Plan Review Notes
Plan Review Notes For Permit 07050937
Permit Number 07050937
Review Stop P
Sequence Number 1
Notes
Date Text
2007-07-06 12:48:28DENIED
 REFERENCE: FBC-2004 CHAPTER 424
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. INDICATE ON THE PLANS THE CODES RELEVENT TO THIS
 PROJECT. FBC-2004 PLUMBING, FBC-2004 BUILDING ETC.
 SECTION 106.1.1.
  
 2. SHT 5 OF 5 PLEASE INDICATE THAT ALL WASTE SHALL
 DRAIN INTO THE SANITARY SYSTEM, AND ALL OVERFLOW SHALL
 DRAIN INTO THE STORM SYSTEM. MUNICIPAL CODE SECTIONS
 90-125(5) AND 90-203(A).
  
 3. SUBMIT THE MANUF SPECIFICATIONS FOR THE POOL
 HEATERS. SECTION 303.4.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]