Plan Review Notes
Plan Review Notes For Permit 07050880
Permit Number 07050880
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-25 14:53:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH NEW WORLD DESIGN STUDIO LLC TITLE
 BLOCK. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET PER FAC 61G1-16.004(2) & FS 481.219, 481.2055.
  
 2. ALL "T", ARCHITECTURAL & PLUMBING SHEETS. THE
 ADDRESS OF THE ARCHITECT OF RECORD DOES NOT REFLECT THE
 ADDRESS RECORDED ON THE FLORIDA STATE DBPR WEBSITE.
 PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR WEBSITE.
 (SEE ATTACHED SHEET). FAC 61G1-16.004(1) & FS
 481.2055.
  
 3. SHT T1.1 DETAILS 6 & 11 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C:
 A. 11-4.16.5 FLUSH CONTROLS.
 DETAILS 5, 8A & 9:
 ___FOR LAVS:
 A. 11-4.19.2 CLEARANCE (FIG 31)
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 4. SHT T1.1 DETAILS 1 & 2 THE 5' TURNING AREA SHALL BE
 UNOBSTRUCTED AS REQUIRED IN SECTION 11-4.22.3. AS SHOWN
 THE W/C'S ARE SHOWN IN THE TURNING AREA. PLEASE SHOW
 THE TURNING AREA AS UNOBSTRUCTED.
  
 5. SHT A1.0 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. INDICATE THE LOCATION AND SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 6. SHT A1.0 INDICATES A WATERFALL CLOSET. PLEASE SUBMIT
 A DETAIL FOR THE CLOSET. INDICATE IF THERE WILL BE
 DRAINAGE AND/OR WATER SUPPLY. BACKFLOW PROTECTION IS
 REQUIRED IF CONNECTED TO A POTABLE WATER SOURCE PER
 SECTION 608. SECTION 106.1.1. SUBMIT A DETAIL FOR THE
 WATERFALL WALL.
  
 7. SHTS P1.0 & P1.1 PLUMBING SCHEDULES DO NOT REFLECT
 THE FLOOR PLANS. ITEMS P7 & P7A INDICATE A QUANTITY OF
 2, BUT THE FLOOR PLAN ONLY SHOWS 1.--ITEM P9B
 INDICATES A QUANTITIY OF 3, BUT FLOOR PLAN ONLY SHOWS
 2.--ITEM P11 INDICATED ON THE SCHEDULE WAS NOT
 FOUND ON THE FLOOR PLAN.--ITEM P13 DOES NOT
 INDICATE A FIXTURE TYPE. PLEASE INDICATED FIXTURE TYPE.
 --ITEM P14 INDICATED ON THE SCHEDULE WAS NOT FOUND ON
 THE FLOOR PLAN.--ITEM P15 INDICATES A QUANTITIY OF
 4, BUT ONLY 2 WERE LOCATED ON THE FLOOR PLAN.--ITEM
 P17 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE
 FLOOR PLAN. PLEASE SUBMIT A DETAIL OR MANUF.
 SPECIFICATION SHEETS FOR THIS ITEM.--ITEM P19
 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE FLOOR
 PLAN.--ITEM P20 INDICATES A QUANTITIY OF 8, BUT
 ONLY 2 ARE FOUND ON THE FLOOR PLAN.--ITEM P21
 INDICATES A QUANTITIY OF 4, BUT ONLY 1 WAS FOUND ON THE
 FLOOR PLAN. PLEASE CLARIFY AND CORRELATE THE SCHEDULE
 AND THE FLOOR PLANS. SECTION 106.1.1.
  
 8. SUBMIT A PLAN VIEW LAYOUT FOR ALL SANITARY DRAINAGE
 PIPING AND ALL WATER PIPING. INDICATE WHERE THE PIPING
 ENTERS THE SUITE AND SHOW THE LOCATION OF ALL VENTS ON
 THE SANT. AND SHOW THE MAIN WATER SHUTOFF VALVE AND
 BACKFLOWS ON THE WATER PIPING. SECTIONS 106.1.2.
  
 9. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM SHOWING
 ALL PIPE SIZES, TRAPS, VENTS ETC. AND SUBMIT A WATER
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE SIZES, VALVES
 AND WATER HAMMER ARRESTORS (REQUIRED BY SECTION 604.9).
 SECTIONS 106.3.5.1.3(3)(4)(5)(6)(8)(10)(13).
  
 10. SUBMIT A DETAIL FOR THE REQUIRED WATER HEATER. SHOW
 COMPLIANCE WITH SECTIONS 503.1, 504.4, 504.6 & 504.7
 WITH ALL SUBSECTIONS. SHOWTHE LOCATION OF THE WATER
 HEATER. SECTIONS 106..1.1 & 607.1.
  
 11. A GAS DRYER IS INDICATED ON THE PLANS. SUBMIT THE
 FOLLOWING INFORMATION REQUIRED FOR THE SEPARAGE GAS
 PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved