| Date |
Text |
| 2007-12-03 17:45:28 | NOTE ADDED, |
| | |
| | 1) NOTE: AS NOTED ON PREVIOUS REVIEW, IF THIS SCOPE OF |
| | WORK IS PERMITTED AND COMMENCED BEFORE BASE BUILDING |
| | OBTAINS AND CERTIFICATE OF OCCUPANCY, ANY ELECTRICAL |
| | AND OTHER TRADE SCOPE WILL NEED TO BE REVISED ON BASE |
| | PLANS ALONG WITH REVISED ELECTRICAL CALCULATIONS, |
| | ENERGY CALCULATIONS ETC. |
| | PLEASE ALSO KNOW THESE PLANS ARE REQUIRED TO BE STAMPED |
| | *REVIEWED* BY THE BASE BUILDING DESIGN TEAM INCLUDING |
| | ARCHITECTURAL PLANS. |
| | |
| | ** THIS BUILDING IS STILL UNDER THE RESPONSIBILITY OF |
| | THE BASE BUILDING DESIGN TEAM AND BASE BUILDIGN |
| | CONTRACTOR. |
| | ALSO NEED TO OBTAIN LETTER FROM CONTRACTOR FOR BASE |
| | BUILDING IN ACKNOWLEDGMENT OF SCOPE OF WORK AS APPLIED. |
| 2007-12-03 17:36:19 | ** DENIED 2NDREVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW |
| | NOTES DUE TO NEW INFORMATION. |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE |
| | CALCULATIONS PER FBC 13-415.2. |
| | PLEASE KNOW IT WAS CONFIRMED ON 9/26/07 WITH THE |
| | FLORIDA BUILDING COMMISSION THAT METHOD *A* AS |
| | SUBMITTED MAY NOT BE USED AS THIS APPLIES TO *WHOLE |
| | BUILDING*. |
| | PLEASE COMPLETE THE FIXTURE LEGEND WITH THE INFORMATION |
| | ON FIXTURES FOR TYPES, WATTAGE ETC. THESE WILL NEED TO |
| | CORRELATE WITH THE LIGHTING PERFORMANCE CALCULATIONS TO |
| | BE SUBMITTED. |
| | 13-415.2 |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS NOTE #3 WITH RESPECT TO |
| | LIGHTING CONTROLS AND AUTOMATED SHUT OFF OF LIGHTING. |
| | NOT ENOUGH INFORMATION FOR SYSTEM OR DEVICES AS SHOWN |
| | FOR MAIN AREAS IS SHOWN AT THIS TIME. |
| | PLEASE PROVIDE OVER RIDES, TIMES ETC. THE INDIVIDUAL |
| | ROOMS WHICH ARE CONTROLLED BY OCCUPANCY DEVICES NEED TO |
| | PROVIDE DETAIL FOR TYPE AND CONNECTIONS.(MAX TIMES) |
| | SWITCHES AS SHOWN ON PLANS ARE BEING SHOWN AS STANDARD |
| | DEVICES. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | |
| | 3) NOTE: PLEASE SEE NEC 517 AS THIS SECTION BASED ON |
| | WHAT IS KNOWN AS THE PROPOSED USE REQUIRES DESIGN TO |
| | COMPLY WITH NEC 517. THIS DOES NOT COMPLY WITH A |
| | MAKE-UP ONLY FACILITY. |
| | 517.10, 517.13 ETC. |
| | (ONLY APPLIES TO TREATMENT ROOMS/EXAM ROOMS, NOT TO |
| | OFFICE, RECEPTION, HALL AREAS ETC.) |
| | PLEASE CALL TO GO OVER THIS. |
| | |
| | 4) NOTE: PLEASE BE SURE THE LIGHTING FIXTURE LOCATIONS |
| | ON ELECTRICAL PLANS COORDINATE WITH THE LIGHTING |
| | FIXTURES PLACED ON PHOTO-METRIC SHEETS. |
| | |
| | 5) NOTE: PLEASE KNOW THE SUITE/UNIT # HAS NOT YET BEEN |
| | ASSIGNED. PLEASE BE SURE TO INCLUDE ONCE DETERMINED. |
| | FBC 106.1.2, 106.3.5 ETC |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |