| 2007-07-12 14:32:15 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. CONSTRUCTIONS PLANS SHALL BE SUBMITTED IN TWO OR |
| | MORE SETS WITH EACH APPLICATION. ONLY ONE SET OF PLANS |
| | WITH THIS ADDRESS SUBMITTED. |
| | |
| | 2. PLEASE INDICATE ALL CODES ADOPTED AND IN EFFECT BY |
| | THE STATE ON THE PLANS INCLUDING FBC-2004 PLUMBING |
| | W/2006 AMENDMENTS. |
| | |
| | 3. INDICATE THE OCCUPANCY. THE APPLICATION INDICATES |
| | "NO CHANGE OF OCCUPANCY" AND PLANS INDICATE A RESIDENCE |
| | SO THE PLANS WILL BE REVIEWED AS AN R-3 OCCUPANCY. AS |
| | SUCH, A KITCHEN, BATHING FACILITIES, & A WASH MACHINE |
| | CONNECTION WILL BE REQUIRED PER TABLE 403.1. SUBMIT AN |
| | EXISTING FLOOR PLAN SHOWING THE LOCATION OF ALL |
| | REQUIRED FACILITIES. SECTION 106.1.2. |
| | |
| | 4. SHT 4 OF 8SANITARY RISER DIAGRAM. TRAPS ARE NOT |
| | APPROVED FOR WATER CLOSETS AS THEY HAVE AN INTEGRAL |
| | TRAP IN THE FIXTURES. DELETE FROM RISER DIAGRAM. |
| | SECTION 1002.1.--THE SIZE OF THE DRAINAGE PIPE |
| | SHALL NOT BE REDUCED IN THE DIRECTION OF FLOW. SECTION |
| | 704.2. (THE 3" LINE TO THE W/C REDUCES TO 2" ON THE |
| | RISER DIAGRAM). |
| | |
| | 5. SHT 7 OF 9 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE BEING |
| | DRAINED BY EACH ROOF DRAIN AS WELL AS 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS IN THE CALCULATIONS. |
| | SHOW THE LOCATION OF THE PRIMARY AND SECONDARY ROOF |
| | DRAINS AS WELL AS A DETAIL FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS. SECTIONS 106.1.1 & 106.1.2. |
| | |
| | 6. NOTE: IF THIS TURNS OUT TO BE A CHANGE OF OCCUPANCY, |
| | OR IS A COMMERCIAL OCCUPANCY AND NOT RESIDENTUAL AS |
| | INDICATED, THEN MORE COMMENTS WILL FOLLOW. AS THE PLANS |
| | ARE NOW SUBMITTED, NO PLUMBING WORK IS SHOWN ON THE |
| | PLANS. PLEASE CLARIFY. |
| | |
| | 7. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, |
| | VALVES AND, (IF REQUIRED BY SECTION 604.9), WATER |
| | HAMMER ARRESTORS INSTALLED PER PDI-WH 201 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | 8. A HOT WATER HEATER IS REQUIRED PER SECTION 607.1. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |