| 2007-10-11 14:00:20 | ** DENIED 2ND REVIEW** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED ALONG WITH NEW NOTE DUE TO |
| | ADDITIONAL INFORMATION ONLY NOW SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE PANEL SCHEDULE PROVIDED FRO THE |
| | VAK-PAK PANEL IS MISSING THE CIRCUITS FOR THE TWO SETS |
| | OF GFI RECEPTACLES WHICH FEED CHEMICAL FEEDERS ETC. |
| | 408.4, 220, 310.16 ETC |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS COMMENT REQUESTED FOR |
| | INFORMATION ON HOW NEW PANEL WAS GOING TO BE FED FOR |
| | FEEDERS, OVER CURRENT PROTECTION ETC. THE RESPONSE |
| | LETTER MENTIONS TO SEE BASE BUILDING E-13 SHEETS. |
| | THE E-13 SHEETS WERE SUBMITTED HOWEVER THIS SHEET |
| | INDICATES A DIFFERENT PANEL FOR POOL EQUIPMENT (2EQ) |
| | AND CLEARLY SHOWS BRANCH CIRCUITS FOR POOL EQUIPMENT |
| | AND NOT A SUB-FEED FOR A VAK-PAK PANEL. |
| | PLEASE CORRELATE ALL PLANS, EQUIPMENT, FEEDERS, BRANCH |
| | CIRCUITS, OVER CURRENT PROTECTION ETC. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |