| Date |
Text |
| 2008-02-05 11:15:59 | 433 NORTHWOOD RD, |
| | LOT 29/ 07050950 |
| | FEB.05,2008 |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07050950 |
| | ADD: 433 NORTHWOOD RD |
| | CONT: KDN CONSTRUCTION SERVICES, LLC |
| | TEL: (561)662-1002 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) --- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL. S. S. 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE FL |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) IT APPEARS THERE ARE TWO PERMIT APPLICATIONS ( 433 |
| | NORTHWOOD LOT 29 PERMIT # 07050950 & 435 NORTHWOOD LOT |
| | 28 PERMIT 07050947) . PLEASE REVIEW YOUR PERMIT |
| | APPLICATION FOR THIS JOB: |
| | A) UNDER THE PERMIT NUMBER 07050950 WE USE THE PCN TO |
| | IDENTIFY THE LOT AND ADDRESS. THIS PERMIT APPLICATION |
| | INDICATES WORK UNDER THIS PERMIT IS TO TAKE PLACE ON |
| | LOT 29 WHICH IS 433 NORTHWOOD. THE PERMIT APPLICATION |
| | INDICATES WORK TO BE COMPLETED UNDER ADDRESS 433 & 435, |
| | ONLY WORK ON ONE LOT CAN BE COVERED UNDER THIS PERMIT |
| | FOR LOT 29. |
| | B) IF THE IDEA OF ADJOINING THE LOTS 28 & 29 INTO ONE |
| | LOT AND WORK TO BE COMPLETED UNDER A SINGLE PERMIT AND |
| | A SINGLE ADDRESS , THIS CAN BE ACCOMPLISHED BY A UNITY |
| | OF TITLE. THERE MAY BE OTHER ISSUES THAT MAY ARISE, (2) |
| | ELECTRIC RISERS AND METERS ON A SINGLE BUILDING, MAY BE |
| | A ISSUE? |
| | C) THE SHEET# 1 DOES NOT CORRELATE WITH THE PERMIT |
| | APPLICATION, THE PERMIT APPLICATION INDICATES LOT# 29 |
| | WHERE AS THE PLANS INDICATE SHEET # 1, LOT# 28. |
| | 106.1.2, ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 4) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | PLEASE PROVIDE ADDITIONAL INFORMATION. 106.1.2, 110.2* |
| | W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT IS |
| | REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT WAS |
| | DESIGNED. |
| | 2004 FBC BUILDING W/ 2006 AMENDMENTS |
| | 2004 EXISTING BUILDING CODE WITH? 2006 AMENDMENTS |
| | LIST TO WHAT LEVEL OF ALTERATIONS WILL BE COMPLETED |
| | UNDER THIS PERMIT? |
| | EXISTING BUILDING CODE : CHAPTER 8 CHANGE OF OCCUPANCY |
| | : CHAPTER 9 ADDITIONS |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503 & |
| | CHAPTER 6, TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED. |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT. |
| | H) TOTAL SQ FT UNDER ROOF |
| | |
| | 5) NOTE INFORMATIONAL, 109.3.10* IMPACT OF |
| | CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY |
| | THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO |
| | ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY, |
| | UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY |
| | THE APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED |
| | TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE |
| | FINAL INSPECTION. |
| | |
| | 6) NOTE INFORMATIONAL, 109.3.10.1 HURRICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW |
| | CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO |
| | REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND |
| | DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION |
| | SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE |
| | DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND |
| | DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| | WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR |
| | SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS |
| | WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO |
| | THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 7)PLEASE PROVIDE THE WALL RATING BETWEEN LOTS 28 & 29. |
| | SHEETS 2 & 3 INDICATES TWO SEPARATE UNITS LOT 28 & 29, |
| | WITH A COMMON WALL. THIS IS A SHARED BEARING WALL OR |
| | FIRE WALL BETWEEN TWO LOTS OR PROPERTIES REQUIRING |
| | RATINGS OF WALL AND ROOF DECKING . 705.1 WHERE A FIRE |
| | WALL ALSO SEPARATES GROUPS THAT ARE REQUIRED TO BE |
| | SEPARATED BY A FIRE BARRIER WALL, THE MOST RESTRICTIVE |
| | REQUIREMENTS OF EACH SEPARATION SHALL APPLY. FIRE WALLS |
| | LOCATED ON LOT LINES SHALL ALSO COMPLY WITH SECTION |
| | 503.2 . SUCH FIRE WALLS (PARTY WALLS) SHALL PROVIDE A |
| | 4-HOUR FIRE-RESISTANCE RATING AND SHALL BE CONSTRUCTED |
| | WITHOUT OPENINGS. |
| | |
| | 8)FIRE WALLS OR PARTY WALLS, 705.5 HORIZONTAL |
| | CONTINUITY. |
| | FIRE WALLS SHALL BE CONTINUOUS FROM EXTERIOR WALL TO |
| | EXTERIOR WALL AND SHALL EXTEND AT LEAST 18 INCHES (457 |
| | MM) BEYOND THE EXTERIOR SURFACE OF EXTERIOR WALLS. |
| | EXCEPTIONS: |
| | 1. FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT THE |
| | INTERIOR SURFACE OF COMBUSTIBLE EXTERIOR SHEATHING OR |
| | SIDING PROVIDED THE EXTERIOR WALL HAS A FIRE-RESISTANCE |
| | RATING OF AT LEAST 1 HOUR FOR A HORIZONTAL DISTANCE OF |
| | AT LEAST 4 FEET (1220 MM) ON BOTH SIDES OF THE FIRE |
| | WALL . OPENINGS WITHIN SUCH EXTERIOR WALLS SHALL BE |
| | PROTECTED BY FIRE ASSEMBLIES HAVING A FIRE PROTECTION |
| | RATING OF NOT LESS THAN ? HOUR. |
| | 2. FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT THE |
| | INTERIOR SURFACE OF NONCOMBUSTIBLE EXTERIOR SHEATHING, |
| | EXTERIOR SIDING OR OTHER NONCOMBUSTIBLE EXTERIOR |
| | FINISHES PROVIDED THE SHEATHING, SIDING, OR OTHER |
| | EXTERIOR NONCOMBUSTIBLE FINISH EXTENDS A HORIZONTAL |
| | DISTANCE OF AT LEAST 4 FEET (1220 MM) ON BOTH SIDES OF |
| | THE FIREWALL. |
| | 3. FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT THE |
| | INTERIOR SURFACE OF NONCOMBUSTIBLE EXTERIOR SHEATHING |
| | WHERE THE BUILDING ON EACH SIDE OF THE FIRE WALL IS |
| | PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 . |
| | |
| | 9) IF THE OWNER ELECTS TO COMBINE THE TWO LOTS INTO ONE |
| | WITH A UNITY OF TITLE THE FIRE WALL WILL NOT BE |
| | REQUIRED, BUT HIS WOULD BECOME A STIPULATION THAT WOULD |
| | OCCUR ON THE PROPERTY CONTROL NUMBER, THAT THERE COULD |
| | NOT BE A LOT SPLIT WITHOUT THE REQUIRED FIRE RATINGS |
| | FOR A FIRE WALL IN PLACE ALREADY! SEE (4G). |
| | |
| | 10) THE PERMIT APPLICATION INDICATES ALTERATIONS AND A |
| | ADDITION WHERE AS THE PLANS SHEET 1 UNDER SCOPE OF WORK |
| | INDICATES THIS TO BE A SHELL PERMIT ONLY. PLEASE NOTE |
| | THERE ARE NO PLANS FOR FUTURE PLUMBING OR EXISTING |
| | PLUMBING ( WASTE) FOR A FUTURE RESTROOMS? 106.1.2. |
| | |
| | 11) THE SITE PLAN DOESN?T INDICATE THE HANDICAPPED |
| | PARKING WITH AN ACCESSIBLE AISLE, WALKWAY TO THE |
| | ENTRANCE OF THE UNIT. PLEASE PROVIDE THE DETAILS. |
| | 11-4.6.3 PARKING SPACES. PARKING ACCESS AISLES MUST BE |
| | NO LESS THAN 5 FEET (1524 MM) WIDE AND MUST BE PART OF |
| | AN ACCESSIBLE ROUTE TO THE BUILDING OR FACILITY |
| | ENTRANCE. TWO ACCESSIBLE SPACES MAY SHARE A COMMON |
| | ACCESS AISLE [SEE FIGURE 9 (A)]. THE ACCESS AISLE SHALL |
| | BE STRIPED DIAGONALLY TO DESIGNATE IT AS A NO-PARKING |
| | ZONE. CURB RAMPS MUST BE LOCATED OUTSIDE OF THE |
| | DISABLED PARKING SPACES AND ACCESS AISLES. |
| | |
| | |
| | 12) 1203.2 ATTIC SPACES. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH |
| | SEPARATE SPACE BY VENTILATING OPENINGS PROTECTED |
| | AGAINST THE ENTRANCE OF RAIN. BLOCKING AND BRIDGING |
| | SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH THE |
| | MOVEMENT OF AIR. A MINIMUM OF 1 INCH (25 MM) OF |
| | AIRSPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND |
| | THE ROOF SHEATHING. |
| | |
| | 13) SHEET# 4, THE NEW FA?ADE BRACING IS INDICATED TO BE |
| | ANCHORED WITH LAG BOLTS THROUGH 2X8 INTO THE ROOF |
| | FRAMING MEMBERS, BUT THE PLANS DO NOT INDICATE HOW THIS |
| | AREA WILL BE MAINTAINED AS A WATER TIGHT ROOFING |
| | SYSTEM. 1503.1. |
| | |
| | 14) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE PROVISIONS |
| | OF THE SMALL MISSILE TEST. |
| | |
| | FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT |
| | INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS |
| | ARE AS FOLLOWS: |
| | A) FIXED WINDOWS- STOREFRONT GLASS |
| | B) GLAZED SWING DOORS |
| | C) HOLLOW CORE METAL DOORS (PAIR) |
| | D) MULLIONS |
| | E) TRUSS ANCHOR STRAPS AND CONNECTIONS |
| | F) STORM SHUTTERS |
| | G) PRE-ENGINEERED A/C STANDS |
| | H) ROOFING ASSEMBLIES |
| | |
| | 15) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WW.FLORIDABUILDING.ORG |
| | |
| | 16) ) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 17) THE MIAMI-DADE PRODUCT APPROVAL REPORTS THAT WERE |
| | TESTED BEFORE 2004 FBC WILL NEED TO BE REVIEWED BY AN |
| | ENGINEER TO SEE IF REDUCTIONS NEED TO BE TAKEN. 2004 |
| | FBC 1605.3.1.1 DO NOT ALLOW FOR THE 1/3RD INCREASES |
| | THAT HAD BEEN TAKEN WHEN THE PRODUCTS WERE TESTED .THE |
| | PRODUCTS MAY REQUIRE ADDITIONAL FASTENERS. SEE |
| | CALCULATIONS LISTED UNDER SUB HEADING# 3 ON THE PRODUCT |
| | APPROVALS, IF THE 2004 CODE IS NOT REFERENCED AN |
| | ENGINEER WILL NEED TO VERIFY LOADING OF FASTENERS!!!! |
| | 1605.3.1.1 LOAD REDUCTION. |
| | 1. IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT OF |
| | TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE EFFECT |
| | OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN SHALL |
| | NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD LOAD AND |
| | ANY OF THE VARIABLE LOADS. |
| | 2. INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE |
| | MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED |
| | STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD |
| | COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD |
| | INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER |
| | 23 . |
| | |
| | 18) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED FOR ALL |
| | NON-IMPACT GLAZING. FBC 1606.1.4. |
| | |
| | 19) FL BLD CODE 2001 SECTION 103.6, 1606.1.4, 1707.4 & |
| | 3401.7.2.4. PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT |
| | SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS, |
| | WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE |
| | PLAN REVIEW AND PERMIT ISSUANCE. |
| | 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE |
| | DEBRIS IMPACT PROTECTION |
| | QUESTION# 13 RECOGNIZING SUCH CONCERNS AS ABSENTEE |
| | OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS |
| | NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY |
| | BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR |
| | IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR |
| | SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE |
| | HURRICANE? |
| | |
| | IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE |
| | GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE, |
| | SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING, |
| | CHAPTER 1, |
| | ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY |
| | OF WEST PALM BEACH, PROVDES THE ABILITY FOR THE |
| | BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR |
| | ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION |
| | OF EXISTING BUILDINGS. |
| | |
| | IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR |
| | MULTI-STORY BUILDINGS, OR MULTIPLE BUILDINGS ON THE |
| | SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST BE |
| | SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS FOR |
| | REVIEW BY THE CONSTRUCTION SRVICES DEPARTMENT. ANY SUCH |
| | PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION OF |
| | THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE |
| | SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH |
| | COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND |
| | THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS. |
| | PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN |
| | TWELVE (12) HOURS OR LESS OF THE |
| | OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES |
| | OF A HURRICANE WATCH. |
| | |
| | PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| | ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE |
| | MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO |
| | REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN |
| | QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, |
| | DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED |
| | UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE |
| | MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE |
| | BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO |
| | SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. |
| | |
| | 20) THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE |
| | FOLLOW ITEMS: |
| | _XXX__ CONTRACTOR / ENGINEER DID NOT INDICATE THE ROOF |
| | PITCH. |
| | |
| | _XXX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE |
| | USED. |
| | |
| | _XXX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE |
| | _2&3__ . |
| | |
| | |
| | _XXX__ NOT KNOWN- THE SYSTEM PROVIDED STATES |
| | LIMITATION# 7, SHOULD THE FASTENER RESISTANCE BE LESS |
| | THAN THAT REQUIRED, AS DETERMINED BY THE BUILDING |
| | OFFICIAL, A REVISED FASTENER SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL |
| | ENGINEER, REGISTERED ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | __XXX_ NOT KNOWN- THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | |
| | 21) PLANS ALSO FAIL TO PROVIDE ENERGY CALCULATIONS. |
| | |
| | 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |