| Notes |
| Date |
Text |
| 2007-09-15 10:16:23 | REDLINED PLANS. | | | | | | REDLINED CA #, AS THIS IS PRINTED UNDER CONTRACTORS | | | NAME. | | | | | | NEED TO VERIFY OCP FOR AHU, AS THIS SEEMS TOO HIGH FOR | | | 5KW. | | | NEED TO VERIFY 2-POLE BREAKER FOR DISHWASHER DISPOSAL | | | PER 210.4B IF ON SAME YOKE. | | | NEED TO VERIFY NOTE FOR AFCI PROTECTION SHOWN FOR | | | EXISTING BEDROOMS NOT BEING REWIRED. | | | SMOKE ALARMS IN BEDROOMS MISSING PER FBC R313, NFPA-72 | | | 11.5.1.1, ALSO IF THESE ARE 120V UNITS THEY REQUIRE | | | AFCIPROTECTION. | | | | | | ** NEED TO CHANGE THE ABOVE AND REVISE PANEL SCHEDULE | | | BEFORE FINAL. |
|