| Date |
Text |
| 2007-10-04 09:12:49 | NEW RESIDENCE TRUSS DRAWINGS BUILDING REVIEW FIRST |
| | CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE AND 2004 |
| | FBC. |
| | |
| | 1- ENGINEER OF RECORD NEEDS TO REVIEW AND APPROVE TRUSS |
| | PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 2- "EACH OF THE DRAWINGS IN THE TRUSS DESIGN PACKAGE |
| | FOR INDIVIDUAL TRUSSES SHALL INCLUDE A TITLE BLOCK |
| | BEARING THE PRINTED NAME, ADDRESS, AND LICENSE NUMBER |
| | OF THE TRUSS DESIGN ENGINEER AND THE DATE OF THE |
| | DRAWINGS" AS REQUIRED BY SEC. 61G15-31.003(5) OF |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 3- ALL GENERAL DETAILS NEED TO HAVE ENGINEER'S ORIGINAL |
| | SEAL, SIGNATURE AND DATE AS WELL AS ALL ENGINEER'S |
| | INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE |
| | AND SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 4- SOME OF THE GENERAL DETAILS INCLUDED IN THE TRUSS |
| | PACKAGE ARE NOT LEGIBLE. PLEASE, MAKE SURE ALL COPIES |
| | ARE CLEAR AND LEGIBLE PRIOR TO SUBMITTAL. SEC. 106.1.3 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 5- UPDATE "TRUSSED VALLEY DETAIL".DETAIL IS REFERRING |
| | TO ASCE 7-98 AND 100MPH. REVISEAS REQUIRED USING ASCE |
| | 7-02 AND 140MPH. |
| | |
| | 6- CONNECTORS SPECIFIED FOR ROOF TRUSS H7A DON'T RESIST |
| | THE CALCULATED UPLIFT LOADS. ENGINEER OF RECORD TO |
| | REVISEROOF FRAMING PLAN AND TRUSS ANCHOR SCHEDULE AS |
| | REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 7- ROOF TRUSS H5 REQUIRES ANCHORING AT DIFFERENT |
| | POINTS. NO JUST AT THE ENDS AS SHOWN ON ENGINEER'S OF |
| | RECORD ROOF FRAMING PLAN.ENGINEER OF RECORD TO REVISE |
| | ROOF FRAMING PLAN ANDTRUSS ANCHOR SCHEDULE AS |
| | REQUIRED TO PROVIDE PROPER ANCHORING FOR ROOF TRUSS H5. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 8- TRUSS PACKAGE INDEX SHEET IS MISSING THE NAME OF THE |
| | ENGINEER OF RECORD AS REQUIRED BY SEC. |
| | 61G15-31.003(5). |
| | |
| | 9- THESE COMMENTS APPLY TO MAIN RESIDENCE AND GUEST |
| | HOUSE TRUSS PACKAGE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |