOR SHEATHING |
| | OR SIDING PROVIDED THE EXTERIOR WALL HAS A |
| | FIRE-RESISTANCE RATING OF AT LEAST 1 HOUR FOR A |
| | HORIZONTAL DISTANCE OF AT LEAST 4 FEET (1220 MM) ON |
| | BOTH SIDES OF THE FIRE WALL . OPENINGS WITHIN SUCH |
| | EXTERIOR WALLS SHALL BE PROTECTED BY FIRE ASSEMBLIES |
| | HAVING A FIRE PROTECTION RATING OF NOT LESS THAN ? |
| | HOUR. |
| | 2.FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT |
| | THE INTERIOR SURFACE OF NONCOMBUSTIBLE EXTERIOR |
| | SHEATHING, EXTERIOR SIDING OR OTHER NONCOMBUSTIBLE |
| | EXTERIOR FINISHES PROVIDED THE SHEATHING, SIDING, OR |
| | OTHER EXTERIOR NONCOMBUSTIBLE FINISH EXTENDS A |
| | HORIZONTAL DISTANCE OF AT LEAST 4 FEET (1220 MM) ON |
| | BOTH SIDES OF THE FIRE WALL . |
| | 3.FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT |
| | THE INTERIOR SURFACE OF NONCOMBUSTIBLE EXTERIOR |
| | SHEATHING WHERE THE BUILDING ON EACH SIDE OF THE FIRE |
| | WALL IS PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM |
| | INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR |
| | 903.3.1.2 . |
| | |
| | 9) PLEASE PROVIDE AN EXPLANATION WHY THERE IS NO BEAMS |
| | OR BEARING WALLS BEING REMOVED DOWN THE CENTER OF THE |
| | BUILDING ON THE DEMO SHEET BUT NEW COLUMNS AND LVL'S |
| | ARE BEING REPLACED? |
| | |
| | 10) SHEET# 8 ALSO HAS INK HAND DRAWN CHANGES ADDED TO |
| | THIS SHEET. |
| | |
| | 11) DISCREPANCY, SHEET# 8 INDICATES 3 NEW MASONARY |
| | COLUMNS THAT DO NOT SHOW ON SHEET 8 DETAIL# 2. |
| | |
| | 12) SHEET 8 DETAIL# 2 ALSO INDICATES THE USE OF 3 1/2" |
| | 22 GAUGE METAL STUDS FOR FRAMING, ISN'T THIS CONSIDERD |
| | LIGHT GAUGE METAL AND NOT FOR STRUCTURALAPPLICATION? |
| | |
| | 13) BENEATH THE HORIZONTAL FRAMING MEMBERS THERE |
| | APPEARS TO BE METAL SLEEPERS THA WILL BE ATTACHED TO |
| | THE EXISTING CONCRETE DECK, IS THIS A SINGLE MEMBER |
| | STEEL STUD OR TWO MEMBERS CREATING A BOX BEAM? PROVIDE |
| | MORE INFORMATION? |
| | |
| | 14) ON SHEET 8 DETAIL# 2 PLEASE INDICATE WHERE THE |
| | PROPERTY LINE IS LOCATED? |
| | |
| | 15) 11-4.1.5 ACCESSIBLE BUILDINGS: ADDITIONS. |
| | EACH ADDITION TO AN EXISTING BUILDING OR FACILITY SHALL |
| | BE REGARDED AS AN ALTERATION. EACH SPACE OR ELEMENT |
| | ADDED TO THE EXISTING BUILDING OR FACILITY SHALL COMPLY |
| | WITH THE APPLICABLE PROVISIONS OF SECTION 11-4.1.1 TO |
| | SECTION 11-4.1.3 , MINIMUM REQUIREMENTS FOR NEW |
| | CONSTRUCTION, AND THE APPLICABLE TECHNICAL |
| | SPECIFICATIONS OF SECTION 11-4.2 THROUGH SECTION |
| | 11-4.35 AND SECTION 11-5 THROUGH SECTION 11-10 . EACH |
| | ADDITION THAT AFFECTS OR COULD AFFECT THE USABILITY OF |
| | AN AREA CONTAINING A PRIMARY FUNCTION SHALL COMPLY WITH |
| | SECTION 11-4.1.6 (2). |
| | (2)ALTERATIONS TO AN AREA CONTAINING A PRIMARY |
| | FUNCTION. IN ADDITION TO THE REQUIREMENTS OF SECTION |
| | 11-4.1.6 (1), AN ALTERATION THAT AFFECTS OR COULD |
| | AFFECT THE USABILITY OF OR ACCESS TO AN AREA CONTAINING |
| | A PRIMARY FUNCTION SHALL BE MADE SO AS TO ENSURE THAT, |
| | TO THE MAXIMUM EXTENT FEASIBLE, THE PATH OF TRAVEL TO |
| | THE ALTERED AREA AND THE RESTROOMS, TELEPHONES, AND |
| | DRINKING FOUNTAINS SERVING THE ALTERED AREA, ARE |
| | READILY ACCESSIBLE TO AND USABLE BY INDIVIDUALS WITH |
| | DISABILITIES, UNLESS SUCH ALTERATIONS ARE |
| | DISPROPORTIONATE TO THE OVERALL ALTERATIONS TIN TERMS |
| | OF COST AND SCOPE. |
| | 11-4.1.6(2)ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE |
| | PATH OF TRAVEL TO ALTERED AREAS SHALL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION |
| | TO THE PRIMARY FUNCTION AREA. |
| | DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY. |
| | (1)WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE |
| | THE PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE |
| | IS DISPROPORTIONATE TO THE COST OF THE OVERALL |
| | ALTERATION, THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE |
| | TO THE EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT |
| | INCURRING DISPROPORTIONATE COSTS. |
| | (2)(A)IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| | PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| | THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| | ORDER: |
| | (I)AN ACCESSIBLE ENTRANCE ; |
| | (II)AN ACCESSIBLE ROUTE TO THE ALTERED AREA: (III) |
| | AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A |
| | SINGLE UNISEX RESTROOM: |
| | (IV)ACCESSIBLE TELEPHONES; |
| | (V)ACCESSIBLE DRINKING FOUNTAINS; AND |
| | (VI)WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS |
| | SUCH AS PARKING, STORAGE, AND ALARMS. |
| | |
| | 13) THE SITE PLAN DOESN?T INDICATE THE HANDICAPPED |
| | PARKING WITH AN ACCESSIBLE AISLE, WALKWAY TO THE |
| | ENTRANCE OF THE UNIT. PLEASE PROVIDE THE DETAILS. |
| | 11-4.6.3 PARKING SPACES. PARKING ACCESS AISLES MUST BE |
| | NO LESS THAN 5 FEET (1524 MM) WIDE AND MUST BE PART OF |
| | AN ACCESSIBLE ROUTE TO THE BUILDING OR FACILITY |
| | ENTRANCE. TWO ACCESSIBLE SPACES MAY SHARE A COMMON |
| | ACCESS AISLE [SEE FIGURE 9 (A)]. THE ACCESS AISLE SHALL |
| | BE STRIPED DIAGONALLY TO DESIGNATE IT AS A NO-PARKING |
| | ZONE. CURB RAMPS MUST BE LOCATED OUTSIDE OF THE |
| | DISABLED PARKING SPACES AND ACCESS AISLES. |
| | |
| | 16) DISCREPANCY, PLEASE SEE SHEET# 6DETAIL1 SHEET7 IS |
| | REVERSED WITH DETAIL1 SHEET 8. PLEASE PROVIDE A |
| | CONNECTION DETAIL OF THE NEW 5 1/4X 16 LVL BEAM AT BOTH |
| | ENDS. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 17)1203.2 ATTIC SPACES. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH |
| | SEPARATE SPACE BY VENTILATING OPENINGS PROTECTED |
| | AGAINST THE ENTRANCE OF RAIN. BLOCKING AND BRIDGING |
| | SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH THE |
| | MOVEMENT OF AIR. A MINIMUM OF 1 INCH (25 MM) OF |
| | AIRSPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND |
| | THE ROOF SHEATHING. |
| | |
| | 18) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE PROVISIONS |
| | OF THE SMALL MISSILE TEST. |
| | |
| | FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT |
| | INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS |
| | ARE AS FOLLOWS: |
| | A) FIXED WINDOWS- STOREFRONT GLASS |
| | B) GLAZED SWING DOORS |
| | C) HOLLOW CORE METAL DOORS |
| | D) MULLIONS |
| | E) TRUSS ANCHOR STRAPS AND CONNECTIONS |
| | F) STORM SHUTTERS |
| | G) PRE-ENGINEEREDA/C STANDS |
| | H)ROOF ASSEMBLIES |
| | |
| | 19) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WW.FLORIDABUILDING.ORG |
| | |
| | 20) ) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 21) THE MIAMI-DADE PRODUCT APPROVAL REPORTS THAT WERE |
| | TESTED BEFORE 2004 FBC WILL NEED TO BE REVIEWED BY AN |
| | ENGINEER TO SEE IF REDUCTIONS NEED TO BE TAKEN. 2004 |
| | FBC 1605.3.1.1 DO NOT ALLOW FOR THE 1/3RD INCREASES |
| | THAT HAD BEEN TAKEN WHEN THE PRODUCTS WERE TESTED .THE |
| | PRODUCTS MAY REQUIRE ADDITIONAL FASTENERS. SEE |
| | CALCULATIONS LISTED UNDER SUB HEADING# 3 ON THE PRODUCT |
| | APPROVALS, IF THE 2004 CODE IS NOT REFERENCED AN |
| | ENGINEER WILL NEED TO VERIFY LOADING OF FASTENERS!!!! |
| | 1605.3.1.1 LOAD REDUCTION. |
| | 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT |
| | OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE |
| | EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN |
| | SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD |
| | LOAD AND ANY OF THE VARIABLE LOADS. |
| | 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE |
| | MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED |
| | STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD |
| | COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD |
| | INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER |
| | 23 . |
| | |
| | 22)PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED FOR ALL |
| | NON-IMPACT GLAZING. FBC 1606.1.4. |
| | |
| | 23) FL BLD CODE 2001 SECTION 103.6, 1606.1.4, 1707.4 |
| | & 3401.7.2.4. PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT |
| | SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS, |
| | WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE |
| | PLAN REVIEW AND PERMIT ISSUANCE. |
| | 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE |
| | DEBRIS IMPACT PROTECTION |
| | QUESTION# 13 RECOGNIZING SUCH CONCERNS AS ABSENTEE |
| | OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS |
| | NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY |
| | BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR |
| | IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR |
| | SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE |
| | HURRICANE? |
| | |
| | IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE |
| | GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE, |
| | SECTION 104.6 OF THE FLORIDA BUILDING CODE,BUILDING, |
| | CHAPTER 1, |
| | ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY |
| | OF WEST PALM BEACH, PROVDES THE ABILITY FOR THE |
| | BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR |
| | ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION |
| | OF EXISTING BUILDINGS. |
| | |
| | IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR |
| | MULTI-STORY BUILDINGS, OR MULTIPLE BUILDINGS ON THE |
| | SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST BE |
| | SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS FOR |
| | REVIEW BY THE CONSTRUCTION SRVICES DEPARTMENT. ANY SUCH |
| | PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION OF |
| | THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE |
| | SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH |
| | COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND |
| | THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS. |
| | PROTECTION OF OPENINGS SHALL BE ACCOMPLISHEDWITHIN |
| | TWELVE (12) HOURS OR LESS OF THE |
| | OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES |
| | OF A HURRICANE WATCH. |
| | |
| | PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| | ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE |
| | MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO |
| | REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN |
| | QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, |
| | DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED |
| | UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE |
| | MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE |
| | BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO |
| | SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. |
| | |
| | 24)THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH |
| | THE FOLLOW ITEMS: |
| | _XXX__ CONTRACTOR / ENGINEER DID NOT INDICATE THE ROOF |
| | PITCH. |
| | |
| | _XXX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE |
| | USED. |
| | |
| | _XXX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR |
| | ZONE _2&3__ . |
| | |
| | |
| | _XXX__ NOT KNOWN- THE SYSTEM PROVIDED STATES |
| | LIMITATION# 7, SHOULD THE FASTENERRESISTANCE BE |
| | LESS THAN THATREQUIRED, AS DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISEDFASTENER SPACING, |
| | PREPARED , SIGNEDAND SEALED BY A FLORIDA |
| | REGISTEREDPROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | __XXX_ NOT KNOWN- THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | |
| | 25) PLANS DO NOT SHOW ANY ROOF DRAINAGE, SLOPE OR |
| | EMERGENCY OVERFLOWS: |
| | |
| | 1503.4.1 GUTTERS. |
| | GUTTERS AND LEADERS PLACED ON THE OUTSIDE OF BUILDINGS, |
| | OTHER THAN GROUP R-3 AS APPLICABLE IN SECTION 101.2 , |
| | PRIVATE GARAGES AND BUILDINGS OF TYPE V CONSTRUCTION, |
| | SHALL BE OF NONCOMBUSTIBLE MATERIAL OR A MINIMUM OF |
| | SCHEDULE 40 PLASTIC PIPE. |
| | |
| | 1503.4.2 SCUPPER. |
| | WHERE REQUIRED FOR ROOF DRAINAGE, A SCUPPER SHALL BE |
| | PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR |
| | PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY |
| | THE SLOPE AND THE CONTRIBUTING AREA OF THE ROOF. THE |
| | EXTERIOR FACING OR LINING OF A SCUPPER, IF METAL, SHALL |
| | BE THE SAME AS FLASHING MATERIAL REQUIRED BY SECTIONS |
| | 1503 THROUGH 1510 FOR THE PARTICULAR TYPE OF COVERING |
| | SPECIFIED FOR THE BUILDING. FOR OTHER TYPE MATERIALS, |
| | FOLLOW MANUFACTURER?S SPECIFICATIONS. |
| | |
| | 1503.4.3 OVERFLOW SCUPPERS. |
| | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT |
| | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR |
| | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 |
| | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND |
| | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| | VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET |
| | SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. |
| | |
| | 26) PLANS ALSO FAIL TO PROVIDE ENERGY CALCULATIONS. |
| | |
| | 27) IF THIS IS NOT A RESIDENCEON TARGET DESIGN CAN |
| | NOT WORK AS DESIGNER OF RECORD, PLEASE SEE DEPARTMENT |
| | OF BUSINESS & PROFESSIONAL REGULATION, DIVISION OF |
| | ADMINISTRATION CASE HEARING 03-0489!!!! THIS MAY EFFECT |
| | ENGINEER RIZA ALTANS LICENSURE ALSO!!! |
| | |
| | 28)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW II |