Plan Review Notes
Plan Review Notes For Permit 07050876
Permit Number 07050876
Review Stop M
Sequence Number 2
Notes
Date Text
2007-11-01 16:51:25REVIEW #: 2 (1ST REVIEW FOR PERMIT)
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THE REQUEST WAS FOR HOW ROOF CURB FOR RTAC UNITS ARE
 TO BE ATTACHED TO BUILDING STRUCTURE. THIS IS NOT
 RELATED TO THE PRE-ENGINEERED A/C STANDS FOR THE
 CONDENSING UNITS. THE DETAIL ON PG M.107 INDICATES
 CURBS ARE TO "ANCHOR OR BOLT TO ROOF STRUCTURE AS REQ'D
 BY LOCAL CODES." THERE ARE NO LOCAL CODES WHICH GIVE
 DESIGNS FOR STRUCTURAL ATTACHMENTS. THE STRUCTURAL
 ENGINEER IS RESPONSIBLE FOR DESIGNING AN ATTACHMENT
 METHOD DESIGNED TO MEET WIND LOAD REQUIREMENTS IN
 ACCORDANCE WITH FBC 1609. THE STRUCTURAL ENGINEER HAS
 PROVIDED A DETAIL FOR FRAMING OF THE ROOF OPENING FOR
 THE CURB ON PG S-3, BUT NO INFORMATION WAS PROVIDED FOR
 HOW THE CURB IS TO BE ATTACHED TO THIS STEEL FRAMING.
 PROVIDE INFORMATION ON TYPE AND SPACING OF
 ATTACHMENTS.
  
 2. IF THE EQUIPMENT LIFTING LUGS ARE TO BE USED FOR
 WIND RESISTANCE, PROVIDE MANUFACTURER?S SUBMITTAL
 SHOWING THE LIFTING LUGS CAPABLE OF WITHSTANDING THE
 REQUIRED WIND LOADS. IF CABLES ARE TO BE LOOPED OVER
 THE UNITS, PROVIDE WIND LOAD CALCULATIONS FOR
 STRUCTURAL REVIEW. RESPONSE ALSO REFERENCES NOA FOR A/C
 STANDS, WHICH DO NOT RELATE TO ROOF CURB MOUNTING OF
 RTAC UNITS.
  
 3. OK.
 NOTE: MIAMI-DADE NOA?S WHICH ARE UP-TO-DATE DO NOT
 REQUIRE LOCAL PRODUCT APPROVAL AS THEY ARE ACCEPTABLE
 UNDER THE FLORIDA PRODUCT APPROVAL SYSTEM.
  
 4. LOCATION OF CONDENSATE DISPOSAL OK. HOWEVER,
 AUXILIARY DRAIN PROTECTION IS STILL REQUIRED. THE
 ASSERTION THAT CONDENSATE OVERFLOW FROM A ROOFTOP
 PACKAGE UNIT WILL NOT CAUSE DAMAGE TO BUILDING
 COMPONENTS IS NOT ACCEPTED. THE UNIT SITS OVER A ROOF
 CURB WHICH LEAVES THE UNDERSIDE OF THE UNIT EXPOSED TO
 THE INTERIOR OF THE BUILDING. IF THE CONDENSATE DRAIN
 PAN OVERFLOWS, THE WATER FROM THE PAN WILL MOST LIKELY
 FLOW INTO THE BUILDING WITH THE POTENTIAL TO DAMAGE ANY
 BUILDING COMPONENT BELOW IT SUCH AS DUCTWORK,
 ELECTRICAL EQUIPMENT, CEILINGS, ETC. AUXILIARY DRAIN
 PROTECTION MAY BE PROVIDED BY INSTALLING A WATER LEVEL
 DETECTION DEVICE (SUCH AS A FLOAT SWITCH) IN THE
 PRIMARY DRAIN PAN OF THE RTAC UNITS. PROVIDE AUXILIARY
 OR SECONDARY DRAIN PROTECTION AS REQUIRED BY FBC,M
 307.2.3.
  
 5. OK
  