2007-08-10 19:06:27THE NOTICE OF COMMENCMENT IS VOID AS IT HAS EXPIRED PER
 FS 713.13(2).
 THIS IS ONLY NEEDED TO BE RE-RECORDED AND SUBMITTED
 BEFORE PICKING UP PERMIT.
2007-08-10 19:01:54** DENIED **
  
 1) NOTE: PLEASE SEE THE CIRCUITING ON THE PLANS NEEDS
 TO COORDINATE ON PLANS AND PANEL SCHEDULE.
 PLEASE SEE FOR EXAMPLE THE DRYER IS SHOWN AS 5KW WITH
 12 AWG AND 20AMP OVER CURRENT PROTECTION.
 PLEASE SEE THE BATH CIRCUIT ON PLANS WHICH IS SHOWN AS
 A SPARE CIRCUIT ON PANEL SCHEDULE. PLEASE ALSO SEE THAT
 THE OTHER BATH GFI CIRCUIT ON PANEL SCHEDULE IS NOT ON
 PLANS.
 PLEASE SEE PLANS INDICATE NEW RECESSED LIGHTING HOWEVER
 PLANS ALSO INDICATE THESE AS EXISTING IN BATHROOMS.
 NOTES ON LEFT HAND SIDE OF PLANS CLEARLY STATES THE
 RECESSED LIGHTS ARE NEW.
 PLEASE CORRELATE.
 PLEASE SEE PLANS INDICATE A NEW RECEPTACLE IN BEDROOM
 WITHOUT ANY CIRCUITING/ARC FAULT PROTECTION. (210.12).
 PLEASE VERIFY THE OVER CURRENT PROTECTION FOR THE AHU
 AS 50AMP IS HIGH FOR A 5KW UNIT.
 408.4, 310.16, 240.4
 FBC 106.3.5.1.2
  
 2) NOTE: PLEASE SEE THE PANEL IS BEING SHOWN BOTH AS
 150AMP AND 200AMP? PLEASE CLARIFY.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717