| 2008-02-04 12:58:41 | ****DENIED***** |
| | |
| | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE |
| | PLAN REVIEW STILL NEED TO BE ADDRESSED: |
| | |
| | 04.NFPA 101 - 2003 EDITION SHALL BE REFERENCED. |
| | |
| | 05.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 06.CONSTRUCTION/DEMOLITION OPERATIONS SHALL NOT |
| | INTERFERE OF HINDER EMERGENCY RESPONSE ACCESS TO THE |
| | SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING |
| | STREETS, ALLEYS, FIRE LANES. |
| | |
| | 07.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 08.THERE ARE TWO SUBMITTED PLAN SETS FOR BOTH 433 AND |
| | 435 AS NUMERICAL ADDRESSES IN THE TITLE BLOCK. PLEASE |
| | EXPLAIN |
| | |
| | 09.SHOW THE NUMERICAL ADDRESS ON THE NEW FRONT |
| | ELEVATION VISIBLE FROM NORTHWOOD ROAD.. AS PER WEST |
| | PALM BEACH CODE, THESE NUMBERS SHALL BE NO LESS THAN 6" |
| | IN HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| | |
| | 10.SHOW THE ADDRESS NUMBER ON THE NEW REAR ELEVATION |
| | SO THAT THE SPACE IS DISTINGUISHALBE FROM OTHER UNIT |
| | SPACES.AS PER WEST PALM BEACH CODE, THESE NUMBERS |
| | SHALL BE NO LESS THAN 3" IN HEIGHT AND NO LESS THAN 1" |
| | IN WIDTH. |
| | |
| | 12.SHOW LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS, |
| | AND FIRE EXTINGUISHERS FOR THE NEW FLOOR PLAN. |
| | |
| | 13.INDICATE IF THE BUILDING IS EQUIPPED WITH A FIRE |
| | SPRINKLER AND/OR A FIRE ALARM SYSTEM. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |