| 2008-03-11 15:16:30 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | COMMENTS NOT ADDRESSED: |
| | |
| | 2.)PRODUCT APPROVALS REQUIRED FOR THE PEEL AND STICK |
| | ROOF SPECIFIED BY THE ENGINEER. |
| | |
| | 4.)PLEASE CLARIFY THE APPROX 6' OPENING.WILL A DOOR |
| | BE INSTALLED?IF A DOOR IS TO BE INSTALLED, PROVIDE |
| | PRODUCT APPROVALS. |
| | |
| | THE PLANS DATED 2/27/08 NOW SHOW A 6'X6'8" DOUBLE HUNG |
| | DOOR.THE PHRASE "DOUBLE HUNG" USUALLY IS A TYPE OF |
| | WINDOW.IS THIS A SIDE HINGED SWING DOOR?FLOOR PLANS |
| | TYPICALLY SHOW DOORS OF ANY TYPE AS A GRAPHIC SO THAT |
| | DOOR TYPE IS CLEAR (OVERHEAD OR SWING).DUE TO THE |
| | VERY SMALL SCOPE OF THIS PROJECT, I DID NOT REQUIRE |
| | ELEVATIONS.HOWEVER, THIS MAY BE REQUIRED IF THE PLANS |
| | CANNOT CLEARLY SHOW SCOPE OF WORK.THE PRODUCT |
| | APPROVALS REQUESTED WERE NOT PROVIDED. |
| | |
| | 5.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| | OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), |
| | FBC*106.3.3. |
| | |
| | **NOTE** - AS DISCUSSED WITH CONTRACTOR, THE NOTE |
| | REGARDING THE ROOF FASTENING MAY BE REMOVED FROM THE |
| | PLAN AND REVIEWED LATER AS A PART OF THE ROOFING PERMIT |
| | APPLICATION WHEN ROOFING PRODUCT APPROVALS ARE |
| | SUBMITTED.ALTERNATELY, ENGINEER CAN ADDRESS COMMENTS |
| | REGARDING ROOF SPECIFICATIONS AT THIS TIME.ENGINEER'S |
| | REVIEW OF PRODUCT APPROVALS WILL STILL BE REQUIRED WHEN |
| | ROOF PERMIT APPLICATION IS SUBMITTED. |
| | |
| | NEW COMMENT: |
| | |
| | 6.THE RESUBMITTAL SHEET STATES THAT THE BUILDING WAS |
| | DESIGNED SMALLER ACCORDING TO "CODE OF WEST PALM". |
| | GOVERNING CODE IS FBC2004, SAME CODE THROUGHOUT ALL OF |
| | FLORIDA; SIZE IS RESTRICTED BY FBC CHAPTER 5, AND DOES |
| | NOT APPLY IN THIS CASE. |
| | |
| | 7.THE NEW SITE PLAN SHOWS THE PROPOSED SHED ATTACHED |
| | TO ANOTHER STRUCTURE.PLEASE SEE FBC CHAPTER 3, |
| | BUILDING PLANNING.PROVIDE STRUCTURAL DETAILS SHOWING |
| | HOW THE TWO BUILDINGS WILL BE CONNECTED.CORRELATE THE |
| | BUILDING PLAN WITH THE SITE PLAN EITHER BY SHOWING THE |
| | DOORS ON THE SITE PLAN OR BY SHOWING "NORTH" ON THE |
| | BUILDING PLAN.IF THE TWO BUILDINGS ARE NOT CONNECTED, |
| | SHOW DISTANCE AND SEE FBC R302, AND SHOW REQUIRED FIRE |
| | RESISTANCE ON THE PLAN. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |