| Date |
Text |
| 2007-06-29 16:14:31 | *** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SE MOST COMMENTS FROM PREVIOUS REVIEW AS |
| | STILL IN NEED OF ADDRESSING. PLEASE SEE NEW COMMENT |
| | BASED ON THE SHEETS SUBMITTED. |
| | |
| | 1) NOTE:NO, SAME NOTE: |
| | PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE CODES TO |
| | BE STATED ON PLANS. |
| | PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL |
| | AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE |
| | KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. |
| | PLEASE LIST THE FOLLOWING |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: NO, SAME NOTE: |
| | PLEASE SEE FS 481.229 AS THE PLANS ARE REQUIRED TO BE |
| | DONE BY AN ARCHITECT AT A MINIMUM. PLEASE BE SURE TITLE |
| | BLOCKS ARE COMPLETE, PLANS CONTAIN THE PRINTED NAME, |
| | SEAL AND SIGNATURE OF THE DESIGNER OF RECORD. |
| | FAC 61G1-16.004 |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 3) NOTE: NO, SAME NOTE: PLEASE SEE THAT ONLY TWO SMOKE |
| | DEVICES WERE ADDED AND ARE NOW BEING SHOWN AS SMOKE |
| | DETECTORS AND NOT SMOKE ALARMS. IF THESE ARE SMOKE |
| | DETECTORS, PLEASE COMPLETE PLANS ACCORDINGLY TO THESE |
| | TYPES OF DEVICES WHICH REQUIRE HORNS/SOUNDING DEVICES |
| | ALONG WITH PANEL FOR FA |
| | PLEASE SEE THE DEVICES SHOWN W/IN 20FT OF KITCHEN |
| | COOKING APPLIANCE NEEDS TO MEET NFPA-72 11.8.3 |
| | PLEASE SEE CIRCUITING IF 120V REQUIRES AFCI PROTECTION |
| | PER 210.12 OF THE NEC. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC 2004 W/ 2006 REVISIONS R313 WHICH |
| | REQUIRES ALL SMOKE ALARMS OR DETECTORS TO BE BROUGHT UP |
| | TO CODE IF THE EXISTING DOES NOT MEET CODE. PLEASE |
| | INDICATE WHICH TYPES OF DEVICES ARE TO BE INSTALLED, |
| | EXISTING AND LOCATIONS PER NFPA-72 11.5.1.1, 11.8.3. |
| | |
| | 4) NOTE: NO, SAME NOTE: |
| | PLEASE INDICATE THE MINIMUM CIRCUITS AND GFI RECEPTACLE |
| | LOCATIONS IN KITCHEN IF NEW OR EXISTING. SMALL |
| | APPLIANCE(S), 20AMP #12 PER 210.52B1, 210.11C1, 220.53, |
| | 210.52C1-5 |
| | AS SHOWN NEW, PLEASE SUBMIT A PANEL SCHEDULE, INDICATE |
| | CIRCUITS ON PLANS AND CORRELATE WITH THE PANEL |
| | SCHEDULE. |
| | |
| | 5) NOTE: NO, SAME NOTE: |
| | PLEASE INDICATE THE MINIMUM REQUIRED CIRCUITS FOR |
| | BATHS,DEDICATED CIRCUIT(S) ARE PER 210.52D, |
| | 210.11C3. |
| | MUST BE 20AMP AND #12. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: NOTE TO REMAIN AS NOT ALL DEVICES AND TYPE ARE |
| | COMPLETE. |
| | PLEASE CLARIFY ALL SYMBOLS ON PLANS WITH A SYMBOLS |
| | LEGEND. |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: NO, SAME NOTE: |
| | PLEASE SEE 210.4 FOR POSSIBLE TYPE OF BREAKER REQUIRED |
| | FOR ANY DISPOSAL AND DISHWASHER FEEDING THE SAME YOKE. |
| | |
| | ******* NEW NOTE **** |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |