2008-01-23 17:36:59REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 NOT ADDRESSED:
 1. FIRE DAMPERS HAVE BEEN ADDED TO WALLS IN AREAS
 RELATED TO PREVIOUS REVIEW COMMENT. HOWEVER, PG A1.2
 NOW SHOWS THE WALLS AROUND STAFF ROOM 109 HAVE BEEN
 REVISED AND ARE NOW SHOWN AS TYPE 6A, WHICH HAS 1-1/2
 HR RATING. PG M-1 SHOWS SEVERAL DUCT PENETRATIONS
 THROUGH THESE WALLS WHICH ARE UNPROTECTED. SHOW HOW
 THESE DUCT PENETRATIONS ARE TO BE PROTECTED IN THE
 NEWLY DESIGNATED RATED WALLS IN ACCORDANCE WITH FBC, M
 607.5.
  
 2. OK
  
 3. OK
  
 4. OK
  
 NOT ADDRESSED:
 5. CEILING HAS BEEN REMOVED FROM ARCHITECTURAL PLANS.
 HOWEVER, PG M-2 SHOWS CEILING ACCESS DOORS FOR SERVICE
 OF EQUIPMENT ABOVE A CEILING. PLEASE CLARIFY.
  
 NOT ADDRESSED:
 6. LOUVER IS STILL WITHIN 10 FEET OF ALLEY, AT THE
 ENTRANCE TO THE ALLEY. PLEASE SHOW LOUVER LOCATED AS
 FAR TO THE NORTH AS POSSIBLE WITHIN THE MECHANICAL ROOM
 TO ACHIEVE MAXIMUM DISTANCE FROM THE ALLEY. FBC, M
 401.5.1.
  
 NOT ADDRESSED:
 7. OK EXCEPT, PG FA-1 RISER DIAGRAM SHOWS TWO DUCT
 SMOKE DETECTORS TYING INTO THE FACP. WHERE IS THE DUCT
 SMOKE DETECTOR LOCATED ON THE GROUND FLOOR AS INDICATED
 BY THIS RISER DIAGRAM? THERE IS NO EQUIPMENT SHOWN ON
 PLANS AT GROUND FLOOR LEVEL WHICH REQUIRES A DUCT SMOKE
 DETECTOR. PLEASE CLARIFY AND COORDINATE PLANS. FBC, M
 606.2 AND FBC 106.1.1.
  
 8. OK
  
 9. OK
  
 NOT ADDRESSED:
 10. PROVIDE DETAIL ON ARCHITECTURAL PLAN FOR EXTERIOR
 WALL FINISHES IN MECHANICAL ROOM 209 TO CORRESPOND WITH
 NEW NOTE #11 ON PG M-2. SHOW ALL REQUIRED COMPONENTS IN
 THE DETAIL. FBC 13-410.1.ABC.3.6.
  
 IT APPEARS THAT NONE OF THE OUTSTANDING COMMENTS FROM
 THE PREVIOUS REVIEW, DATED 12/5/07, HAVE BEEN ADDRESSED
 IN ANY WAY. PLEASE ADDRESS EACH OF THESE COMMENTS,
 SHOWING COMPLIANCE WITH THE CITED CODE SECTIONS AND
 RESUBMIT. AN ADDITIONAL FINE OF 4X THE PLAN REVIEW FEE
 WILL BE ASSESED IF REPEAT CODE DEFICIENCIES ARE CITED
 AGAIN IN ACCORDANCE WITH FS 533.80(2)(B).
  