| 2007-06-19 08:37:04 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | NOTE: MORE INFORMATION IS REQUIRED FOR PLAN REVIEW. |
| | RECORDS INDICATE THAT RESIDENCE HAS EXISTING GAS. |
| | PLEASE REFERENCE THE ATTACHED PERMIT INFORMATION TO THE |
| | GAS PLAN REVIEW COMMENTS INDICAING THIS. PLEASE PROVIDE |
| | THE FOLLOWING INFORMATION TO MEET CODE COMPLIANCE. |
| | PLEASE REFERENCE THE ENCLOSED CITY OF WEST PALM BEACH |
| | GAS PERMIT APPLICATION REQUIREMENTS FOR FUTURE PERMIT |
| | APPLICATIONS. |
| | |
| | 1. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: THIS INCLUDES THE EXISTING SYSTEM. |
| | |
| | 2. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: THIS INCLUDES THE EXISTING SYSTEM. |
| | |
| | 3. PLEASE INDICATE THE ABOVE GROUND PIPING MATERIAL OF |
| | THE PROPOSED POOL HEATER. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |