Text |
| 2007-06-20 18:02:21 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE PLANS SHALL HAVE CODES STATED WHICH |
| | ARE RELEVANT TO PROJECT AND DESIGN. THE FOLLOWING CODES |
| | ARE TO BE STATED ON BOTH ELECTRICAL AND ARCHITECTURAL |
| | SHEETS AS ADOPTED BY THE STATE OF FLORIDA AS OF |
| | DECEMBER 8TH, 2006. |
| | 2004 FB C W/2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** OTHER CODES MAY BE REQUESTED FROM OTHER TRADES. |
| | |
| | 2) NOTE: PLEASE SEE MANY SHEETS IN MEP SETS ARE NOT |
| | SIGNED WITH SIGNATURE FROM THE ENGINEER OF RECORD WHICH |
| | IS ALREADY ON FILE AND RECOGNIZED BY THIS OFFICE. |
| | PLEASE SEE FS 471.025. |
| | THIS IS REQUIRED FOR ALL MEP SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 3) NOTE: PLEASE SEE PLANS WERE SUBMITTED WITH NO |
| | DESIGNS PER FBC FOR REQUIRED LIGHTING CONTROLS PER FBC |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE NO FIXTURE LEGEND WAS SHOWN ON PLANS. PLEASE |
| | SEE THE ENERGY CALCULATIONS ARE NOT CODE COMPLIANT. |
| | PLEASE SEE THE LIGHTING FIXTURES DO NOT CORRELATE. |
| | PLEASE SEE THE NUMBER OF FIXTURES DOES NOT CORRELATE. |
| | PLEASE SEE THE WATTAGE FOR FIXTURES DOES NOT |
| | CORRELATE. |
| | PLEASE COORDINATE ALL ON PLANS WITH THE ENERGY |
| | CALCULATIONS. |
| | PLEASE BE SURE THE OWNER AGENT IS SIGNED ON SHEETS AS |
| | REQUIRED. |
| | PLEASE SUBMIT TIME SCHEDULING DEPENDING ON SYSTEMS OR |
| | DEVICES. |
| | PLEASE INDICATE THE MAXIMUM OVER RIDE TIMES DEPENDING |
| | ON DEVICES. |
| | 13-415.1.AB.1.1, 13-415.2, 13-103.1 |
| | ** PLEASE KNOW AS MOST ITEMS WERE NOT DONE FOR THE |
| | REQUIRED CONTROLS, NO REVIEW OF ANY SYSTEMS OR PROPOSED |
| | DESIGNS COULD BE DONE AT THIS TIME. THERE MAY VERY WELL |
| | BE NEW COMMENTS ON THE NEXT REVIEW. |
| | |
| | 4) NOTE: PLEASE SEE THE PLANS NOTE TRANSFORMER(S) IN |
| | CLOSET WHICH IS NOT SHOWN ON PLANS OR CODE COMPLIANT |
| | DEPENDING ON UNITS. 450.9,450.13, 110.26, 408.7, |
| | 240.24. |
| | PLEASE PROVIDE MORE INFORMATION. |
| | |
| | 5) NOTE: PLEASE PROVIDE PHOTO-METRIC LEVELS FOR STAIRS |
| | UNDER NORMAL AND UNDER EMERGENCY CONDITIONS. PLEASE SEE |
| | NFPA-101 7.8.1.3, 7.9.2.2 |
| | |
| | 6) NOTE: PLEASE SEE MISSING LICENSE INFORMATION ON |
| | TITLE BLOCKS FOR * NEW WORLD DESIGN STUDIO*. PLEASE SEE |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.002, 61G1-16.004, |
| | FLORIDA STATUTES 471.023 AND 481.219. |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S). |
| | PLEASE SEE THIS COMMENT IS NOT FOR MR. KOLANY, OR |
| | FELLER ENGINEERING. |
| | |
| | 7) NOTE: PLEASE PLACE BE SURE ALL CIRCUIT DESIGNATIONS |
| | ON PLANS ARE SPECIFIC TO ALL ROOMS AND AREAS. PLEASE |
| | SEE NEC 408.4 AND COMMENTARY UNDER THE HANDBOOK AS |
| | FOLLOWS. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION* |
| | |
| | 8) NOTE: PLEASE KNOW THAT THE BASE BUILDING HAS NOT |
| | BEEN CO-ED AND ANY INFORMATION, LOAD CHANGES AND |
| | LIGHTING CHANGES NEEDS TO BE REVISED ON THE BASE |
| | BUILDING PLANS. |
| | PLEASE PROVIDE LOAD ON EXISTING SERVICE. |
| | 220 OF THE NEC AND FBC 106.3.5.1.2 |
| | |
| | 9) NOTE: PLEASE PROVIDE INFORMATION FOR NEC 517 AND |
| | 517.60 IF AND WHERE APPLICABLE. USE IS NOT CLEAR AT |
| | THIS TIME. |
| | |
| | 10) NOTE: PLEASE KNOW THE SUITE/UNIT # ONCE ASSIGNED |
| | WILL BE REQUIRED TO BE PLACED ON TITLE BLOCKS OF |
| | PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |