Plan Review Notes
Plan Review Notes For Permit 07050880
Permit Number 07050880
Review Stop P
Sequence Number 2
Notes
Date Text
2007-09-24 18:27:14DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****REREVIEW OF PLANS. THERE WAS CONFUSION BECAUSE OF
 MULTIPLE "P" SHEETS AND THE ENGINEERS "P" SHEETS WERE
 NOT REVIEWED. SOME COMMENTS WILL BE DELETED BECAUSE OF
 THE MEETING HELD ON 9-13-7. THERE WILL BE SOME NEW
 COMMENTS BECAUSE OF THE REVIEW OF THE ENGINEERS
 SHEETS.
  
  
 1. ALL SHEETS WITH NEW WORLD DESIGN STUDIO LLC TITLE
 BLOCK. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET PER FAC 61G1-16.004(2) & FS 481.219, 481.2055.
  
 2. ALL "T", ARCHITECTURAL & PLUMBING SHEETS. THE
 ADDRESS OF THE ARCHITECT OF RECORD DOES NOT REFLECT THE
 ADDRESS RECORDED ON THE FLORIDA STATE DBPR WEBSITE.
 PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR WEBSITE.
 (SEE ATTACHED SHEET). FAC 61G1-16.004(1) & FS
 481.2055.
  
 3. SHT T1.1 DETAILS 6 & 11 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C:
 A. 11-4.16.5 FLUSH CONTROLS.
 DETAILS 5, 8A & 9:
 ___FOR LAVS:
 A. 11-4.19.2 CLEARANCE (FIG 31)
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 4. SHT T1.1 DETAILS 1 & 2 THE 5' TURNING AREA SHALL BE
 UNOBSTRUCTED AS REQUIRED IN SECTION 11-4.22.3. AS SHOWN
 THE W/C'S ARE SHOWN IN THE TURNING AREA. PLEASE SHOW
 THE TURNING AREA AS UNOBSTRUCTED.
  
 5. SHT A1.0 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. INDICATE THE LOCATION AND SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 6. SHT A1.0 INDICATES A WATERFALL CLOSET. PLEASE SUBMIT
 A DETAIL FOR THE CLOSET. INDICATE IF THERE WILL BE
 DRAINAGE AND/OR WATER SUPPLY. BACKFLOW PROTECTION IS
 REQUIRED IF CONNECTED TO A POTABLE WATER SOURCE PER
 SECTION 608. SECTION 106.1.1. SUBMIT A DETAIL FOR THE
 WATERFALL WALL.
  
 7. SHTS P1.0 & P1.1 PLUMBING SCHEDULES DO NOT REFLECT
 THE FLOOR PLANS. ITEMS P7 & P7A INDICATE A QUANTITY OF
 2, BUT THE FLOOR PLAN ONLY SHOWS 1.--ITEM P9B
 INDICATES A QUANTITIY OF 3, BUT FLOOR PLAN ONLY SHOWS
 2.--ITEM P11 INDICATED ON THE SCHEDULE WAS NOT
 FOUND ON THE FLOOR PLAN.--ITEM P13 DOES NOT
 INDICATE A FIXTURE TYPE. PLEASE INDICATED FIXTURE TYPE.
 --ITEM P14 INDICATED ON THE SCHEDULE WAS NOT FOUND ON
 THE FLOOR PLAN.--ITEM P15 INDICATES A QUANTITIY OF
 4, BUT ONLY 2 WERE LOCATED ON THE FLOOR PLAN.--ITEM
 P17 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE
 FLOOR PLAN. PLEASE SUBMIT A DETAIL OR MANUF.
 SPECIFICATION SHEETS FOR THIS ITEM.--ITEM P19
 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE FLOOR
 PLAN.--ITEM P20 INDICATES A QUANTITIY OF 8, BUT
 ONLY 2 ARE FOUND ON THE FLOOR PLAN.--ITEM P21
 INDICATES A QUANTITIY OF 4, BUT ONLY 1 WAS FOUND ON THE
 FLOOR PLAN. PLEASE CLARIFY AND CORRELATE THE SCHEDULE
 AND THE FLOOR PLANS. SECTION 106.1.1.
  
 8. SUBMIT A PLAN VIEW LAYOUT FOR ALL SANITARY DRAINAGE
 PIPING AND ALL WATER PIPING. INDICATE WHERE THE PIPING
 ENTERS THE SUITE AND SHOW THE LOCATION OF ALL VENTS ON
 THE SANT. AND SHOW THE MAIN WATER SHUTOFF VALVE AND
 BACKFLOWS ON THE WATER PIPING. SECTIONS 106.1.2.
  
 9. N/A
 10. N/A - CENTRAL WATER HEATER IN BLDG.
 11. N/A NO GAS WORK
  
 ****NEW COMMENTS SAME NUMBER SEQUENCE:
  
 12. SHT P-1 KEY NOTES 9 & 13 NOT FOUND. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 13. SHT P-1 KEY NOTE 12 INDICATES HOT & COLD WATER UP,
 BUT ONLY HOT IS SHOWN ON ONE RISER. SECTION 106.1.1.
 PLEASE CLARIFY.
  
 14. SHT P-1 SHOWS 2 HOT LINES UP BY THE ELEVATORS, BUT
 ONLY ONE LINE SHOWN ON MEZZANINE LEVEL. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 15. SHT P-2 KEY NOTES 4, 7 & 14 NOT FOUND. SECTION
 106.1.1. PLEASE CLARIFY.
  
 16. SHT P-2 KEY NOTE 2 INDICATES HOT & COLD WATER FROM
 BELOW, BUT ONLY HOT IS SHOWN ON TWO RISERS. SECTION
 106.1.1. PLEASE CLARIFY.
  
 17. SHT P-2 KEY NOTE 3 BY RAIN SHOWER ROOM DOES NOT
 REFLECT THE KEY NOTE. SECTION 106.1.1. PLEASE
 CORRELATE.
  
 18. SHT P-3 SANT. RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN OF THE VENTS. SEE SECTIONS TO THE LEFT OF
 WERE THE 3" VENT TO RISER S/17 CONNECTS TO THE 2' & 3"
 HORIZONTAL VENT LINE.
  
 19. SHT P-4 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN, SHOWS TWO COLD LINE BY THE RAIN SHOWER, AND
 IN THE MEN'S LOCKER ROOM WHERE THE BRANCH FOR THE LAV
 FROM ROOM 105A CONNECTS TO THE MAIN.--ALSO RISER
 DOES NOT MEET CODE AS THERE ARE NO WATER HAMMER
 ARRESTORS AT THE WASH MACHINE AS REQUIRED PER SECTION
 604.9. PLEASE MAKE SURE ALL QUICK CLOSING VALVES SHOW
 WATER HAMMER ARRESTORS. SECTION 106.1.1.
  
 ****END OF NEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS