Plan Review Notes
Plan Review Notes For Permit 07050880
Permit Number 07050880
Review Stop P
Sequence Number 4
Notes
Date Text
2008-07-21 11:38:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****REREVIEW OF PLANS. THERE WAS CONFUSION BECAUSE OF
 MULTIPLE "P" SHEETS AND THE ENGINEERS "P" SHEETS WERE
 NOT REVIEWED. SOME COMMENTS WILL BE DELETED BECAUSE OF
 THE MEETING HELD ON 9-13-7. THERE WILL BE SOME NEW
 COMMENTS BECAUSE OF THE REVIEW OF THE ENGINEERS
 SHEETS.
  
 ******FROM PREVIOUS REVIEWS:
  
 ********FROM PREVIOUS REVIEWS:
  
  
 1. ALL SHEETS WITH NEW WORLD DESIGN STUDIO LLC TITLE
 BLOCK. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET PER FAC 61G1-16.004(2) & FS 481.219, 481.2055.
 ****RESPONSE NOTED, BUT THERE ARE STILL SHEETS WITH NEW
 WORLD DESIGN STUDIO LLC IN THE TITLE BLOCK OF SOME
 SHEETS. PLEASE DELETE OR INDICATE FIRM LICENSE NUMBER
 IN THE TITLE BLOCKS.
 ********NO RESPONSE, COMMENT NOT ADDRESSED. NEW WORLD
 DESIGN STUDIO LLC IS STILL INDICATED IN THE TITLE BLOCK
 OF EACH SHEET AND AS SUCH THE COMPANY IS STILL
 ADVERTISING AS A COMPANY.
  
 2. OK
 3. OK
 4. OK
 5. OK
  
 6. SHT A1.0 INDICATES A WATERFALL CLOSET. PLEASE SUBMIT
 A DETAIL FOR THE CLOSET. INDICATE IF THERE WILL BE
 DRAINAGE AND/OR WATER SUPPLY. BACKFLOW PROTECTION IS
 REQUIRED IF CONNECTED TO A POTABLE WATER SOURCE PER
 SECTION 608. SECTION 106.1.1. SUBMIT A DETAIL FOR THE
 WATERFALL WALL.
 ******RESPONSE NOTED, BUT NO RESPONSE FROM THE
 ENGINEER. WATER SUPPLY NOTED, BUT DRAINAGE NOT
 INDICATED.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 7. OK
 8. OK
 9. N/A
 10. N/A - CENTRAL WATER HEATER IN BLDG.
 11. N/A NO GAS WORK
  
 ****NEW COMMENTS SAME NUMBER SEQUENCE:
  
 12. OK
 13. OK
 14. OK
  
 15. SHT P-2 KEY NOTES 4, 7 & 14 NOT FOUND. SECTION
 106.1.1. PLEASE CLARIFY.
 ******RESPONSE NOTED, BUT NOW KEY NOTE #3 IS OMITED,
 BUT IS INDICATED ON THE FLOOR PLAN & KEY NOTE #6 IS NOT
 FOUND.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 16. OK
  
 17. SHT P-2 KEY NOTE 3 BY RAIN SHOWER ROOM DOES NOT
 REFLECT THE KEY NOTE. SECTION 106.1.1. PLEASE
 CORRELATE.
 ******RESPONSE NOTED, BUT KEY NOTE #3 IS OMITED BUT
 SHOWN ON THE FLOOR PLAN.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 18. SHT P-3 SANT. RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN OF THE VENTS. SEE SECTIONS TO THE LEFT OF
 WERE THE 3" VENT TO RISER S/17 CONNECTS TO THE 2' & 3"
 HORIZONTAL VENT LINE.
 ******RESPONSE NOTED, BUT THE VENT FROM SINK IN ROOM
 107 IS SHOWN CONNECTING TO THE VENT ON THE 1ST FLOOR ON
 THE FLOOR PLAN, BUT IS SHOWN CONNECTING TO THE VENT ON
 THE SECOND FLOOR ON THE RISER DIAGRAM. PLEASE RECHECK
 RISER CORRELATE WITH FLOOR PLAN.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 19. SHT P-4 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN, SHOWS TWO COLD LINES BY THE RAIN SHOWER,
 AND IN THE MEN'S LOCKER ROOM WHERE THE BRANCH FOR THE
 LAV FROM ROOM 105A CONNECTS TO THE MAIN.--ALSO
 RISER DOES NOT MEET CODE AS THERE ARE NO WATER HAMMER
 ARRESTORS AT THE WASH MACHINE AS REQUIRED PER SECTION
 604.9. PLEASE MAKE SURE ALL QUICK CLOSING VALVES SHOW
 WATER HAMMER ARRESTORS. SECTION 106.1.1. ******RESPONSE
 NOTED, BUT THE CONNECTION TO THE LAV IN ROOM 105A HAS
 NOT BEEN CHANGED AND STILL DOES NOT REFLECT THE FLOOR
 PLAN.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ******NEW COMMENTS******
  
 1C. SHT P-2 CORRECTIONS INDICATED FROM THE ENGINEER
 SHOW A FUNNEL FLOOR DRAIN FOR THE SPILLAGE FROM THE
 STEAM GENERATOR. AN EMERGENCY PAN SHALL BE INSTALLED
 AND THE INDIRECT WASTE SHALL DRAIN INTO A FLOOR SINK OR
 HUB DRAIN AS A FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SECTION 504.7, 802.3 & 802.3.2.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2C. SHT P-4 THE ENGINEERINDICATES WATER ISOMETRIC
 REVISED TO REFLECT THE FLOOR PLAN, BUT IT DOES NOT
 COMPLETLY REFLECT. PLEASE CORRELATE.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3C. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]