Plan Review Notes
Plan Review Notes For Permit 07050880
Permit Number 07050880
Review Stop E
Sequence Number 3
Notes
Date Text
2008-01-18 11:39:55 
  
 ** DENIED 3RDREVIEW **
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL NEED TO BE ADDRESSED.
 PLEASE SEE NEW NOTES DUE TO CHANGES ONCE MORE ON PLANS
 WHICH WERE NOT ON PREVIOUS PLANS.
  
  
 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.3.
 THIS WAS REQUESTED ON THE TWO PREVIOUS REVIEWS HOWEVER
 THEY ARE STILL NOT SUBMITTED.
 PLEASE SEE THE ARCHITECTURAL PLANS DO NOT CONTAIN THE
 SAME LIGHTING AS SHOWN ON ELECTRICAL PLANS. PLEASE SEE
 IN FACT THE EXTERIOR LIGHTING ON L1.0 WHICH IS NOT ON
 ELECTRICAL.
 FOR ONE EXAMPLE: PLEASE SEE ELECTRICAL FIXTURE LEGEND
 IS MISSING FIXTURE H2. THERE ARE OTHERS ALSO.
 PLEASE BE SURE THE FIXTURE LEGEND ON ELECTRICAL PLANS
 COORDINATES WITH ELECTRICAL LIGHTING ON PLANS.
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
 FAC 61G15-33.004 FOR RESPONSIBILITY OF DESIGN.
  
 2) NOTE: PLEASE SEE BOTH PREVIOUS REVIEWS WHICH
 REQUESTED MORE INFORMATION FOR COMPLIANCE WITH FBC
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE NUMEROUS LOCATIONS WHICH STILL ONLY SHOW
 STANDARD SINGLE POLE SWITCHES AND NO AUTOMATED
 CONTROLS.
 PLEASE SEE NO LIGHTING CONTROL SYSTEM OR DETAILS ON
 ELECTRICAL WERE SUBMITTED.
 PLEASE SEE NO SCHEDULING.
 PLEASE SEE NO MAXIMUM TIMES.
 PLEASE SEE NO DETAIL FOR OCCUPANCIES AS ROOMS ARE
 SHOWING A *STANDARD* SINGLE POLE SWITCH AS PART OF THE
 OS DEVICES AND PREVIOUS REVIEW REQUESTED DETAIL ON
 THIS.
 PLEASE SEE SEPARATE SYSTEM/CONTROLS FOR MULTIPLE
 LEVELS/FLOORS.
  
 AS NO SYSTEM WAS SHOWN, A FULL REVIEW FOR MANY ITEMS
 CAN NOT BE DONE AT THIS TIME.
  
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
 FAC 61G15-33.004 FOR RESPONSIBILITY OF DESIGN.
  
 3) NOTE: PLEASE SEE NEC 517 AS THIS SECTION BASED ON
 WHAT IS KNOWN AS THE PROPOSED USE REQUIRES DESIGN TO
 COMPLY WITH NEC 517. THIS DOES NOT COMPLY WITH A
 MAKE-UP ONLY FACILITY.
 517.10, 517.13 ETC.
 (ONLY APPLIES TO TREATMENT ROOMS/EXAM ROOMS, NOT TO
 OFFICE, RECEPTION, HALL AREAS ETC.)
 NO CHANGES OR ADJUSTMENTS WERE MADE ON PLANS SINCE
 PREVIOUS REVIEW AND THIS ITEM WAS SPECIFICALLY GONE
 OVER IN THE MEETING PREVIOUSLY.
 PLEASE SEE THE FOLLOWING TEXT FROM THE NEC COMMENTARY.
 *THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY
 TO ALL TYPES OF HEALTH CARE FACILITIES. THE
 REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE
 NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC
 MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES
 WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE
 WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE
 REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER
 PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS
 ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE
 REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45
 IN ARTICLE 517.*
  
 4) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES WITH
 RESPECT TO FLOOR AND MEZZANINE DESIGNATIONS.
  
 5) NOTE: PLEASE SEE CHANGES IN EMERGENCY AND EXIT
 LIGHTING WHICH DOES NOT MEET THE CIRCUITING
 REQUIREMENTS OFNEC 700.12F. THESE EM AND EXT LIGHTING
 SHALL BE CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT
 IN ANY ONE AREA.
 PLEASE SEE THE PHOTO-METRIC PLANS STILL DO NOT SHOW THE
 FIXTURES AS EMERGENCY ON ELECTRICAL PLANS FIGURED INTO
 PHOTO-METRICS.
 PLEASE SEE FIXTURE LEGEND DESIGNATIONS FOR SOME
 FIXTURES WHICH ARE SHOWN AS EM DO NOT INCLUDE BATTERY
 BACK UP INFORMATION.
 PLEASE EXPLAIN HOW MANY THE TENANT WILL HAVE ACCESS TO
 ALL OVER CURRENT PROTECTION DEVICES FOR ELECTRICAL
 FIXTURES ETC FED INTO THEIR SPACE. PLANS SHOW THE EM
 LTS FED TO BASE BUILDING HOUSE EM PANEL.
 THIS IS MIXING SERVICES IN ONE SPACE FROM SEPARATE
 TRANSFORMERS VOLTAGES ETC WHICH IS NOT PERMITTED.
 AS STATED BEFORE THE CIRCUITING OF ANY OF THESE
 FIXTURES SHALL BE ON THE LOCAL LIGHTING.
 700.12F, 240.24 A AND B, ETC.
  
 6) NOTE: PLEASE SEE FIXTURES SHOWN IN CLOSETS WHICH ARE
 NOT PERMITTED NEAR SHELVING AREAS. PLEASE SEE 410.08
 THESE FIXTURES ARE SHOWN ON ARCHITECTS PLANS BUT NOT ON
 ELECTRICAL SHEETS.
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR MINIMUM CODE COMPLIANCE.
 PLEASE SEE THAT A FEE HAS NOW BEEN ASSESSED FOR THE
 AMOUNT OF $10, 200 WHICH IS DUE BEFORE PLANS MAY BE
 RESUBMITTED.
 PLEASE ALSO KNOW THAT ONE SET OF ELECTRICAL PLANS AND
 LIGHTING PLANS FROM ARCHITECTURAL ARE NOW BEING
 RETAINED BY THIS OFFICE.
  
 8) NOTE: PLEASE KNOW THE ORIGINAL PERMIT APPLICATION
 WAS NOT IN PACKAGE. CALLED AND SPOKE TO GARRY FROM GC
 AND HE WILL BRING IN PERMIT APPLICATION.
  
 ** PLEASE KNOW THERE WILL BE SEVERAL CHANGES WHICH ARE
 NEEDED ON PLANS AND NOT ALL POSSIBLE COMMENTS CAN BE
 MADE DUE TO LACK OF INFORMATION ON MANY ITEMS AS NOTED
 ABOVE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.