Plan Review Notes
Plan Review Notes For Permit 07050880
Permit Number 07050880
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-07 11:21:21MD BEAUTY LABS
 410EVERNIA STSUITE#______
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07050880
 ADD: 410 EVERNIA ST, SUITE# ______
 CONT: SHAKMAN HOSPITALITY, LLC
 TEL: (561)750-8288
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE SEE ADDRESSING COMMENTS TO OBTAIN A SUITE
 NUMBER FOR RECORD KEEPING PURPOSES.
  
 4) COVERSHEET T1.0, BUILDING DATA:
 4A)OCCUPANCY REFERENCES THE 2001 FBC, PLEASE CORRECT,
 THIS SAME NOTE ALSO REFERENCES SECTION 304.1 GROUP2
 PLEASE ALSO CORRECT THE GROUP.
  
 4B) CONSTRUCTION CLASSIFICATION REFERENCES THE 2001 FBC
 PLEASE CORRECT, THIS SAME NOT ALSO
 REFERENCES THE BUILDING TYPE II PROTECTED CURRENT CODES
 REFERENCES TYPE II-A FOR A 1 HR PROTECTED BUILDING.
  
 4C) FIRE SEPARATION ? EXITS REFERENCES 3310.1 THIS
 REFERENCE IS FOR BUILDINGS DURING CONSTRUCTION?
  
 5) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED, F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT.
 G) NUMBER OF FLOORS IN BUILDING
 H) GROSS FOOTPRINT OF BUILDING
 I) SQ FT FIRST FLOOR OF TENANT SPACE
 J) SQ FT OF MEZZANINE AREA
  
 6) IT APPEARS THE MEZZANINE LEVEL MAY BE LARGER THAN
 ALOUD, IN DETERMINING THE ALLOWABLE AREA OF A
 MEZZANINE, THE ENCLOSED SPACE OF THE ROOM BELOW ARE NOT
 TO BE INCLUDED IN THE CALCULATING THE ROOM SIZE. IF THE
 AREA LIMITATION IS EXCEEDED, THE PROVISIONS OF THIS
 SECTION DO NOT APPLY AND THE LEVEL IS CONSIDERED A
 STORY.
 505.2 AREA LIMITATIONS: THE AGGREGATE AREA OF A
 MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL NOT EXCEED
 ONE-THIRD OF THE AREA OF THAT ROOM OR SPACE IN WHICH
 THEY ARE LOCATED. THE ENCLOSED PORTIONS OF ROOMS SHALL
 NOT BE INCLUDED IN A DETERMINATION OF THE SIZE OF THE
 ROOM IN WHICH THE MEZZANINE IS LOCATED. IN DETERMINING
 THE ALLOWABLE MEZZANINE AREA, THE AREA OF THE MEZZANINE
 SHALL NOT BE INCLUDED IN THE AREA OF THE ROOM.
  
 7) SHEET A1.0 INDICATES TO REACH THE MEZZANINE LEVEL A
 PERSON IN A WHEEL CHAIR WILL NEED TO LEAVE THE TENANT
 SPACE GO TO THE ELEVATORS IN THE HALLWAY TO REACH THE
 MEZZANINE LEVEL.
 THIS IS DISCRIMINATION AGAINST THOSE WITH DISABILITIES,
 SEE 11-2.2 EQUIVALENT FACILITATION.
 DEPARTURES FROM PARTICULAR TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE BY THE USE OF OTHER DESIGNS
 AND TECHNOLOGIES ARE PERMITTED WHERE THE ALTERNATIVE
 DESIGNS AND TECHNOLOGIES USED WILL PROVIDE
 SUBSTANTIALLY EQUIVALENT OR GREATER ACCESS TO AND
 USABILITY OF THE FACILITY.
 DEPARTURE FROM THE EXPLICIT TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE FOR ANY ELEMENT VOIDS ANY
 OTHERWISE APPLICABLE PRESUMPTION OF REBUTTABLE EVIDENCE
 THAT THE ELEMENT HAS BEEN CONSTRUCTED OR ALTERED IN
 ACCORDANCE WITH THE MINIMUM ACCESSIBILITY REQUIREMENTS
 OF THE ADA.
 EITHER A LIFT OR ELEVATOR MUST BE PLACED IN THE TENANT
 SPACE SO THE DISABLED WILL BE ABLE TO REACH THE
 MEZZANINE LEVEL.
 11-4.1.3(5) (5)ONE PASSENGER ELEVATOR COMPLYING
 WITH SECTION 11-4.10 SHALL SERVE EACH LEVEL, INCLUDING
 MEZZANINES, IN ALL MULTISTORY BUILDINGS AND FACILITIES
 UNLESS EXEMPTED BELOW. IF MORE THAN ONE ELEVATOR IS
 PROVIDED, EACH FULL PASSENGER ELEVATOR SHALL COMPLY
 WITH SECTION 11-4.10 .
 VERTICAL ACCESSIBILITY SHALL BE PROVIDED TO ALL
 LEVELS ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL,
 REGARDLESS OF WHETHER THE CODE REQUIRES AN ELEVATOR TO
 BE INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY,
 EXCEPT FOR: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES,
 MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND
 PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS,
 ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. HOWEVER, AS PROVIDED IN SECTION 553.509,
 FLORIDA STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES
 MUST, AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF
 ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADA MAY BE
 REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS OTHERWISE
 EXEMPT UNDER SECTION 11-4.1.3 (5)(3) OF THE CODE.
  
 8) SHEET A5.2 STAIRWAY HANDRAILS ARE MISSING:
 11-4.9.4(2)IF HANDRAILS ARE NOT CONTINUOUS, THEY
 SHALL EXTEND AT LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND AT LEAST 12 INCHES (305 MM) PLUS THE WIDTH OF
 ONE TREAD BEYOND THE BOTTOM RISER. AT THE TOP, THE
 EXTENSION SHALL BE PARALLEL WITH THE FLOOR OR GROUND
 SURFACE. AT THE BOTTOM, THE HANDRAIL SHALL CONTINUE TO
 SLOPE FOR A DISTANCE OF THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE EXTENSION SHALL BE
 HORIZONTAL [SEE FIGURE 19 (C) AND FIGURE 19 (D)].
 HANDRAIL EXTENSIONS SHALL COMPLY WITH SECTION 11-4.4 .
  
  
 9) SHEET A5.2 PLEASE PROVIDE ADDITIONAL INFORMATION ON
 THE STAIRS:
 9A) PLEASE PROVIDE INFORMATION ON THE WOOD FINISH OF
 THE STAIRS? PROVIDE THE RISER AND TREAD DIMENSIONS? 9B)
 PLEASE PROVIDE THE ADDITIONAL DETAILS THAT DO NOT
 APPEAR ON THIS SHEET DETAIL# 5, AND THE DECORATIVE
 STEEL BALUSTERS.
  
 10) PLANS DO NOT PROVIDE ROOM FINISHES, PLEASE
 INDICATE. 803.1.
  
 11A)SHEET A1.1 AND A3.0 INDICATES DETAILS FOR OVER
 THE TREATMENT ROOM FOR A MECHANICAL ROOM, WHAT TYPE
 WALLS AND CEILING ARE THE TREATMENT ROOM MADE OF
 BEARING WALLS AND TYPE OF CEILING JOIST?
  
 11B) SHEET A5.5 INDICATES THE USE OF CATWALK GRATING
 AND REFERENCES TO STRUCTURAL SHEETS WHICH DO NOT APPEAR
 IN THE SHEET INDEX?
  
 11C) WHAT MATERIALS DOES THE WALKWAY TO THE MECHANICAL
 ROOM MADE OF, AND HOW IS IT
 SUPPORTED? PROVIDE ADDITIONAL INFORMATION?
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]