Plan Review Notes
Plan Review Notes For Permit 07050880
Permit Number 07050880
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-22 13:51:36------------------DENIED----------------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
 NFPA 72-02
 NFPA 90A-02
  
 1. PG A1.2: ACCORDING TO WALL TYPE DESIGNATION,
 CORRIDOR 108 IS NOT RATED. HOWEVER, THE ARCHITECTURAL
 SYMBOLS SCHEDULE INDICATES SOME PORTIONS ARE 1-HOUR
 RATED AND OTHERS 2-HOUR RATED. PLEASE CLARIFY AS THIS
 MAY IMPACT DUCT PENETRATIONS. FBC 106.1.1 AND FBC,M
 607.5
  
 2. M-2: 24X12 AND 6X4 EXHAUST DUCTS ON 2ND FLOOR ARE
 LOCATED IN A RETURN AIR PLENUM. EXHAUST DUCTS UNDER
 POSITIVE PRESSURE, CHIMNEYS, AND VENTS SHALL NOT EXTEND
 INTO OR PASS THROUGH DUCTS OR PLENUMS. FBC,M 601.3
  
 3. M-2: 30X14 SUPPLY DUCT FROM VAV 13 IS SHOWN PASSING
 THROUGH A 2-HOUR RATED WALL AS AN UNPROTECTED OPENING.
 PLEASE SHOW OPENING PROTECTIVES PER FBC,M 607.5.
  
 4. M-1: NOTE FOR ROOMS 117 AND 118 STATES "OPEN TO
 ABOVE" BUT THE REFLECTIVE CEILING PLAN ON A2.1 SHOWS A
 CEILING WITH RETURN AIR GRILLS. PLEASE CLARIFY. FBC
 106.1.1 AND FBC,M 601.4
  
 5. M-2: EQUIPMENT ROOM 209 SHOWS AN 8' CEILING. THE
 60X24 R/A OPENING WITH F.D. IS ABOVE THE CEILING WHILE
 HP-1 IS BELOW THE CEILING. HOW WILL THE AIR RETURN BACK
 TO HP-1?
  
 6. M-2: THE 18X14 DUCT TO 24X24 LOUVER FOR OUTDOOR AIR
 INTAKE FACES AN ALLEY OR STREET. MECHANICAL AND GRAVITY
 OUTSIDE AIR INTAKE OPENINGS SHALL BE LOCATED A MINIMUM
 OF 10 FEET FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS,
 ALLEYS, PARKING LOTS AND LOADING DOCKS. FBC,M 401.5.1
  
 7. M-2: SMOKE DETECTOR LOCATIONS AS SHOWN DO NOT
 MONITOR THE ENTIRE SUPPLY AIRFLOW. VAV 13 AND 15 (FOR
 EXAMPLE) TAP FROM SUPPLY UPSTREAM OF DETECTORS. SMOKE
 DETECTORS REQUIRED BY THIS SECTION SHALL BE INSTALLED
 IN ACCORDANCE WITH NFPA 72. THE REQUIRED SMOKE
 DETECTORS SHALL BE INSTALLED TO MONITOR THE ENTIRE
 AIRFLOW CONVEYED BY THE SYSTEM INCLUDING RETURN AIR,
 SUPPLY AIR, AND EXHAUST OR RELIEF AIR. ACCESS SHALL BE
 PROVIDED TO SMOKE DETECTORS FOR INSPECTION AND
 MAINTENANCE. FBC,M 606.3 ALSO, THE DUCT SMOKE DETECTORS
 SHALL BE CONNECTED TO A FIRE ALARM SYSTEM. THE
 ACTUATION OF A DUCT SMOKE DETECTOR SHALL ACTIVATE A
 VISIBLE AND AUDIBLE SUPERVISORY SIGNAL AT A CONSTANTLY
 ATTENDED LOCATION. EXCEPTION: THE SUPERVISORY SIGNAL AT
 A CONSTANTLY ATTENDED LOCATION IS NOT REQUIRED WHERE
 THE DUCT SMOKE DETECTOR ACTIVATES THE BUILDING'S
 ALARM-INDICATING APPLIANCES. FBC 606.4
  
 8. M-4: FIRE DAMPER DETAIL, PLEASE VERIFY DETAIL IS IN
 ACCORDANCE WITH F.D. MANUFACTURER'S INSTALLATIN
 INSTRUCTIONS. SEE FBC,M 607.2. ALSO, PLEASE CHECK FIRE
 DAMPER DETAIL NOTE #5. IT CALLS FOR A 3' HIGH CURB
 AROUND DUCT FLOOR OPENINGS. IS THIS CORRECT? IS THIS
 INTENDED TO BE 3"? FIRE DAMPER SLEEVE MUST BE LONG
 ENOUGH TO GO THROUGH FLOOR AND CURB WITH ENOUGH LENGTH
 FOR ANGLE AND DUCT CONNECTIONS. HOW WILL CONCRETE CURB
 BE INCORPRATED INTO THIS RATED ASSEMBLY?
  
 9. M-5 HEAT PUMP CLOSET DETAIL: HP-1 IS LOCATED IN A
 RETURN AIR PLENUM. PLEASE SHOW CONDENSATE DRAIN PIPE
 MATERIALS TO BE NON-COMBUSTIBLE OR MEET THE 25/50
 RATING AS REQUIRED BY FBC,M 602.2.1.
  
 10. PLENUM AREAS, SUCH AS ABOVE CEILING AND EQUIPMENT
 ROOM SHALL BE LINED WITH AN APPROVED AIR BARRIER PER
 FBC 13-410.1.ABC.3.7 AND ALL EXTERIOR WALLS EXPOSED TO
 PLENUM ARE TO BE INSULATED TO MINIMUM R-8 PER FBC TABLE
 13-410.1.ABC.2.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561-805-6719
 [email protected]