Plan Review Notes
Plan Review Notes For Permit 07050880
Permit Number 07050880
Review Stop E
Sequence Number 2
Notes
Date Text
2007-12-03 17:45:28NOTE ADDED,
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW, IF THIS SCOPE OF
 WORK IS PERMITTED AND COMMENCED BEFORE BASE BUILDING
 OBTAINS AND CERTIFICATE OF OCCUPANCY, ANY ELECTRICAL
 AND OTHER TRADE SCOPE WILL NEED TO BE REVISED ON BASE
 PLANS ALONG WITH REVISED ELECTRICAL CALCULATIONS,
 ENERGY CALCULATIONS ETC.
 PLEASE ALSO KNOW THESE PLANS ARE REQUIRED TO BE STAMPED
 *REVIEWED* BY THE BASE BUILDING DESIGN TEAM INCLUDING
 ARCHITECTURAL PLANS.
  
 ** THIS BUILDING IS STILL UNDER THE RESPONSIBILITY OF
 THE BASE BUILDING DESIGN TEAM AND BASE BUILDIGN
 CONTRACTOR.
 ALSO NEED TO OBTAIN LETTER FROM CONTRACTOR FOR BASE
 BUILDING IN ACKNOWLEDGMENT OF SCOPE OF WORK AS APPLIED.
2007-12-03 17:36:19** DENIED 2NDREVIEW **
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW
 NOTES DUE TO NEW INFORMATION.
  
  
 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2.
 PLEASE KNOW IT WAS CONFIRMED ON 9/26/07 WITH THE
 FLORIDA BUILDING COMMISSION THAT METHOD *A* AS
 SUBMITTED MAY NOT BE USED AS THIS APPLIES TO *WHOLE
 BUILDING*.
 PLEASE COMPLETE THE FIXTURE LEGEND WITH THE INFORMATION
 ON FIXTURES FOR TYPES, WATTAGE ETC. THESE WILL NEED TO
 CORRELATE WITH THE LIGHTING PERFORMANCE CALCULATIONS TO
 BE SUBMITTED.
 13-415.2
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE #3 WITH RESPECT TO
 LIGHTING CONTROLS AND AUTOMATED SHUT OFF OF LIGHTING.
 NOT ENOUGH INFORMATION FOR SYSTEM OR DEVICES AS SHOWN
 FOR MAIN AREAS IS SHOWN AT THIS TIME.
 PLEASE PROVIDE OVER RIDES, TIMES ETC. THE INDIVIDUAL
 ROOMS WHICH ARE CONTROLLED BY OCCUPANCY DEVICES NEED TO
 PROVIDE DETAIL FOR TYPE AND CONNECTIONS.(MAX TIMES)
 SWITCHES AS SHOWN ON PLANS ARE BEING SHOWN AS STANDARD
 DEVICES.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3
  
 3) NOTE: PLEASE SEE NEC 517 AS THIS SECTION BASED ON
 WHAT IS KNOWN AS THE PROPOSED USE REQUIRES DESIGN TO
 COMPLY WITH NEC 517. THIS DOES NOT COMPLY WITH A
 MAKE-UP ONLY FACILITY.
 517.10, 517.13 ETC.
 (ONLY APPLIES TO TREATMENT ROOMS/EXAM ROOMS, NOT TO
 OFFICE, RECEPTION, HALL AREAS ETC.)
 PLEASE CALL TO GO OVER THIS.
  
 4) NOTE: PLEASE BE SURE THE LIGHTING FIXTURE LOCATIONS
 ON ELECTRICAL PLANS COORDINATE WITH THE LIGHTING
 FIXTURES PLACED ON PHOTO-METRIC SHEETS.
  
 5) NOTE: PLEASE KNOW THE SUITE/UNIT # HAS NOT YET BEEN
 ASSIGNED. PLEASE BE SURE TO INCLUDE ONCE DETERMINED.
 FBC 106.1.2, 106.3.5 ETC
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]