Plan Review Notes
Plan Review Notes For Permit 07050907
Permit Number 07050907
Review Stop E
Sequence Number 4
Notes
Date Text
2007-09-15 10:16:23REDLINED PLANS.
  
 REDLINED CA #, AS THIS IS PRINTED UNDER CONTRACTORS
 NAME.
  
 NEED TO VERIFY OCP FOR AHU, AS THIS SEEMS TOO HIGH FOR
 5KW.
 NEED TO VERIFY 2-POLE BREAKER FOR DISHWASHER DISPOSAL
 PER 210.4B IF ON SAME YOKE.
 NEED TO VERIFY NOTE FOR AFCI PROTECTION SHOWN FOR
 EXISTING BEDROOMS NOT BEING REWIRED.
 SMOKE ALARMS IN BEDROOMS MISSING PER FBC R313, NFPA-72
 11.5.1.1, ALSO IF THESE ARE 120V UNITS THEY REQUIRE
 AFCIPROTECTION.
  
 ** NEED TO CHANGE THE ABOVE AND REVISE PANEL SCHEDULE
 BEFORE FINAL.