Plan Review Notes
Plan Review Notes For Permit 07050880
Permit Number 07050880
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-20 18:02:21*** UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS SHALL HAVE CODES STATED WHICH
 ARE RELEVANT TO PROJECT AND DESIGN. THE FOLLOWING CODES
 ARE TO BE STATED ON BOTH ELECTRICAL AND ARCHITECTURAL
 SHEETS AS ADOPTED BY THE STATE OF FLORIDA AS OF
 DECEMBER 8TH, 2006.
 2004 FB C W/2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** OTHER CODES MAY BE REQUESTED FROM OTHER TRADES.
  
 2) NOTE: PLEASE SEE MANY SHEETS IN MEP SETS ARE NOT
 SIGNED WITH SIGNATURE FROM THE ENGINEER OF RECORD WHICH
 IS ALREADY ON FILE AND RECOGNIZED BY THIS OFFICE.
 PLEASE SEE FS 471.025.
 THIS IS REQUIRED FOR ALL MEP SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES.
  
 3) NOTE: PLEASE SEE PLANS WERE SUBMITTED WITH NO
 DESIGNS PER FBC FOR REQUIRED LIGHTING CONTROLS PER FBC
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE NO FIXTURE LEGEND WAS SHOWN ON PLANS. PLEASE
 SEE THE ENERGY CALCULATIONS ARE NOT CODE COMPLIANT.
 PLEASE SEE THE LIGHTING FIXTURES DO NOT CORRELATE.
 PLEASE SEE THE NUMBER OF FIXTURES DOES NOT CORRELATE.
 PLEASE SEE THE WATTAGE FOR FIXTURES DOES NOT
 CORRELATE.
 PLEASE COORDINATE ALL ON PLANS WITH THE ENERGY
 CALCULATIONS.
 PLEASE BE SURE THE OWNER AGENT IS SIGNED ON SHEETS AS
 REQUIRED.
 PLEASE SUBMIT TIME SCHEDULING DEPENDING ON SYSTEMS OR
 DEVICES.
 PLEASE INDICATE THE MAXIMUM OVER RIDE TIMES DEPENDING
 ON DEVICES.
 13-415.1.AB.1.1, 13-415.2, 13-103.1
 ** PLEASE KNOW AS MOST ITEMS WERE NOT DONE FOR THE
 REQUIRED CONTROLS, NO REVIEW OF ANY SYSTEMS OR PROPOSED
 DESIGNS COULD BE DONE AT THIS TIME. THERE MAY VERY WELL
 BE NEW COMMENTS ON THE NEXT REVIEW.
  
 4) NOTE: PLEASE SEE THE PLANS NOTE TRANSFORMER(S) IN
 CLOSET WHICH IS NOT SHOWN ON PLANS OR CODE COMPLIANT
 DEPENDING ON UNITS. 450.9,450.13, 110.26, 408.7,
 240.24.
 PLEASE PROVIDE MORE INFORMATION.
  
 5) NOTE: PLEASE PROVIDE PHOTO-METRIC LEVELS FOR STAIRS
 UNDER NORMAL AND UNDER EMERGENCY CONDITIONS. PLEASE SEE
 NFPA-101 7.8.1.3, 7.9.2.2
  
 6) NOTE: PLEASE SEE MISSING LICENSE INFORMATION ON
 TITLE BLOCKS FOR * NEW WORLD DESIGN STUDIO*. PLEASE SEE
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002, 61G1-16.004,
 FLORIDA STATUTES 471.023 AND 481.219.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
 PLEASE SEE THIS COMMENT IS NOT FOR MR. KOLANY, OR
 FELLER ENGINEERING.
  
 7) NOTE: PLEASE PLACE BE SURE ALL CIRCUIT DESIGNATIONS
 ON PLANS ARE SPECIFIC TO ALL ROOMS AND AREAS. PLEASE
 SEE NEC 408.4 AND COMMENTARY UNDER THE HANDBOOK AS
 FOLLOWS.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION*
  
 8) NOTE: PLEASE KNOW THAT THE BASE BUILDING HAS NOT
 BEEN CO-ED AND ANY INFORMATION, LOAD CHANGES AND
 LIGHTING CHANGES NEEDS TO BE REVISED ON THE BASE
 BUILDING PLANS.
 PLEASE PROVIDE LOAD ON EXISTING SERVICE.
 220 OF THE NEC AND FBC 106.3.5.1.2
  
 9) NOTE: PLEASE PROVIDE INFORMATION FOR NEC 517 AND
 517.60 IF AND WHERE APPLICABLE. USE IS NOT CLEAR AT
 THIS TIME.
  
 10) NOTE: PLEASE KNOW THE SUITE/UNIT # ONCE ASSIGNED
 WILL BE REQUIRED TO BE PLACED ON TITLE BLOCKS OF
 PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]