| 2009-02-03 15:44:31 | 435 NORTHWOOD RD, |
| | LOT 28/ 07050947 |
| | FEB.03,2009 |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07050947 |
| | ADD: 435 NORTHWOOD RD |
| | CONT: KDN CONSTRUCTION SERVICES, LLC |
| | TEL: (561)662-1002 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 4TH REVIEW |
| | ACTION: DENIED |
| | |
| | 1) --- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL. S. S. 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE FL |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3-6) COMPLIED. |
| | |
| | 7-8) COMPLIED. THIS COMMENT DEALS WITH THE EXTERIOR |
| | WALLS OF THE BUILDING AND ADDITION. SINCE THERE IS NO |
| | WORK BEING COMPLETEED TO THE EXISTING BUILDING ON THE |
| | EXTERIOR WALLS THIS COMMENT PERTAINS EXCLUSIVELY TO THE |
| | ADDITION WALLS TABLE 601 DEALS WITH THE BUILDING |
| | ELEMENTS, TABLE 602 DEALS WITH FIRE-RESISTANCE RATING |
| | REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE |
| | SEPERATION, THE TYPE V-B BUILDING < 5 FEET WOULD |
| | REQUIRE A 1 HOUR FIRE SEPERATION, WHICH THE BLOCK WALL |
| | WILL MEET THIS REQUIREMENT. |
| | |
| | 9-14 COMPLIED. |
| | |
| | 15) RESPONCE INDICATES THIS SPACE TO BE A SHELL |
| | BUILDING. 1203.2 ATTIC SPACES. ENCLOSED ATTICS AND |
| | ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE |
| | APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF FRAMING |
| | MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. BLOCKING AND BRIDGING SHALL BE |
| | ARRANGED SO AS NOT TO INTERFERE WITH THE MOVEMENT OF |
| | AIR. A MINIMUM OF 1 INCH (25 MM) OF AIRSPACE SHALL BE |
| | PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING. |
| | SHEET 3 INDICATES THE USE OF 2X12'S @ 16" O.C. THE |
| | PLANS DO NOT INDICATE ANY TYPE OF BLOCKING OR BRIDGING |
| | FOR THE SPAN OF OVER 23'-0". |
| | 2308.10.6 BLOCKING.ROOF RAFTERS AND CEILING JOISTS |
| | SHALL BE SUPPORTED LATERALLY TO PREVENT ROTATION AND |
| | LATERAL DISPLACEMENT IN ACCORDANCE WITH THE PROVISIONS |
| | OF SECTION 2308.8.5. |
| | |
| | 2308.8.5 LATERAL SUPPORT. |
| | FLOOR, ATTIC AND ROOF FRAMING WITH A NOMINAL |
| | DEPTH-TO-THICKNESS RATIO GREATER THAN OR EQUAL TO 5:1 |
| | SHALL HAVE ONE EDGE HELD IN LINE FOR THE ENTIRE SPAN. |
| | WHERE THE NOMINAL DEPTH-TO-THICKNESS RATIO OF THE |
| | FRAMING MEMBER EXCEEDS 6:1, THERE SHALL BE ONE LINE OF |
| | BRIDGING FOR EACH 8 FEET (2438 MM) OF SPAN, UNLESS BOTH |
| | EDGES OF THE MEMBER ARE HELD IN LINE. THE BRIDGING |
| | SHALL CONSIST OF NOT LESS THAN 1-INCH BY 3-INCH (25 MM |
| | BY 76 MM) LUMBER, DOUBLE NAILED AT EACH END, OF |
| | EQUIVALENT METAL BRACING OF EQUAL RIGIDITY, FULL-DEPTH |
| | SOLID BLOCKING OR OTHER APPROVED MEANS. A LINE OF |
| | BRIDGING SHALL ALSO BE REQUIRED AT SUPPORTS WHERE |
| | EQUIVALENT LATERAL SUPPORT IS NOT OTHERWISE PROVIDED. |
| | |
| | 16-27) COMPLIED. |
| | |
| | |
| | 28) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 29) PERMIT FEES ARE TO BE PAID AT TIME OF APPLICATION A |
| | HOLD WILL BE PLACED BEFORE RESUBMITTAL .$156.06 DUE. |
| | |
| | 30) 21) THIS REVIEW ENERGY CALCULATIONS WERE SUBMITTED. |
| | PART OF THE RESPONSE TO COMMENT NUMBER 12 INDICATED |
| | THAT THE ROOF/CEILING INSULATION WAS TO BE THE |
| | RESPONSIBILITY OF THE TENANT. BUT THE ENERGY CALCS CAME |
| | IN AS METHOD "B" WHICH CAN BE FOR THE "SHELL BUILDING". |
| | 3-101.1.6 SHELL BUILDINGS. |
| | NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO |
| | DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS |
| | AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY |
| | WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE |
| | CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL |
| | ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL |
| | LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE |
| | LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO |
| | THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS |
| | COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL |
| | CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S) |
| | USING METHODS A, B OR C SHALL BE SUBMITTED WHEN |
| | COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS |
| | PERMITTED. |
| | |
| | WITHIN THE DATAINPUT REPORT UNDER THE HEADING OF |
| | ROOFING THE REPORT INDICATES THE USE OF 6" BATTS WHICH |
| | WILL NEED TO BE REFLECTED WITHIN THE PLANS, THE ROOFING |
| | SECTION OF THE INPUT DATA REPORT ALSO INDICATED USE OF |
| | SHINGLES, THAT WILL NEED TO BE CORRECTED WITHIN THE |
| | DATA INPUT REPORT. |
| | |
| | THE SECOND ISSUE WITH THE DATA INPUT REPORT IS THE |
| | EXTERIOR BACK DOOR IS INDICATED AS A SOLID CORE 2.25 |
| | INCH DOOR WHERE WHAT WAS SUBMITTED IS A 1 33/4 FOAM |
| | FILLED DOOR. |
| | |
| | THE THIRD ITEM THAT WILL NEED TO BE REVIEWED IS THIS IS |
| | FOR THE SHELL OF THE BUILDING BUT THE WALL SQUARE |
| | FOOTAGE IS ONLY FOR THE ADDITION NOT THE SHELL |
| | BUILDING. |
| | |
| | THE FOURTH ITEM IS THE FOURTH EXTERIOR WALL NOT INTHE |
| | DATA INPUT REPORT IS MISSING THE GLAZED WINDOW AND |
| | DOORWAY IN THE FRONT OF THE BUILDING. |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |