| 2007-09-24 18:27:14 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****REREVIEW OF PLANS. THERE WAS CONFUSION BECAUSE OF |
| | MULTIPLE "P" SHEETS AND THE ENGINEERS "P" SHEETS WERE |
| | NOT REVIEWED. SOME COMMENTS WILL BE DELETED BECAUSE OF |
| | THE MEETING HELD ON 9-13-7. THERE WILL BE SOME NEW |
| | COMMENTS BECAUSE OF THE REVIEW OF THE ENGINEERS |
| | SHEETS. |
| | |
| | |
| | 1. ALL SHEETS WITH NEW WORLD DESIGN STUDIO LLC TITLE |
| | BLOCK. THE FIRM LICENSE NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH |
| | SHEET PER FAC 61G1-16.004(2) & FS 481.219, 481.2055. |
| | |
| | 2. ALL "T", ARCHITECTURAL & PLUMBING SHEETS. THE |
| | ADDRESS OF THE ARCHITECT OF RECORD DOES NOT REFLECT THE |
| | ADDRESS RECORDED ON THE FLORIDA STATE DBPR WEBSITE. |
| | PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR WEBSITE. |
| | (SEE ATTACHED SHEET). FAC 61G1-16.004(1) & FS |
| | 481.2055. |
| | |
| | 3. SHT T1.1 DETAILS 6 & 11 SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | ___FOR W/C: |
| | A. 11-4.16.5 FLUSH CONTROLS. |
| | DETAILS 5, 8A & 9: |
| | ___FOR LAVS: |
| | A. 11-4.19.2 CLEARANCE (FIG 31) |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | |
| | 4. SHT T1.1 DETAILS 1 & 2 THE 5' TURNING AREA SHALL BE |
| | UNOBSTRUCTED AS REQUIRED IN SECTION 11-4.22.3. AS SHOWN |
| | THE W/C'S ARE SHOWN IN THE TURNING AREA. PLEASE SHOW |
| | THE TURNING AREA AS UNOBSTRUCTED. |
| | |
| | 5. SHT A1.0 A DRINKING FOUNTAIN IS REQUIRED PER TABLE |
| | 403.1. INDICATE THE LOCATION AND SUBMIT A DETAIL |
| | SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL |
| | SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | |
| | 6. SHT A1.0 INDICATES A WATERFALL CLOSET. PLEASE SUBMIT |
| | A DETAIL FOR THE CLOSET. INDICATE IF THERE WILL BE |
| | DRAINAGE AND/OR WATER SUPPLY. BACKFLOW PROTECTION IS |
| | REQUIRED IF CONNECTED TO A POTABLE WATER SOURCE PER |
| | SECTION 608. SECTION 106.1.1. SUBMIT A DETAIL FOR THE |
| | WATERFALL WALL. |
| | |
| | 7. SHTS P1.0 & P1.1 PLUMBING SCHEDULES DO NOT REFLECT |
| | THE FLOOR PLANS. ITEMS P7 & P7A INDICATE A QUANTITY OF |
| | 2, BUT THE FLOOR PLAN ONLY SHOWS 1.--ITEM P9B |
| | INDICATES A QUANTITIY OF 3, BUT FLOOR PLAN ONLY SHOWS |
| | 2.--ITEM P11 INDICATED ON THE SCHEDULE WAS NOT |
| | FOUND ON THE FLOOR PLAN.--ITEM P13 DOES NOT |
| | INDICATE A FIXTURE TYPE. PLEASE INDICATED FIXTURE TYPE. |
| | --ITEM P14 INDICATED ON THE SCHEDULE WAS NOT FOUND ON |
| | THE FLOOR PLAN.--ITEM P15 INDICATES A QUANTITIY OF |
| | 4, BUT ONLY 2 WERE LOCATED ON THE FLOOR PLAN.--ITEM |
| | P17 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE |
| | FLOOR PLAN. PLEASE SUBMIT A DETAIL OR MANUF. |
| | SPECIFICATION SHEETS FOR THIS ITEM.--ITEM P19 |
| | INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE FLOOR |
| | PLAN.--ITEM P20 INDICATES A QUANTITIY OF 8, BUT |
| | ONLY 2 ARE FOUND ON THE FLOOR PLAN.--ITEM P21 |
| | INDICATES A QUANTITIY OF 4, BUT ONLY 1 WAS FOUND ON THE |
| | FLOOR PLAN. PLEASE CLARIFY AND CORRELATE THE SCHEDULE |
| | AND THE FLOOR PLANS. SECTION 106.1.1. |
| | |
| | 8. SUBMIT A PLAN VIEW LAYOUT FOR ALL SANITARY DRAINAGE |
| | PIPING AND ALL WATER PIPING. INDICATE WHERE THE PIPING |
| | ENTERS THE SUITE AND SHOW THE LOCATION OF ALL VENTS ON |
| | THE SANT. AND SHOW THE MAIN WATER SHUTOFF VALVE AND |
| | BACKFLOWS ON THE WATER PIPING. SECTIONS 106.1.2. |
| | |
| | 9. N/A |
| | 10. N/A - CENTRAL WATER HEATER IN BLDG. |
| | 11. N/A NO GAS WORK |
| | |
| | ****NEW COMMENTS SAME NUMBER SEQUENCE: |
| | |
| | 12. SHT P-1 KEY NOTES 9 & 13 NOT FOUND. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 13. SHT P-1 KEY NOTE 12 INDICATES HOT & COLD WATER UP, |
| | BUT ONLY HOT IS SHOWN ON ONE RISER. SECTION 106.1.1. |
| | PLEASE CLARIFY. |
| | |
| | 14. SHT P-1 SHOWS 2 HOT LINES UP BY THE ELEVATORS, BUT |
| | ONLY ONE LINE SHOWN ON MEZZANINE LEVEL. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | 15. SHT P-2 KEY NOTES 4, 7 & 14 NOT FOUND. SECTION |
| | 106.1.1. PLEASE CLARIFY. |
| | |
| | 16. SHT P-2 KEY NOTE 2 INDICATES HOT & COLD WATER FROM |
| | BELOW, BUT ONLY HOT IS SHOWN ON TWO RISERS. SECTION |
| | 106.1.1. PLEASE CLARIFY. |
| | |
| | 17. SHT P-2 KEY NOTE 3 BY RAIN SHOWER ROOM DOES NOT |
| | REFLECT THE KEY NOTE. SECTION 106.1.1. PLEASE |
| | CORRELATE. |
| | |
| | 18. SHT P-3 SANT. RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN OF THE VENTS. SEE SECTIONS TO THE LEFT OF |
| | WERE THE 3" VENT TO RISER S/17 CONNECTS TO THE 2' & 3" |
| | HORIZONTAL VENT LINE. |
| | |
| | 19. SHT P-4 WATER RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN, SHOWS TWO COLD LINE BY THE RAIN SHOWER, AND |
| | IN THE MEN'S LOCKER ROOM WHERE THE BRANCH FOR THE LAV |
| | FROM ROOM 105A CONNECTS TO THE MAIN.--ALSO RISER |
| | DOES NOT MEET CODE AS THERE ARE NO WATER HAMMER |
| | ARRESTORS AT THE WASH MACHINE AS REQUIRED PER SECTION |
| | 604.9. PLEASE MAKE SURE ALL QUICK CLOSING VALVES SHOW |
| | WATER HAMMER ARRESTORS. SECTION 106.1.1. |
| | |
| | ****END OF NEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |