| Notes |
| Date |
Text |
| 2007-05-29 09:26:11 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) PLEASE SHOW THE SEER OF THE A/C SYSTEMS ON THE | | | MECHANICAL PLANS. | | | | | | 3) PLEASE SHOW THE LOCATION OF THE CLOTHES DRYER VENTS | | | TERMINATION ON THE MECHANICAL PLANS, BE ADVISED THE | | | CLOTHES DRYERS MAY NOT DISCHARGE NEAR THE A/C CONDENSER | | | UNITS, SEE 2004 FBC/M 501.2 . | | | | | | 4) SEE COOLING LOAD CALCULATIONS PAGE 3 SHOWS NO | | | MINIMUM AND MAXIMUM VELOCITY'S, PLEASE CORRECT. | | | | | | 5) SEE MECHANICAL PLANS FOR THE COTTAGE THE 6" MAIN | | | SUPPLY DUCT TO THE MIXING BOX AT 800 CFM'S WOULD BE A | | | HIGH PRESSURE DUCT, PLEASE SHOW ON PLANS THAT THE DUCTS | | | ARE TO BE METAL AS FLEX DUCT IS NOT RATED FOR HIGH | | | PRESSURE, OR RE-CALCULATE DUCT CALCULATIONS. | | | | | | 6) SEE MECHANICAL PLANS MAIN HOUSE THE TWO 6" MAIN | | | SUPPLY AIR DUSTS TO THE MIXING BOXES APPEARS TO BE A | | | MISTAKE PLEASE RE-CALCULATE DUCT CALCULATIONS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|