| 2007-08-10 19:06:27 | THE NOTICE OF COMMENCMENT IS VOID AS IT HAS EXPIRED PER |
| | FS 713.13(2). |
| | THIS IS ONLY NEEDED TO BE RE-RECORDED AND SUBMITTED |
| | BEFORE PICKING UP PERMIT. |
| 2007-08-10 19:01:54 | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE THE CIRCUITING ON THE PLANS NEEDS |
| | TO COORDINATE ON PLANS AND PANEL SCHEDULE. |
| | PLEASE SEE FOR EXAMPLE THE DRYER IS SHOWN AS 5KW WITH |
| | 12 AWG AND 20AMP OVER CURRENT PROTECTION. |
| | PLEASE SEE THE BATH CIRCUIT ON PLANS WHICH IS SHOWN AS |
| | A SPARE CIRCUIT ON PANEL SCHEDULE. PLEASE ALSO SEE THAT |
| | THE OTHER BATH GFI CIRCUIT ON PANEL SCHEDULE IS NOT ON |
| | PLANS. |
| | PLEASE SEE PLANS INDICATE NEW RECESSED LIGHTING HOWEVER |
| | PLANS ALSO INDICATE THESE AS EXISTING IN BATHROOMS. |
| | NOTES ON LEFT HAND SIDE OF PLANS CLEARLY STATES THE |
| | RECESSED LIGHTS ARE NEW. |
| | PLEASE CORRELATE. |
| | PLEASE SEE PLANS INDICATE A NEW RECEPTACLE IN BEDROOM |
| | WITHOUT ANY CIRCUITING/ARC FAULT PROTECTION. (210.12). |
| | PLEASE VERIFY THE OVER CURRENT PROTECTION FOR THE AHU |
| | AS 50AMP IS HIGH FOR A 5KW UNIT. |
| | 408.4, 310.16, 240.4 |
| | FBC 106.3.5.1.2 |
| | |
| | 2) NOTE: PLEASE SEE THE PANEL IS BEING SHOWN BOTH AS |
| | 150AMP AND 200AMP? PLEASE CLARIFY. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |