| 2009-02-02 14:09:56 | ** DENIED ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2, |
| | 13-400.3.B, 13-400.2.A.2, |
| | PLANS SHOW METHOD *C* FROM TABLE, YET SEPARATE METHOD |
| | *B* ARE ALSO SUBMITTED. |
| | PLEASE SEE 13-415.2.ABC.1 WHICH DOES NOT PERMIT |
| | DIFFERENT METHODS. PLEASE SEE COMMENTS FROM OTHER |
| | TRADES WITH RESPECT TO ITEMS SHOWN ON THE IDR WHICH MAY |
| | OR MAY NOT BE PART OF THE PLANS. IS THE CEILING GOING |
| | TO BE INSTALLED? IF NOT WHAT FIXTURES ARE GOING TO BE |
| | INSTALLED ON WHAT TYPE OF CEILING? |
| | PLEASE BE SURE TO PLACE SPECIFIC FIXTURE INFORMATION. |
| | STATING A FIXTURE WITH 2-32W BULBS DOES NOT GIVEN |
| | INFORMATION ON EFFICIENCY RATING OF BALLAST WHICH IS |
| | WHAT NEEDS TO BE USED FOR THE ACTUAL WATTAGE IN |
| | CALCULATIONS. THE VA TO BE USED ON ALL CALCULATIONS ARE |
| | BASED ON FIXTURE RATING NOT BULB WATTAGES. THIS IS ALSO |
| | FOR EXTERIOR LIGHTING FIXTURES. PLEASE SEE |
| | 13-415.2.ABC.1.1 AS NOTED ABOVE FOR ACTUAL VA RATINGS |
| | TO BE USED DEPENDING ON THE TYPE OF |
| | FIXTURES.13-415.2.ABC.1.3 (EXTERIOR) |
| | |
| | 2) NOTE: FEE BALANCE FOR EXTENDING PERMIT AND RESUB |
| | FEES WERE NOT PAID. BALANCE OF FEES IS DUE AT THIS |
| | TIME. PLANS WILL BE PLACED ON HOLD. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |