| 2008-01-18 11:39:55 | |
| | |
| | ** DENIED 3RDREVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW |
| | WHICH ARE STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE NEW NOTES DUE TO CHANGES ONCE MORE ON PLANS |
| | WHICH WERE NOT ON PREVIOUS PLANS. |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE |
| | CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.3. |
| | THIS WAS REQUESTED ON THE TWO PREVIOUS REVIEWS HOWEVER |
| | THEY ARE STILL NOT SUBMITTED. |
| | PLEASE SEE THE ARCHITECTURAL PLANS DO NOT CONTAIN THE |
| | SAME LIGHTING AS SHOWN ON ELECTRICAL PLANS. PLEASE SEE |
| | IN FACT THE EXTERIOR LIGHTING ON L1.0 WHICH IS NOT ON |
| | ELECTRICAL. |
| | FOR ONE EXAMPLE: PLEASE SEE ELECTRICAL FIXTURE LEGEND |
| | IS MISSING FIXTURE H2. THERE ARE OTHERS ALSO. |
| | PLEASE BE SURE THE FIXTURE LEGEND ON ELECTRICAL PLANS |
| | COORDINATES WITH ELECTRICAL LIGHTING ON PLANS. |
| | FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND |
| | ADDITIONAL INFORMATION. |
| | FAC 61G15-33.004 FOR RESPONSIBILITY OF DESIGN. |
| | |
| | 2) NOTE: PLEASE SEE BOTH PREVIOUS REVIEWS WHICH |
| | REQUESTED MORE INFORMATION FOR COMPLIANCE WITH FBC |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE NUMEROUS LOCATIONS WHICH STILL ONLY SHOW |
| | STANDARD SINGLE POLE SWITCHES AND NO AUTOMATED |
| | CONTROLS. |
| | PLEASE SEE NO LIGHTING CONTROL SYSTEM OR DETAILS ON |
| | ELECTRICAL WERE SUBMITTED. |
| | PLEASE SEE NO SCHEDULING. |
| | PLEASE SEE NO MAXIMUM TIMES. |
| | PLEASE SEE NO DETAIL FOR OCCUPANCIES AS ROOMS ARE |
| | SHOWING A *STANDARD* SINGLE POLE SWITCH AS PART OF THE |
| | OS DEVICES AND PREVIOUS REVIEW REQUESTED DETAIL ON |
| | THIS. |
| | PLEASE SEE SEPARATE SYSTEM/CONTROLS FOR MULTIPLE |
| | LEVELS/FLOORS. |
| | |
| | AS NO SYSTEM WAS SHOWN, A FULL REVIEW FOR MANY ITEMS |
| | CAN NOT BE DONE AT THIS TIME. |
| | |
| | FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND |
| | ADDITIONAL INFORMATION. |
| | FAC 61G15-33.004 FOR RESPONSIBILITY OF DESIGN. |
| | |
| | 3) NOTE: PLEASE SEE NEC 517 AS THIS SECTION BASED ON |
| | WHAT IS KNOWN AS THE PROPOSED USE REQUIRES DESIGN TO |
| | COMPLY WITH NEC 517. THIS DOES NOT COMPLY WITH A |
| | MAKE-UP ONLY FACILITY. |
| | 517.10, 517.13 ETC. |
| | (ONLY APPLIES TO TREATMENT ROOMS/EXAM ROOMS, NOT TO |
| | OFFICE, RECEPTION, HALL AREAS ETC.) |
| | NO CHANGES OR ADJUSTMENTS WERE MADE ON PLANS SINCE |
| | PREVIOUS REVIEW AND THIS ITEM WAS SPECIFICALLY GONE |
| | OVER IN THE MEETING PREVIOUSLY. |
| | PLEASE SEE THE FOLLOWING TEXT FROM THE NEC COMMENTARY. |
| | *THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY |
| | TO ALL TYPES OF HEALTH CARE FACILITIES. THE |
| | REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE |
| | NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC |
| | MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES |
| | WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE |
| | WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE |
| | REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER |
| | PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS |
| | ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE |
| | REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45 |
| | IN ARTICLE 517.* |
| | |
| | 4) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES WITH |
| | RESPECT TO FLOOR AND MEZZANINE DESIGNATIONS. |
| | |
| | 5) NOTE: PLEASE SEE CHANGES IN EMERGENCY AND EXIT |
| | LIGHTING WHICH DOES NOT MEET THE CIRCUITING |
| | REQUIREMENTS OFNEC 700.12F. THESE EM AND EXT LIGHTING |
| | SHALL BE CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT |
| | IN ANY ONE AREA. |
| | PLEASE SEE THE PHOTO-METRIC PLANS STILL DO NOT SHOW THE |
| | FIXTURES AS EMERGENCY ON ELECTRICAL PLANS FIGURED INTO |
| | PHOTO-METRICS. |
| | PLEASE SEE FIXTURE LEGEND DESIGNATIONS FOR SOME |
| | FIXTURES WHICH ARE SHOWN AS EM DO NOT INCLUDE BATTERY |
| | BACK UP INFORMATION. |
| | PLEASE EXPLAIN HOW MANY THE TENANT WILL HAVE ACCESS TO |
| | ALL OVER CURRENT PROTECTION DEVICES FOR ELECTRICAL |
| | FIXTURES ETC FED INTO THEIR SPACE. PLANS SHOW THE EM |
| | LTS FED TO BASE BUILDING HOUSE EM PANEL. |
| | THIS IS MIXING SERVICES IN ONE SPACE FROM SEPARATE |
| | TRANSFORMERS VOLTAGES ETC WHICH IS NOT PERMITTED. |
| | AS STATED BEFORE THE CIRCUITING OF ANY OF THESE |
| | FIXTURES SHALL BE ON THE LOCAL LIGHTING. |
| | 700.12F, 240.24 A AND B, ETC. |
| | |
| | 6) NOTE: PLEASE SEE FIXTURES SHOWN IN CLOSETS WHICH ARE |
| | NOT PERMITTED NEAR SHELVING AREAS. PLEASE SEE 410.08 |
| | THESE FIXTURES ARE SHOWN ON ARCHITECTS PLANS BUT NOT ON |
| | ELECTRICAL SHEETS. |
| | |
| | 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR MINIMUM CODE COMPLIANCE. |
| | PLEASE SEE THAT A FEE HAS NOW BEEN ASSESSED FOR THE |
| | AMOUNT OF $10, 200 WHICH IS DUE BEFORE PLANS MAY BE |
| | RESUBMITTED. |
| | PLEASE ALSO KNOW THAT ONE SET OF ELECTRICAL PLANS AND |
| | LIGHTING PLANS FROM ARCHITECTURAL ARE NOW BEING |
| | RETAINED BY THIS OFFICE. |
| | |
| | 8) NOTE: PLEASE KNOW THE ORIGINAL PERMIT APPLICATION |
| | WAS NOT IN PACKAGE. CALLED AND SPOKE TO GARRY FROM GC |
| | AND HE WILL BRING IN PERMIT APPLICATION. |
| | |
| | ** PLEASE KNOW THERE WILL BE SEVERAL CHANGES WHICH ARE |
| | NEEDED ON PLANS AND NOT ALL POSSIBLE COMMENTS CAN BE |
| | MADE DUE TO LACK OF INFORMATION ON MANY ITEMS AS NOTED |
| | ABOVE. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |