Plan Review Notes
Plan Review Notes For Permit 07050907
Permit Number 07050907
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-29 16:14:31*** UNSAT 2ND REVIEW ***
  
 ** PLEASE SE MOST COMMENTS FROM PREVIOUS REVIEW AS
 STILL IN NEED OF ADDRESSING. PLEASE SEE NEW COMMENT
 BASED ON THE SHEETS SUBMITTED.
  
 1) NOTE:NO, SAME NOTE:
 PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE CODES TO
 BE STATED ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: NO, SAME NOTE:
 PLEASE SEE FS 481.229 AS THE PLANS ARE REQUIRED TO BE
 DONE BY AN ARCHITECT AT A MINIMUM. PLEASE BE SURE TITLE
 BLOCKS ARE COMPLETE, PLANS CONTAIN THE PRINTED NAME,
 SEAL AND SIGNATURE OF THE DESIGNER OF RECORD.
 FAC 61G1-16.004
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: NO, SAME NOTE: PLEASE SEE THAT ONLY TWO SMOKE
 DEVICES WERE ADDED AND ARE NOW BEING SHOWN AS SMOKE
 DETECTORS AND NOT SMOKE ALARMS. IF THESE ARE SMOKE
 DETECTORS, PLEASE COMPLETE PLANS ACCORDINGLY TO THESE
 TYPES OF DEVICES WHICH REQUIRE HORNS/SOUNDING DEVICES
 ALONG WITH PANEL FOR FA
 PLEASE SEE THE DEVICES SHOWN W/IN 20FT OF KITCHEN
 COOKING APPLIANCE NEEDS TO MEET NFPA-72 11.8.3
 PLEASE SEE CIRCUITING IF 120V REQUIRES AFCI PROTECTION
 PER 210.12 OF THE NEC.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS R313 WHICH
 REQUIRES ALL SMOKE ALARMS OR DETECTORS TO BE BROUGHT UP
 TO CODE IF THE EXISTING DOES NOT MEET CODE. PLEASE
 INDICATE WHICH TYPES OF DEVICES ARE TO BE INSTALLED,
 EXISTING AND LOCATIONS PER NFPA-72 11.5.1.1, 11.8.3.
  
 4) NOTE: NO, SAME NOTE:
 PLEASE INDICATE THE MINIMUM CIRCUITS AND GFI RECEPTACLE
 LOCATIONS IN KITCHEN IF NEW OR EXISTING. SMALL
 APPLIANCE(S), 20AMP #12 PER 210.52B1, 210.11C1, 220.53,
 210.52C1-5
 AS SHOWN NEW, PLEASE SUBMIT A PANEL SCHEDULE, INDICATE
 CIRCUITS ON PLANS AND CORRELATE WITH THE PANEL
 SCHEDULE.
  
 5) NOTE: NO, SAME NOTE:
 PLEASE INDICATE THE MINIMUM REQUIRED CIRCUITS FOR
 BATHS,DEDICATED CIRCUIT(S) ARE PER 210.52D,
 210.11C3.
 MUST BE 20AMP AND #12.
  
 6) NOTE: OK.
  
 7) NOTE: NOTE TO REMAIN AS NOT ALL DEVICES AND TYPE ARE
 COMPLETE.
 PLEASE CLARIFY ALL SYMBOLS ON PLANS WITH A SYMBOLS
 LEGEND.
 FBC 106.1.2
  
 8) NOTE: NO, SAME NOTE:
 PLEASE SEE 210.4 FOR POSSIBLE TYPE OF BREAKER REQUIRED
 FOR ANY DISPOSAL AND DISHWASHER FEEDING THE SAME YOKE.
  
 ******* NEW NOTE ****
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]