Plan Review Notes
Plan Review Notes For Permit 07050880
Permit Number 07050880
Review Stop P
Sequence Number 6
Notes
Date Text
2009-08-29 16:15:17DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P-1, P-3 & P-4 THE REVISIONS OF THE ENGINEER OF
 RECORD SHALL BE SIGNED, SEALED AND DATED BY THE
 ENGINEER OF RECORD. SECTION 106.1, FAC 61G15-23.002 &
 FS 471.205.
  
 2. SHT P-1 PER SECTION 106.1.1 PLANS & DRAWINGS SHALL
 BE OF SUFFICIENT CLARITY. THERE APPEARS TO BE FIXTURES
 DELETED, BUT THE VENTING IS STILL SHOWN. OTHER FIXTURES
 APPEAR TO HAVE WHITE OUT BUT THE FIXTURE IS NOT
 INDICATED AS BEING DELETED. OTHER FIXTURES HAVE HAD
 AAV'S INSTALLED BUT THE VENTING IS STILL SHOWN. PLEASE
 CLARIFY. SECTION 917.
  
 3. SHT P-1 SHOWS TWO BULING DRAIN/BRANCH LINES
 CONNECTING TO THE EXISTING SANITARY IN TREATMENT ROOM
 107. THAT DOES NOT REFLECT THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 4. SHT P-1 SHOWS TWO DRAIN LINES TO THE SHOWER DRAIN IN
 MEN'S LOCKER ROOM # 105. PLEASE CLARIFY. SECTIONS
 106.1.1 & 701.1.
  
 5. SHT P-1 INDICATES "AAV IN WALL" BETWEEN MEN'S AND
 WOMEN'S LOCKER ROOMS. WHAT FIXTURE(S) DOES IT VENT.
 SECTIONS 106.1.1 & 901.1.
  
 6. SHT P-1 STATES RELIEF VENT BUT DOES NOT SHOW THE
 RELIEF VENT. PLEASE INDICATE THE LOCATION OF THE
 REQUIRED RELIEF VENT. SECTIONS 106.1.1 & 917.3.2.
  
 7. SHT P-1 ON FILE FOR PUBLIC RECORD SHOWS A REVISION
 #2 DATED 8-5-08. NEW REVISIONS WILL REQUIRED A NEW
 REVISION NUMBER AS THE REVISION NUMBERS SHALL BE
 RETAINED ON RECORD FOR THE LIFE OF THE PROJECT. SECTION
 106.1.3.
  
 8. SHT P-3 ON FILE FOR PUBLIC RECORD SHOWS A REVISION
 #2 DATED 8-5-08. NEW REVISIONS WILL REQUIRED A NEW
 REVISION NUMBER AS THE REVISION NUMBERS SHALL BE
 RETAINED ON RECORD FOR THE LIFE OF THE PROJECT. SECTION
 106.1.3.
  
 9. SHTS P-3 & P-4 SHOWS CHANGES TO THE SANITARY FOR THE
 SECOND FLOOR. A REVISION FOR SHT P-2, (2ND FLOOR), IS
 REQUIRED TO REFLECT THE CHANGES INDICATED ON SHT P-3.
 SECTION 106.1.1.
  
 10. SHT P-3 INDICATE THE LOCATION OF THE REQUIRED
 RELIEF VENT FOR THE AIR ADMITTANCE VALVES. SECTION
 917.3.2.
  
 11. SHT P-3 SANITARY RISER DIAGRAM DOES NOT REFLECT SHT
 P-1 SUBMITTED FOR REVISION NOR DOES IT REFLECT SHT P-2
 ON FILE FOR PUBLIC RECORD. PLEASE CORRELATE. SECTION
 106.1.1.
  
 12. SHT P-3 VENTING FROM THE PUMP ROOM DOES NOT REFLECT
 VENTING AS SHOWN ON FLOOR PLAN. REVISION SHOWS THE
 VENTING FROM THE PUMP ROOM COMMING FROM THE 2ND FLOOR,
 NOT THE 1ST FLOOR. PLEASE CORRELATE. SECTIONS 106.1.1 &
 901.1.
  
 13. SHT P-3 THE DRAIN PIPING FROM THE W/C IN TOILET
 ROOM 105A DOES NOT REFLECT THE CHANGES SHOWN ON SHT
 P-1. PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 14. SHT P-3 SHOW THE PIPE SIZE FOR ALL NEW/REVISED
 SANITARY PIPING. TABLES 710.1(1) & 710.1(2).
  
 15. SHT P-4 ON FILE FOR PUBLIC RECORD SHOWS A REVISION
 #2 DATED 8-5-08. NEW REVISIONS WILL REQUIRED A NEW
 REVISION NUMBER AS THE REVISION NUMBERS SHALL BE
 RETAINED ON RECORD FOR THE LIFE OF THE PROJECT. SECTION
 106.1.3.
  
 16. SHT P-4 THE WATER SUPPLY TO THE RAIN SHOWER, FLUSH
 RING TO SHOWER DRAIN & SINK HAVE BEEN DELETED ON THE
 WATER RISER DIAGRAM. PLEASE INDICATE WHERE THE HOT &
 COLD WATER SUPPLY FOR THESE FIXTURES WILL COMMING FROM.
 SECTION 604.
  
 17. SHT P-4 INDICATES THE WATER SUPPLY LINES TO A
 SHOWER HAS BEEN DELETED, BUT ALL THREE SHOWERS ARE
 STILL INDICATED ON SHEET P-1. PLEASE CLARIFY. SECTIONS
 106.1.1 & 601.1.
  
 18. SHT P-4 INDICATES A HOT WATER LINE TO THE ROOF.
 PLEASE CLARIFY. WHAT IS THE HOT WATER LINE TO THE ROOF
 FOR. SECTION 106.1.2 (MORE INFORMATION REQUIRED).
  
 19. SHT P-4 SECOND COLD WATER LINE TO TREATMENT ROOMS
 113, 114 & 115 DOES NOT SHOW WHERE IT CONNECTS TO THE
 COLD WATER SUPPL MAIN. PLEASE CLARIFY. SECTIONS 106.1.1
 & 604.
  
 20 SHT P-4 SHOWS A COLD WATER LINE CONNECTING TO THE SP
 LINE AND THEN CONNECTING TO THE HOT WATER LINE. PLEASE
 CLARIFY. SECTIONS 106.1.1 & 604.
  
 21. SHTS P-1, P-3 & P-4 REVISIONS ARE DIFFICULT TO
 FOLLOW AND REVIEW AS THERE APPEARS TO BE A LOT OF WHITE
 OUT, LINES ERASED AND THEY LACK CLARITY OF THE ORIGINAL
 PLANS. PLEASE CLEAR UP REVISION PRIOR TO RESUBMITTING
 FOR REVIEW. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  