Plan Review Notes
Plan Review Notes For Permit 07050920
Permit Number 07050920
Review Stop B
Sequence Number 3
Notes
Date Text
2008-03-11 15:16:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS NOT ADDRESSED:
  
 2.)PRODUCT APPROVALS REQUIRED FOR THE PEEL AND STICK
 ROOF SPECIFIED BY THE ENGINEER.
  
 4.)PLEASE CLARIFY THE APPROX 6' OPENING.WILL A DOOR
 BE INSTALLED?IF A DOOR IS TO BE INSTALLED, PROVIDE
 PRODUCT APPROVALS.
  
 THE PLANS DATED 2/27/08 NOW SHOW A 6'X6'8" DOUBLE HUNG
 DOOR.THE PHRASE "DOUBLE HUNG" USUALLY IS A TYPE OF
 WINDOW.IS THIS A SIDE HINGED SWING DOOR?FLOOR PLANS
 TYPICALLY SHOW DOORS OF ANY TYPE AS A GRAPHIC SO THAT
 DOOR TYPE IS CLEAR (OVERHEAD OR SWING).DUE TO THE
 VERY SMALL SCOPE OF THIS PROJECT, I DID NOT REQUIRE
 ELEVATIONS.HOWEVER, THIS MAY BE REQUIRED IF THE PLANS
 CANNOT CLEARLY SHOW SCOPE OF WORK.THE PRODUCT
 APPROVALS REQUESTED WERE NOT PROVIDED.
  
 5.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 **NOTE** - AS DISCUSSED WITH CONTRACTOR, THE NOTE
 REGARDING THE ROOF FASTENING MAY BE REMOVED FROM THE
 PLAN AND REVIEWED LATER AS A PART OF THE ROOFING PERMIT
 APPLICATION WHEN ROOFING PRODUCT APPROVALS ARE
 SUBMITTED.ALTERNATELY, ENGINEER CAN ADDRESS COMMENTS
 REGARDING ROOF SPECIFICATIONS AT THIS TIME.ENGINEER'S
 REVIEW OF PRODUCT APPROVALS WILL STILL BE REQUIRED WHEN
 ROOF PERMIT APPLICATION IS SUBMITTED.
  
 NEW COMMENT:
  
 6.THE RESUBMITTAL SHEET STATES THAT THE BUILDING WAS
 DESIGNED SMALLER ACCORDING TO "CODE OF WEST PALM".
 GOVERNING CODE IS FBC2004, SAME CODE THROUGHOUT ALL OF
 FLORIDA; SIZE IS RESTRICTED BY FBC CHAPTER 5, AND DOES
 NOT APPLY IN THIS CASE.
  
 7.THE NEW SITE PLAN SHOWS THE PROPOSED SHED ATTACHED
 TO ANOTHER STRUCTURE.PLEASE SEE FBC CHAPTER 3,
 BUILDING PLANNING.PROVIDE STRUCTURAL DETAILS SHOWING
 HOW THE TWO BUILDINGS WILL BE CONNECTED.CORRELATE THE
 BUILDING PLAN WITH THE SITE PLAN EITHER BY SHOWING THE
 DOORS ON THE SITE PLAN OR BY SHOWING "NORTH" ON THE
 BUILDING PLAN.IF THE TWO BUILDINGS ARE NOT CONNECTED,
 SHOW DISTANCE AND SEE FBC R302, AND SHOW REQUIRED FIRE
 RESISTANCE ON THE PLAN.
  
  
  
  
  
  
  
  