2007-06-15 11:01:50DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. INFORMATION ON TITLE BLOCK IS INCOMPLETE PER THE
 FOLLOWING.
 FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 NOTE: ITEMS 1, 2, AND 6 ARE MISSING FROM THE TITLE
 BLOCK. PLEASE CLEARLY IDENTIFY WHO THE PERSON IS WHO
 SIGNED AND SEALED THE PRINTS WITH THEIR LICENSE NUMBER.
 IF SAID PERSON IS WORKING FOR A FIRM PLEASE CLEARLY
 INDICATE THE FIRM LICENSE NUMBER AND CERTIFICATE OF
 AUTHORIZATION NUMBER IN THE TITLE BLOCK. PLEASE BE
 AWARE THAT A DPBR SEARCH OF "EDSA LANSCAPE ARCHITECTS"
 CAME UP WITH NO RECORDS FOUND MATCHING SEARCH CRITERIA
 ON BOTH A LICENSE NUMBER AND NAME SEARCH. PLEASE
 CLARIFY THIS ON THE RESUBMITTAL.
  
 2. PLEASE CLEARLY INDICATE THE RAIN SENSOR LOCATION ON
 THE PRINTS AND THE SYMBOL OF THE RAIN SENSOR IN THE
 IRRIGATION LEGEND UNDER THE IRRIGATION EQUIPMENT ON THE
 RESUBMITTAL AS REQUIRED BY FLORIDA STATUTES, SECTION
 373.62.
  
 END OF COMMENTS:
  