| Date |
Text |
| 2007-12-11 18:52:31 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****REREVIEW OF PLANS. THERE WAS CONFUSION BECAUSE OF |
| | MULTIPLE "P" SHEETS AND THE ENGINEERS "P" SHEETS WERE |
| | NOT REVIEWED. SOME COMMENTS WILL BE DELETED BECAUSE OF |
| | THE MEETING HELD ON 9-13-7. THERE WILL BE SOME NEW |
| | COMMENTS BECAUSE OF THE REVIEW OF THE ENGINEERS |
| | SHEETS. |
| | |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | |
| | 1. ALL SHEETS WITH NEW WORLD DESIGN STUDIO LLC TITLE |
| | BLOCK. THE FIRM LICENSE NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH |
| | SHEET PER FAC 61G1-16.004(2) & FS 481.219, 481.2055. |
| | ****RESPONSE NOTED, BUT THERE ARE STILL SHEETS WITH NEW |
| | WORLD DESIGN STUDIO LLC IN THE TITLE BLOCK OF SOME |
| | SHEETS. PLEASE DELETE OR INDICATE FIRM LICENSE NUMBER |
| | IN THE TITLE BLOCKS. |
| | |
| | 2. OK |
| | |
| | 3. SHT T1.1 DETAILS 6 & 11 SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | ___FOR W/C: |
| | A. OK |
| | ___FOR LAVS: |
| | A. 11-4.19.2 CLEARANCE (FIG 31) |
| | ******RESPONSE NOTED, BUT NOT SHOWN IN DETAIL 5/T1.1 B. |
| | OK |
| | C. OK |
| | 4. OK |
| | |
| | 5. SHT A1.0 A DRINKING FOUNTAIN IS REQUIRED PER TABLE |
| | 403.1. INDICATE THE LOCATION AND SUBMIT A DETAIL |
| | SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL |
| | SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | ******RESPONSE NOTED, BUT SPOUT IS SHOWN AT 42" ABOVE |
| | THE FLOOR. 36" REQUIRED. ALSO SECTION 11-4.1.3(10)(A) |
| | HAS NOT BEEN ADDRESSED. |
| | |
| | 6. SHT A1.0 INDICATES A WATERFALL CLOSET. PLEASE SUBMIT |
| | A DETAIL FOR THE CLOSET. INDICATE IF THERE WILL BE |
| | DRAINAGE AND/OR WATER SUPPLY. BACKFLOW PROTECTION IS |
| | REQUIRED IF CONNECTED TO A POTABLE WATER SOURCE PER |
| | SECTION 608. SECTION 106.1.1. SUBMIT A DETAIL FOR THE |
| | WATERFALL WALL. |
| | ******RESPONSE NOTED, BUT NO RESPONSE FROM THE |
| | ENGINEER. WATER SUPPLY NOTED, BUT DRAINAGE NOT |
| | INDICATED. |
| | |
| | 7. SHTS P1.0 & P1.1 PLUMBING SCHEDULES DO NOT REFLECT |
| | THE FLOOR PLANS. ITEMS P7 & P7A INDICATE A QUANTITY OF |
| | 2, BUT THE FLOOR PLAN ONLY SHOWS 1.--ITEM P9B |
| | INDICATES A QUANTITIY OF 3, BUT FLOOR PLAN ONLY SHOWS |
| | 2.--ITEM P11 INDICATED ON THE SCHEDULE WAS NOT |
| | FOUND ON THE FLOOR PLAN.--ITEM P13 DOES NOT |
| | INDICATE A FIXTURE TYPE. PLEASE INDICATED FIXTURE TYPE. |
| | --ITEM P14 INDICATED ON THE SCHEDULE WAS NOT FOUND ON |
| | THE FLOOR PLAN.--ITEM P15 INDICATES A QUANTITIY OF |
| | 4, BUT ONLY 2 WERE LOCATED ON THE FLOOR PLAN.--ITEM |
| | P17 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE |
| | FLOOR PLAN. PLEASE SUBMIT A DETAIL OR MANUF. |
| | SPECIFICATION SHEETS FOR THIS ITEM.--ITEM P19 |
| | INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE FLOOR |
| | PLAN.--ITEM P20 INDICATES A QUANTITIY OF 8, BUT |
| | ONLY 2 ARE FOUND ON THE FLOOR PLAN.--ITEM P21 |
| | INDICATES A QUANTITIY OF 4, BUT ONLY 1 WAS FOUND ON THE |
| | FLOOR PLAN. PLEASE CLARIFY AND CORRELATE THE SCHEDULE |
| | AND THE FLOOR PLANS. SECTION 106.1.1. ******RESPONSE |
| | NOTED, BUT ITEM P9B INDICATES 3 TRENCH DRAINS, BUT |
| | THESE ARE NOT SHOWN ON THE PLANS. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 8. OK |
| | 9. N/A |
| | 10. N/A - CENTRAL WATER HEATER IN BLDG. |
| | 11. N/A NO GAS WORK |
| | |
| | ****NEW COMMENTS SAME NUMBER SEQUENCE: |
| | |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | |
| | 15. SHT P-2 KEY NOTES 4, 7 & 14 NOT FOUND. SECTION |
| | 106.1.1. PLEASE CLARIFY. |
| | ******RESPONSE NOTED, BUT NOW KEY NOTE #3 IS OMITED, |
| | BUT IS INDICATED ON THE FLOOR PLAN & KEY NOTE #6 IS NOT |
| | FOUND. |
| | |
| | 16. OK |
| | |
| | 17. SHT P-2 KEY NOTE 3 BY RAIN SHOWER ROOM DOES NOT |
| | REFLECT THE KEY NOTE. SECTION 106.1.1. PLEASE |
| | CORRELATE. |
| | ******RESPONSE NOTED, BUT KEY NOTE #3 IS OMITED BUT |
| | SHOWN ON THE FLOOR PLAN. |
| | |
| | 18. SHT P-3 SANT. RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN OF THE VENTS. SEE SECTIONS TO THE LEFT OF |
| | WERE THE 3" VENT TO RISER S/17 CONNECTS TO THE 2' & 3" |
| | HORIZONTAL VENT LINE. |
| | ******RESPONSE NOTED, BUT THE VENT FROM SINK IN ROOM |
| | 107 IS SHOWN CONNECTING TO THE VENT ON THE 1ST FLOOR ON |
| | THE FLOOR PLAN, BUT IS SHOWN CONNECTING TO THE VENT ON |
| | THE SECOND FLOOR ON THE RISER DIAGRAM. PLEASE RECHECK |
| | RISER CORRELATE WITH FLOOR PLAN. |
| | |
| | 19. SHT P-4 WATER RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN, SHOWS TWO COLD LINES BY THE RAIN SHOWER, |
| | AND IN THE MEN'S LOCKER ROOM WHERE THE BRANCH FOR THE |
| | LAV FROM ROOM 105A CONNECTS TO THE MAIN.--ALSO |
| | RISER DOES NOT MEET CODE AS THERE ARE NO WATER HAMMER |
| | ARRESTORS AT THE WASH MACHINE AS REQUIRED PER SECTION |
| | 604.9. PLEASE MAKE SURE ALL QUICK CLOSING VALVES SHOW |
| | WATER HAMMER ARRESTORS. SECTION 106.1.1. ******RESPONSE |
| | NOTED, BUT THE CONNECTION TO THE LAV IN ROOM 105A HAS |
| | NOT BEEN CHANGED AND STILL DOES NOT REFLECT THE FLOOR |
| | PLAN. |
| | |
| | ******NEW COMMENTS****** |
| | |
| | 1C. SHT P-2 CORRECTIONS INDICATED FROM THE ENGINEER |
| | SHOW A FUNNEL FLOOR DRAIN FOR THE SPILLAGE FROM THE |
| | STEAM GENERATOR. AN EMERGENCY PAN SHALL BE INSTALLED |
| | AND THE INDIRECT WASTE SHALL DRAIN INTO A FLOOR SINK OR |
| | HUB DRAIN AS A FLOOR SINK IS NOT AN APPROVED INDIRECT |
| | WASTE RECEPTOR. SECTION 504.7, 802.3 & 802.3.2. |
| | |
| | 2C. SHT P-4 THE ENGINEERINDICATES WATER ISOMETRIC |
| | REVISED TO REFLECT THE FLOOR PLAN, BUT IT DOES NOT |
| | COMPLETLY REFLECT. PLEASE CORRELATE. |
| | |
| | 3C. THE ARCHITECTURAL DESIGN TEAM OF THE TENANT |
| | BUILDOUT IS NOT THE SAME AS THE ARCHITECTURAL DESIGN |
| | TEAM OF THE SHELL BUILDING AND WILL BE REQUIRED TO HAVE |
| | ALL ARCHITECTURAL & STRUCTURAL SHEETS REVIEWED BY THE |
| | DESIGN TEAM OF THE SHELL BUILDING AND STAMP APPROVAL |
| | WITH A SHOP APPROVAL STAMP SUCH AS THAT FOR SUBMITTALS |
| | PRIOR TO RESUBMITTING. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |