Plan Review Notes
Plan Review Notes For Permit 07050907
Permit Number 07050907
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-03 16:00:41** UNSAT**
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE FS 481.229 AS THE PLANS ARE
 REQUIRED TO BE DONE BY AN ARCHITECT AT A MINIMUM.
 PLEASE BE SURE TITLE BLOCKS ARE COMPLETE, PLANS CONTAIN
 THE PRINTED NAME, SEAL AND SIGNATURE OF THE DESIGNER OF
 RECORD.
 FAC 61G1-16.004
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS R313
 WHICH REQUIRES ALL SMOKE ALARMS OR DETECTORS TO BE
 BROUGHT UP TO CODE IF THE EXISTING DOES NOT MEET CODE.
 PLEASE INDICATE WHICH TYPES OF DEVICES ARE TO BE
 INSTALLED, EXISTING AND LOCATIONS PER NFPA-72 11.5.1.1,
 11.8.3.
  
 4) NOTE: PLEASE INDICATE THE MINIMUM CIRCUITS AND GFI
 RECEPTACLE LOCATIONS IN KITCHEN IF NEW OR EXISTING.
 SMALL APPLIANCE(S), 20AMP #12 PER 210.52B1, 210.11C1,
 220.53, 210.52C1-5
 AS SHOWN NEW, PLEASE SUBMIT A PANEL SCHEDULE, INDICATE
 CIRCUITS ON PLANS AND CORRELATE WITH THE PANEL
 SCHEDULE.
  
 5) NOTE: PLEASE INDICATE THE MINIMUM REQUIRED CIRCUITS
 FOR BATHS,DEDICATED CIRCUIT(S) ARE PER 210.52D,
 210.11C3.
 MUST BE 20AMP AND #12.
  
 6) NOTE: PLEASE SHOW LOCATION OF THE EXISTING PANEL.
 110.26, 408.7, 240.24.
 FBC 106.1.2.
  
 7) NOTE: PLEASE CLARIFY ALL SYMBOLS ON PLANS WITH A
 SYMBOLS LEGEND.
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE 210.4 FOR POSSIBLE TYPE OF BREAKER
 REQUIRED FOR ANY DISPOSAL AND DISHWASHER FEEDING THE
 SAME YOKE.
  
 9) NOTE: PLEASE CLARIFY ADDRESS AS THE PERMIT
 APPLICATION STATES UNIT 2110 AND PLANS STATE 211?
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]