2008-07-18 13:28:35** DENIED 4TH REVIEW**
  
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT CODE COMPLIANT. THE DESIGN WATTAGE IS SHOWN AS
 6829 WATTS WITH AN ALLOWANCE SHOWN AS 5404. HOW IS IT
 POSSIBLE FOR THIS TO PASS WHEN THE ALLOWANCE IS LOWER
 THAN DESIGN?
 PLEASE EXPLAIN HOW DESIGN IS OVER ALLOWANCE. PLEASE SEE
 OTHER ITEMS SUCH AS DOORS. NONE SHOWN. FLOORS, NONE
 SHOWN ETC.THERE ARE DOORS FORM CONDITIONED SPACE TO
 UNCONDITIONED SPACE YET THE IS BLANK IN THE INPUT DATA
 REPORT.
  
 2) NOTE: PLEASE SEE ONE SET MISSING SHEET E-3. IF THIS
 WAS THE ONLY COMMENT, NEW SHEET COULD BE BROUGHT IN.
 TWO COMPLETE SETS REQUIRED.
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717