| 2008-06-10 12:23:52 | ** DENIED** |
| | |
| | 1) NOTE: PLEASE PROVIDE ELEVATION DRAWING FOR |
| | ELECTRICAL SERVICE DROP AND RISER. |
| | PLEASE SEE THE ELECTRICAL PLANS SHOW THE SERVICE AT THE |
| | REAR OF BUILDING YET THE SHEET 1 SHOWS AN ELECTRICAL |
| | SERVICE OVER HEAD DROP TO THE SIDE OF THIS BUILDING. |
| | PLEASE KNOW THAT IF THIS EXISTING OVER HEAD SERVICE |
| | DROP CROSSES OVERTHIS BUILDING TO FEED ANOTHER OR IF |
| | THIS SERVICE DROP AS SHOWN GOES OVER ANY ROOF OR |
| | PARKING LOT AREAS THE MINIMUM CLEARANCES PER 230.24 |
| | |
| | 2) NOTE: PLEASE PROVIDE ENERGY CALCULATIONS PER |
| | 13-400.0, 13-101.1, .1.1,.1.2,.1.3 AND .1.4. |
| | |
| | 3) NOTE: PLEASE VERIFY NOTE ONSHEET #1 WHICH MENTIONS |
| | NO ELECTRICAL OR PLUMBING IN SCOPE OF WORK BASED ON |
| | PLANS SUBMITTED THERE IS CLEARLY SHOW ELECTRICAL. |
| | PLEASE SEE NOTES WITH RESPECT TO MINIMUM TOILET ROOM |
| | FACILITIES AS THESE WILL AFFECT ELECTRICAL PLANS FOR |
| | LIGHTING, LAYOUTS ETC. |
| | |
| | 4) NOTE: PLEASE SEE 13-415.1.ABC.1.2 FOR SPACE CONTROLS |
| | AS REQUIRED PER NOTE #3 ABOVE. |
| | |
| | 5) NOTE: PLEASE SEE MISSING LIGHTING CONTROLS PER |
| | 13-415.1.ABC.1.4. |
| | |
| | ** IT IS IMPORTANT TO UNDERSTAND AS THERE ARE ITEMS NOT |
| | IN DESIGN YET AT THIS TIME OR SHOWN ON PLANS, NEW |
| | COMMENTS MAY BE GENERATE WHICH CAN NOT POSSIBLY BE MADE |
| | AT THIS TIME. REVIEWS ARE DONE BASED ON PLANS |
| | SUBMITTED. |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |