| 2008-04-01 13:07:46 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | COMMENTS NOT ADDRESSED: |
| | |
| | |
| | 5.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| | OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), |
| | FBC*106.3.3. |
| | |
| | 7.)THE NEW SITE PLAN SHOWS THE PROPOSED SHED ATTACHED |
| | TO ANOTHER STRUCTURE.PLEASE SEE FBC CHAPTER 3, |
| | BUILDING PLANNING.PROVIDE STRUCTURAL DETAILS SHOWING |
| | HOW THE TWO BUILDINGS WILL BE CONNECTED.CORRELATE THE |
| | BUILDING PLAN WITH THE SITE PLAN EITHER BY SHOWING THE |
| | DOORS ON THE SITE PLAN OR BY SHOWING "NORTH" ON THE |
| | BUILDING PLAN.IF THE TWO BUILDINGS ARE NOT CONNECTED, |
| | SHOW DISTANCE AND SEE FBC R302, AND SHOW REQUIRED FIRE |
| | RESISTANCE ON THE PLAN. |
| | |
| | FIRE RESISTANCE REQUIREMENTS, RISK TO THE OTHER |
| | BUILDING, IS NOT CLEAR.SEE FBC R 302, LOCATION ON |
| | LOT.I CANNOT DETERMINE FROM THE SITE PLAN THE |
| | ORIENTATION OF THE STRUCTURE.FIRE RESISTANCE DOES NOT |
| | APPEAR TO BE REQUIRED IF THIS IS NOT A GARAGE, BUT SEE |
| | FBC302.2.OPENINGS NOT PERMITTED IN THE EXTERIOR WALL |
| | OF A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED |
| | FROM AN ADJACENT BUILDING BY LESS THAN 6 FEET. |
| | |
| | |
| | |
| | |
| | |
| | |