| Plan Review Notes For Permit 07050910 |
| Permit Number |
07050910 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-09-17 08:32:56 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) NOZZLES SHOWING ON PLAN ARE LESS THAN WHAT NOZZLE | | | LISTING STATES AND TOTAL FLOW POINTS ARE INCORRECT. | | | PLEASE CORRECT. | | | | | | 2) THE PLAN WILL NEED TO BE SIGNED AND SEALED BY THE | | | ENGINEER (C. T. TARNOWSKI) AS HIS INFORMATION IS IN THE | | | TITLE BLOCK. DO NOT USE WHITE OUT ON PLANS. | | | | | | 3) ATLANTIC COAST FIRE EQUIPMENT NEEDS TO PUT THEIR | | | FIRE LICENSE IN THE TITLE BLOCK NOT THEIR AIR | | | CONDITIONING CONTRACTOR LICENSE NUMBER. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|