| 2009-08-29 16:15:17 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS P-1, P-3 & P-4 THE REVISIONS OF THE ENGINEER OF |
| | RECORD SHALL BE SIGNED, SEALED AND DATED BY THE |
| | ENGINEER OF RECORD. SECTION 106.1, FAC 61G15-23.002 & |
| | FS 471.205. |
| | |
| | 2. SHT P-1 PER SECTION 106.1.1 PLANS & DRAWINGS SHALL |
| | BE OF SUFFICIENT CLARITY. THERE APPEARS TO BE FIXTURES |
| | DELETED, BUT THE VENTING IS STILL SHOWN. OTHER FIXTURES |
| | APPEAR TO HAVE WHITE OUT BUT THE FIXTURE IS NOT |
| | INDICATED AS BEING DELETED. OTHER FIXTURES HAVE HAD |
| | AAV'S INSTALLED BUT THE VENTING IS STILL SHOWN. PLEASE |
| | CLARIFY. SECTION 917. |
| | |
| | 3. SHT P-1 SHOWS TWO BULING DRAIN/BRANCH LINES |
| | CONNECTING TO THE EXISTING SANITARY IN TREATMENT ROOM |
| | 107. THAT DOES NOT REFLECT THE RISER DIAGRAM. PLEASE |
| | CORRELATE. SECTIONS 106.1.1 & 701.1. |
| | |
| | 4. SHT P-1 SHOWS TWO DRAIN LINES TO THE SHOWER DRAIN IN |
| | MEN'S LOCKER ROOM # 105. PLEASE CLARIFY. SECTIONS |
| | 106.1.1 & 701.1. |
| | |
| | 5. SHT P-1 INDICATES "AAV IN WALL" BETWEEN MEN'S AND |
| | WOMEN'S LOCKER ROOMS. WHAT FIXTURE(S) DOES IT VENT. |
| | SECTIONS 106.1.1 & 901.1. |
| | |
| | 6. SHT P-1 STATES RELIEF VENT BUT DOES NOT SHOW THE |
| | RELIEF VENT. PLEASE INDICATE THE LOCATION OF THE |
| | REQUIRED RELIEF VENT. SECTIONS 106.1.1 & 917.3.2. |
| | |
| | 7. SHT P-1 ON FILE FOR PUBLIC RECORD SHOWS A REVISION |
| | #2 DATED 8-5-08. NEW REVISIONS WILL REQUIRED A NEW |
| | REVISION NUMBER AS THE REVISION NUMBERS SHALL BE |
| | RETAINED ON RECORD FOR THE LIFE OF THE PROJECT. SECTION |
| | 106.1.3. |
| | |
| | 8. SHT P-3 ON FILE FOR PUBLIC RECORD SHOWS A REVISION |
| | #2 DATED 8-5-08. NEW REVISIONS WILL REQUIRED A NEW |
| | REVISION NUMBER AS THE REVISION NUMBERS SHALL BE |
| | RETAINED ON RECORD FOR THE LIFE OF THE PROJECT. SECTION |
| | 106.1.3. |
| | |
| | 9. SHTS P-3 & P-4 SHOWS CHANGES TO THE SANITARY FOR THE |
| | SECOND FLOOR. A REVISION FOR SHT P-2, (2ND FLOOR), IS |
| | REQUIRED TO REFLECT THE CHANGES INDICATED ON SHT P-3. |
| | SECTION 106.1.1. |
| | |
| | 10. SHT P-3 INDICATE THE LOCATION OF THE REQUIRED |
| | RELIEF VENT FOR THE AIR ADMITTANCE VALVES. SECTION |
| | 917.3.2. |
| | |
| | 11. SHT P-3 SANITARY RISER DIAGRAM DOES NOT REFLECT SHT |
| | P-1 SUBMITTED FOR REVISION NOR DOES IT REFLECT SHT P-2 |
| | ON FILE FOR PUBLIC RECORD. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 12. SHT P-3 VENTING FROM THE PUMP ROOM DOES NOT REFLECT |
| | VENTING AS SHOWN ON FLOOR PLAN. REVISION SHOWS THE |
| | VENTING FROM THE PUMP ROOM COMMING FROM THE 2ND FLOOR, |
| | NOT THE 1ST FLOOR. PLEASE CORRELATE. SECTIONS 106.1.1 & |
| | 901.1. |
| | |
| | 13. SHT P-3 THE DRAIN PIPING FROM THE W/C IN TOILET |
| | ROOM 105A DOES NOT REFLECT THE CHANGES SHOWN ON SHT |
| | P-1. PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1. |
| | |
| | 14. SHT P-3 SHOW THE PIPE SIZE FOR ALL NEW/REVISED |
| | SANITARY PIPING. TABLES 710.1(1) & 710.1(2). |
| | |
| | 15. SHT P-4 ON FILE FOR PUBLIC RECORD SHOWS A REVISION |
| | #2 DATED 8-5-08. NEW REVISIONS WILL REQUIRED A NEW |
| | REVISION NUMBER AS THE REVISION NUMBERS SHALL BE |
| | RETAINED ON RECORD FOR THE LIFE OF THE PROJECT. SECTION |
| | 106.1.3. |
| | |
| | 16. SHT P-4 THE WATER SUPPLY TO THE RAIN SHOWER, FLUSH |
| | RING TO SHOWER DRAIN & SINK HAVE BEEN DELETED ON THE |
| | WATER RISER DIAGRAM. PLEASE INDICATE WHERE THE HOT & |
| | COLD WATER SUPPLY FOR THESE FIXTURES WILL COMMING FROM. |
| | SECTION 604. |
| | |
| | 17. SHT P-4 INDICATES THE WATER SUPPLY LINES TO A |
| | SHOWER HAS BEEN DELETED, BUT ALL THREE SHOWERS ARE |
| | STILL INDICATED ON SHEET P-1. PLEASE CLARIFY. SECTIONS |
| | 106.1.1 & 601.1. |
| | |
| | 18. SHT P-4 INDICATES A HOT WATER LINE TO THE ROOF. |
| | PLEASE CLARIFY. WHAT IS THE HOT WATER LINE TO THE ROOF |
| | FOR. SECTION 106.1.2 (MORE INFORMATION REQUIRED). |
| | |
| | 19. SHT P-4 SECOND COLD WATER LINE TO TREATMENT ROOMS |
| | 113, 114 & 115 DOES NOT SHOW WHERE IT CONNECTS TO THE |
| | COLD WATER SUPPL MAIN. PLEASE CLARIFY. SECTIONS 106.1.1 |
| | & 604. |
| | |
| | 20 SHT P-4 SHOWS A COLD WATER LINE CONNECTING TO THE SP |
| | LINE AND THEN CONNECTING TO THE HOT WATER LINE. PLEASE |
| | CLARIFY. SECTIONS 106.1.1 & 604. |
| | |
| | 21. SHTS P-1, P-3 & P-4 REVISIONS ARE DIFFICULT TO |
| | FOLLOW AND REVIEW AS THERE APPEARS TO BE A LOT OF WHITE |
| | OUT, LINES ERASED AND THEY LACK CLARITY OF THE ORIGINAL |
| | PLANS. PLEASE CLEAR UP REVISION PRIOR TO RESUBMITTING |
| | FOR REVIEW. SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |