| Plan Review Notes For Permit 07050907 |
| Permit Number |
07050907 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2007-11-09 11:47:22 | | | | | | | ** REDLINED, | | | OCP FOR AHU TO VIF, TOO HIGH AS SHOWN. 5KW, 50AMP? | | | SA REQUIRED IN BEDROOMS EVEN AS NO WORK IS BEING DONE. | | | THESE ARE STILL REQUIRED TO BE BATTERY BACK UP. NO | | | ACCESS OR ATTIC SPACE. | | | IF DISH/DISP ARE FED TO SAME YOKE/DEVICE, THEN 2-POL | | | BREAKER IS REQUIRED. 210.4 | | | | | | ** THESE ITEMS ARE TO BE REVISEDBEFORE FINAL. |
|