| 2008-02-04 10:05:48 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK DELETED |
| | |
| | 5. SHT 7 OF 9 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE BEING |
| | DRAINED BY EACH ROOF DRAIN AS WELL AS 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS IN THE CALCULATIONS. |
| | SHOW THE LOCATION OF THE PRIMARY AND SECONDARY ROOF |
| | DRAINS AS WELL AS A DETAIL FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS. SECTIONS 106.1.1 & 106.1.2. |
| | ****NO RESPONSE, BUT THE WALL SECTIONS INDICATE THAT |
| | THE ROOF DRAINAGE WILL BE DRAINED OFF ONE END OF THE |
| | BUILDING. SECONDARY ROOF DRAINS ARE NOT REQUIRED, BUT |
| | THE CALCULATIONS FOR THE SQUARE FOOTAGE OF THE ROOF |
| | PLUS THE VERTICAL CONTRIBUTION OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS REQUESTED IN THE PREVIOUS REVIEW |
| | HAVE NOT BEEN SUBMITTED. (PLEASE SEE COMMENT 1B). |
| | |
| | 6. OK SHELL |
| | 7. OK SHELL |
| | 8. OK SHELL |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. 1503.6 PROTECTION AGAINST DECAY AND TERMITES. |
| | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| | SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| | ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| | HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| | A ROOF ABOVE ANOTHER ROOF. |
| | INDICATE THE SIZE OF THE GUTTERS AND THE DOWNSPOUTS AND |
| | SHOW THE SLOPE OF THE GUTTER PER TABLE 1106.6. INDICATE |
| | THE HIGH POINT OF THE SLOPE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |