| 2007-06-29 18:59:31 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED TO PROVIDE TWO SETS WITH ORIGINAL ENGINEER'S |
| | SEAL AND SIGNATURE. ONLYONE SET WAS SIGNED AND |
| | SEALED. |
| | |
| | 2- REVISE DRAINAGE PLAN.WATER NEED TO BE DIVERTED |
| | AWAY FROM THE NEIGHBOR'S PROPERTY.ARROWS SHOWN ON |
| | SURVEY SHOW WATER LEADING TO THE NEIGHBOR'S PROPERTY. |
| | REVISE AS REQUIRED. |
| | |
| | 3- ENERGY CALCULATIONS NEED TO BE SIGNED AND DATED BY |
| | THE OWNER/AGENT. |
| | ALSO, COMPLETE INFORMATION ON TOP OF FORM AND REVISE |
| | OWNER INFORMATION. |
| | |
| | 4- DRAWINGS TO HAVE CORRECT ADDRESS. THIS PROPERTY IS |
| | LOCATED ON LOT 8, NOT 9. REVISE AS REQUIRED. |
| | |
| | 5- OWES $2046.13 FOR UPDATED VALUATION AND RADON FEES |
| | AND PERMIT FEE BALANCE. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) ALLSIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. |
| | ***NOTE: PROVIDE ONLY THE FLROIDA PRODUCT APPROVAL |
| | COVERPAGE AND SHEET WHERE CONENCTORS IS SHOWN. 7- |
| | ENGINEER OF RECORDNEEDS TO REVIEW AND APPROVEIN |
| | WRITING (NOT SIGNING AND SEALING)ALL PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 8- REVISE ROOF SHEATHING SPECIFICATIONS. SEE SEC. |
| | R803.2.3.1 FOR MINIMUM TYPE OF NAIL TO BE USED AND |
| | SPACING FOR CORNER AREAS. |
| | |
| | 9- FLOOR PLAN DOESN'T SPECIFY SIZE AND TYPE OF WINDOW |
| | IN MASTER BEDROOM. NEED INFOMATION TO VERIFY COMPLIANCE |
| | WITH EGRESS REQUIREMENTS. REVISE ORIGINAL PLAN AS |
| | REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |