2007-09-17 08:32:56PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NOZZLES SHOWING ON PLAN ARE LESS THAN WHAT NOZZLE
 LISTING STATES AND TOTAL FLOW POINTS ARE INCORRECT.
 PLEASE CORRECT.
  
 2) THE PLAN WILL NEED TO BE SIGNED AND SEALED BY THE
 ENGINEER (C. T. TARNOWSKI) AS HIS INFORMATION IS IN THE
 TITLE BLOCK. DO NOT USE WHITE OUT ON PLANS.
  
 3) ATLANTIC COAST FIRE EQUIPMENT NEEDS TO PUT THEIR
 FIRE LICENSE IN THE TITLE BLOCK NOT THEIR AIR
 CONDITIONING CONTRACTOR LICENSE NUMBER.
  
 MECHANICAL PLAN REVIEW BY;