2007-06-14 13:49:031. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. HANDRAILS AND GUARDRAILS SHALL MEET ALL OF THE
 PRESCRIPTIVE STRENGTH REQUIREMENTS OF THE BUILDING AND
 FIRE CODES.
  
 3. PLEASE INDICATE WHAT FIRE RATING EXISTS FOR DOOR
 NUMBER 22 ON PAGE A1.0.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM ADDITIONS.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
 6. PROPER FIRE SEPARATION REQUIRED BETWEEN BEAUTY LAB
 AND OTHER PORTIONS OF THE BUILDING.
  
 7. MORE DETAILS NEEDED ON FREE STANDING CLOSET FABRIC
 ILLUSTRATED ON THE PLANS.
  
 8. PLEASE PROVIDE INFORMATION ON EMERGENCY LIGHTING
 WITHIN THE RETAIL WAITING AREA. PLEASE DISPLAY THEM.
  
 9. MEZZANINE TO COMPLY WITH ALL REQUIREMENTS OF THE
 FLORIDA BUILDING AND FIRE PREVENTION CODES.
  