Plan Review Notes
Plan Review Notes For Permit 07050880
Permit Number 07050880
Review Stop P
Sequence Number 3
Notes
Date Text
2007-12-11 18:52:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****REREVIEW OF PLANS. THERE WAS CONFUSION BECAUSE OF
 MULTIPLE "P" SHEETS AND THE ENGINEERS "P" SHEETS WERE
 NOT REVIEWED. SOME COMMENTS WILL BE DELETED BECAUSE OF
 THE MEETING HELD ON 9-13-7. THERE WILL BE SOME NEW
 COMMENTS BECAUSE OF THE REVIEW OF THE ENGINEERS
 SHEETS.
  
 ******FROM PREVIOUS REVIEWS:
  
  
 1. ALL SHEETS WITH NEW WORLD DESIGN STUDIO LLC TITLE
 BLOCK. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET PER FAC 61G1-16.004(2) & FS 481.219, 481.2055.
 ****RESPONSE NOTED, BUT THERE ARE STILL SHEETS WITH NEW
 WORLD DESIGN STUDIO LLC IN THE TITLE BLOCK OF SOME
 SHEETS. PLEASE DELETE OR INDICATE FIRM LICENSE NUMBER
 IN THE TITLE BLOCKS.
  
 2. OK
  
 3. SHT T1.1 DETAILS 6 & 11 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C:
 A. OK
 ___FOR LAVS:
 A. 11-4.19.2 CLEARANCE (FIG 31)
 ******RESPONSE NOTED, BUT NOT SHOWN IN DETAIL 5/T1.1 B.
 OK
 C. OK
 4. OK
  
 5. SHT A1.0 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. INDICATE THE LOCATION AND SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ******RESPONSE NOTED, BUT SPOUT IS SHOWN AT 42" ABOVE
 THE FLOOR. 36" REQUIRED. ALSO SECTION 11-4.1.3(10)(A)
 HAS NOT BEEN ADDRESSED.
  
 6. SHT A1.0 INDICATES A WATERFALL CLOSET. PLEASE SUBMIT
 A DETAIL FOR THE CLOSET. INDICATE IF THERE WILL BE
 DRAINAGE AND/OR WATER SUPPLY. BACKFLOW PROTECTION IS
 REQUIRED IF CONNECTED TO A POTABLE WATER SOURCE PER
 SECTION 608. SECTION 106.1.1. SUBMIT A DETAIL FOR THE
 WATERFALL WALL.
 ******RESPONSE NOTED, BUT NO RESPONSE FROM THE
 ENGINEER. WATER SUPPLY NOTED, BUT DRAINAGE NOT
 INDICATED.
  
 7. SHTS P1.0 & P1.1 PLUMBING SCHEDULES DO NOT REFLECT
 THE FLOOR PLANS. ITEMS P7 & P7A INDICATE A QUANTITY OF
 2, BUT THE FLOOR PLAN ONLY SHOWS 1.--ITEM P9B
 INDICATES A QUANTITIY OF 3, BUT FLOOR PLAN ONLY SHOWS
 2.--ITEM P11 INDICATED ON THE SCHEDULE WAS NOT
 FOUND ON THE FLOOR PLAN.--ITEM P13 DOES NOT
 INDICATE A FIXTURE TYPE. PLEASE INDICATED FIXTURE TYPE.
 --ITEM P14 INDICATED ON THE SCHEDULE WAS NOT FOUND ON
 THE FLOOR PLAN.--ITEM P15 INDICATES A QUANTITIY OF
 4, BUT ONLY 2 WERE LOCATED ON THE FLOOR PLAN.--ITEM
 P17 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE
 FLOOR PLAN. PLEASE SUBMIT A DETAIL OR MANUF.
 SPECIFICATION SHEETS FOR THIS ITEM.--ITEM P19
 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE FLOOR
 PLAN.--ITEM P20 INDICATES A QUANTITIY OF 8, BUT
 ONLY 2 ARE FOUND ON THE FLOOR PLAN.--ITEM P21
 INDICATES A QUANTITIY OF 4, BUT ONLY 1 WAS FOUND ON THE
 FLOOR PLAN. PLEASE CLARIFY AND CORRELATE THE SCHEDULE
 AND THE FLOOR PLANS. SECTION 106.1.1. ******RESPONSE
 NOTED, BUT ITEM P9B INDICATES 3 TRENCH DRAINS, BUT
 THESE ARE NOT SHOWN ON THE PLANS. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 8. OK
 9. N/A
 10. N/A - CENTRAL WATER HEATER IN BLDG.
 11. N/A NO GAS WORK
  
 ****NEW COMMENTS SAME NUMBER SEQUENCE:
  
 12. OK
 13. OK
 14. OK
  
 15. SHT P-2 KEY NOTES 4, 7 & 14 NOT FOUND. SECTION
 106.1.1. PLEASE CLARIFY.
 ******RESPONSE NOTED, BUT NOW KEY NOTE #3 IS OMITED,
 BUT IS INDICATED ON THE FLOOR PLAN & KEY NOTE #6 IS NOT
 FOUND.
  
 16. OK
  
 17. SHT P-2 KEY NOTE 3 BY RAIN SHOWER ROOM DOES NOT
 REFLECT THE KEY NOTE. SECTION 106.1.1. PLEASE
 CORRELATE.
 ******RESPONSE NOTED, BUT KEY NOTE #3 IS OMITED BUT
 SHOWN ON THE FLOOR PLAN.
  
 18. SHT P-3 SANT. RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN OF THE VENTS. SEE SECTIONS TO THE LEFT OF
 WERE THE 3" VENT TO RISER S/17 CONNECTS TO THE 2' & 3"
 HORIZONTAL VENT LINE.
 ******RESPONSE NOTED, BUT THE VENT FROM SINK IN ROOM
 107 IS SHOWN CONNECTING TO THE VENT ON THE 1ST FLOOR ON
 THE FLOOR PLAN, BUT IS SHOWN CONNECTING TO THE VENT ON
 THE SECOND FLOOR ON THE RISER DIAGRAM. PLEASE RECHECK
 RISER CORRELATE WITH FLOOR PLAN.
  
 19. SHT P-4 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN, SHOWS TWO COLD LINES BY THE RAIN SHOWER,
 AND IN THE MEN'S LOCKER ROOM WHERE THE BRANCH FOR THE
 LAV FROM ROOM 105A CONNECTS TO THE MAIN.--ALSO
 RISER DOES NOT MEET CODE AS THERE ARE NO WATER HAMMER
 ARRESTORS AT THE WASH MACHINE AS REQUIRED PER SECTION
 604.9. PLEASE MAKE SURE ALL QUICK CLOSING VALVES SHOW
 WATER HAMMER ARRESTORS. SECTION 106.1.1. ******RESPONSE
 NOTED, BUT THE CONNECTION TO THE LAV IN ROOM 105A HAS
 NOT BEEN CHANGED AND STILL DOES NOT REFLECT THE FLOOR
 PLAN.
  
 ******NEW COMMENTS******
  
 1C. SHT P-2 CORRECTIONS INDICATED FROM THE ENGINEER
 SHOW A FUNNEL FLOOR DRAIN FOR THE SPILLAGE FROM THE
 STEAM GENERATOR. AN EMERGENCY PAN SHALL BE INSTALLED
 AND THE INDIRECT WASTE SHALL DRAIN INTO A FLOOR SINK OR
 HUB DRAIN AS A FLOOR SINK IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SECTION 504.7, 802.3 & 802.3.2.
  
 2C. SHT P-4 THE ENGINEERINDICATES WATER ISOMETRIC
 REVISED TO REFLECT THE FLOOR PLAN, BUT IT DOES NOT
 COMPLETLY REFLECT. PLEASE CORRELATE.
  
 3C. THE ARCHITECTURAL DESIGN TEAM OF THE TENANT
 BUILDOUT IS NOT THE SAME AS THE ARCHITECTURAL DESIGN
 TEAM OF THE SHELL BUILDING AND WILL BE REQUIRED TO HAVE
 ALL ARCHITECTURAL & STRUCTURAL SHEETS REVIEWED BY THE
 DESIGN TEAM OF THE SHELL BUILDING AND STAMP APPROVAL
 WITH A SHOP APPROVAL STAMP SUCH AS THAT FOR SUBMITTALS
 PRIOR TO RESUBMITTING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved