| Date |
Text |
| 2007-12-05 13:26:39 | REVIEW #: |
| | ACTION: |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. FIRE DAMPERS HAVE BEEN ADDED TO WALLS IN AREAS |
| | RELATED TO PREVIOUS REVIEW COMMENT. HOWEVER, PG A1.2 |
| | NOW SHOWS THE WALLS AROUND STAFF ROOM 109 HAVE BEEN |
| | REVISED AND ARE NOW SHOWN AS TYPE 6A, WHICH HAS 1 ? HR |
| | RATING. PG M-1 SHOWS SEVERAL DUCT PENETRATIONS THROUGH |
| | THESE WALLS WHICH ARE UNPROTECTED. SHOW HOW THESE DUCT |
| | PENETRATIONS ARE TO BE PROTECTED IN THE NEWLY |
| | DESIGNATED RATED WALLS IN ACCORDANCE WITH FBC, M |
| | 607.5. |
| | |
| | 2. OK |
| | |
| | 3. OK |
| | |
| | 4. OK |
| | |
| | 5. CEILING HAS BEEN REMOVED FROM ARCHITECTURAL PLANS. |
| | HOWEVER, PG M-2 SHOWS CEILING ACCESS DOORS FOR SERVICE |
| | OF EQUIPMENT ABOVE A CEILING. PLEASE CLARIFY. |
| | |
| | 6. LOUVER IS STILL WITHIN 10? OF ALLEY, AT THE ENTRANCE |
| | TO THE ALLEY. PLEASE SHOW LOUVER LOCATED AS FAR TO THE |
| | NORTH AS POSSIBLE WITHIN THE MECHANICAL ROOM TO ACHIEVE |
| | MAXIMUM DISTANCE FROM THE ALLEY. FBC, M 401.5.1. |
| | |
| | 7. OK EXCEPT, PG FA-1 RISER DIAGRAM SHOWS TWO DUCT |
| | SMOKE DETECTORS TYING INTO THE FACP. WHERE IS THE DUCT |
| | SMOKE DETECTOR LOCATED ON THE GROUND FLOOR AS INDICATED |
| | BY THIS RISER DIAGRAM? THERE IS NO EQUIPMENT SHOWN ON |
| | PLANS AT GROUND FLOOR LEVEL WHICH REQUIRES A DUCT SMOKE |
| | DETECTOR. PLEASE CLARIFY AND COORDINATE PLANS. FBC, M |
| | 606.2 AND FBC 106.1.1. |
| | |
| | 8. OK |
| | |
| | 9. OK |
| | |
| | 10. PROVIDE DETAIL ON ARCHITECTURAL PLAN FOR EXTERIOR |
| | WALL FINISHES IN MECHANICAL ROOM 209 TO CORRESPOND WITH |
| | NEW NOTE #11 ON PG M-2. SHOW ALL REQUIRED COMPONENTS IN |
| | THE DETAIL. FBC 13-410.1.ABC.3.6. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |
| | RONALD J. REGUEIRO |
| | 561.805.6719 |
| | [email protected] |