Plan Review Notes
Plan Review Notes For Permit 07050876
Permit Number 07050876
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-22 14:12:082007-09-22 14:12:08
  
 ** DENIED 2ND REVIEW**
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
 THERE ARE ALSO SOME NEW COMMENTS BASED ON SOME CHANGES
 MADE TO PLANS.
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS WHICH HAVE STILL
 NOT BEEN ADDRESSED AND INFORMATION NOT PROVIDED FOR
 REVIEW, THERE ARE ITEMS WHICH CAN NOT BE REVIEWED AT
 THIS TIME FOR CODE COMPLIANCE AND MAY VERY WELL HAVE
 NEW COMMENTS ON THE NEXT REVIEW.
 THIS DEPARTMENT CAN ONLY REVIEW PLANS AND DOCUMENTS
 WHICH ARE SUBMITTED.
  
 **THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
  
 1) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS SUCH
 AS ENERGY CALCULATIONS, SOIL REPORTS ETC DOWN THE LEFT
 HAND SIDE OF PLANS. THESE MAY BE PLACED IN A SPIRAL
 NOTE BOOK OR FOLDER OF SOME TYPE.
 THIS WILL HELP IN THE REVIEW PROCESS AND HELP AVOID ANY
 DELAYS.
  
 ** IMPORTANT **
 ANY STAMPS SUCH AS A *SHOP DRAWING* REVIEW STAMPS BY A
 DESIGNER PROFESSIONAL IS REQUIRED TO BE ON THE FRONT OF
 DOCUMENTS.
 THESE DOCUMENTS ARE SCANNED AND REVERSE SIDES ARE NOT
 SCANNED: EVEN IF THE REAR SIDE OF SHEET IS SCANNED,
 THIS STAMPED WOULD BE ON A *BLANK* SHEET WHICH WOULD
 NOT CONNECT THIS STAMP TO ANY DOCUMENT.
 FBC 106.1, 106.5 ADMIN SECTIONS.
  
 2) NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS REVIEW WHICH
 GAVE CODE SECTIONS TO BE STATED ON PLANS. PLEASE SEE
 MOST OF THESE WERE DONE ON ELECTRICAL PLANS HOWEVER
 PLEASE SEE SHEET E-111 WHICH INDICATES THE 2005 IEC AND
 THE SHEET A000 STILL INDICATES THE 2002 NFPA-70/
 NATIONAL ELECTRICAL CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE THERE ARE SEVERAL CODES ON SEVERAL SHEETS
 WHICH DO NOT APPLY TO PROJECT IN THIS STATE. PLEASE
 REMOVE.
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #6 WITH
 RESPECT TO THE FLORIDA ENERGY CODE IN FLORIDA BUILDING
 CODE CHAPTER 13.
 ** PLEASE SEE THE PREVIOUS REVIEW NOTES WILL REMAIN
 BELOW:
 PLEASE SEE THE ENERGY CALCULATIONS SQ FT STILL DOES NOT
 CORRELATE WITH PLANS. RESPONSE DOES NOT MENTION THIS OR
 ANY ADJUSTMENTS
 PLEASE SEE FIXTURE LEGEND WAS NOT PROVIDED ON
 ELECTRICAL PLANS TO COORDINATE AND REVIEW ENERGY
 CALCULATIONS.
 PLEASE SEE THE SUMMARY SHEET AND SHEET 5 FOR LIGHTING
 DESIGN IS THE SAME.
 PLEASE SEE THE INPUT DATA REPORT IS TO BE COORDINATED
 WITH ALL LIGHTING ON PLANS.
 PLEASE SEE THE KW RATING ENTERED FOR THE WATER HEATER
 IS 2KW, YET PLANS INDICATE 3KW?
 PLEASE SEE OWNER AGENT STILL NOT SIGNED.
 PLEASE SEE THE OVER RIDE DEVICE(S) MUST BE LOCATED SO
 THE OCCUPANT CAN SEE ALL LIGHTING WHICH IS BEING
 CONTROLLED. THERE IS AN EXCEPTION FOR INDICATOR/PILOT
 LIGHTS.
 PLEASE SEE ALL SEPARATE SPACES FOR OVER RIDES OR
 LIGHTING CONTROLS. PLEASE SEE ONE LOCATION FOR EXAMPLE
 IS TELLER AREA FOR DRIVE THROUGH WHICH STILL SEEMS TO
 INDICATE STANDARD SWITCHES? AS THE SYMBOL LEGEND DOES
 NOT PROVIDED ANY OTHER TYPE DEVICE EXCEPT FOR
 *HORSEPOWER RATED FOR ONE* AND *TIMER TYPE* FOR THE
 OTHER THESE STANDARD *S* SYMBOLS ON PLANS CAN ONLY BE
 ASSUMED AS THE STANDARD DEVICE AS NOTED IN NOTE #4 IN
 LIGHTING NOTES ON E-101.
 ETC.
 **PLEASE SEE IN FACT THE SAME ENERGY CALCULATIONS WERE
 SUBMITTED BACK AND COMMENTS FROM PREVIOUS REVIEW WITH
 RESPECT TO ENERGY CALCULATIONS REMAIN.
  
 PLEASE SEE THE ENERGY CALCULATIONS CAN NOT BE VERIFIED
 AT THIS TIME AS THE PLANS DO NOT CONTAIN ANY FIXTURE
 LEGEND AND COORDINATION OF LABELING OF FIXTURES STILL
 NEEDS TO BE DONE.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING. PLEASE
 SEE SOME SEPARATE SPACES ARE MISSING THE REQUIRED
 CONTROLS.
 PLEASE SEE NO TIMES FOR THE OVER RIDE DEVICES COULD BE
 LOCATED.
 PLEASE SEE SOME OVER RIDE DEVICE LOCATIONS COULD NOT BE
 FOUND ON PLANS AS REQUIRED.
 PLEASE SEE THE DESIGN WATTS ON ENERGY CALCULATIONS
 SHEET 5 DOES NOT CORRELATE WITH THE DESIGN WATTS ON
 SHEET 2.
 PLEASE SEE THE SQ FT AS SHOWN CALCULATIONS ON ONE PART
 IS NOTED AS 87,000 SQ FT?
 PLEASE SEE THE SHEET 2 ON ENERGY CALCULATIONS MUST BE
 SIGNED BY OWNER AGENT.
 PLEASE SEE 13-103.1.1.1, 13-415.1.ABC.1.1, .1.2 AND
 .1.3, 13-415.1.AB.1.1, 13-415.2 ETC
 PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR FEEDER(S)
 AND BRANCH CIRCUIT(S).
 PLEASE SEE 13-413.1ABC.1
  
 4) NOTE:PLEASE SEE NOTE #7 FROM PREVIOUS REVIEW.
 PLEASE SEE RESPONSE MENTIONS THE SHUNT TRIP IS
 PERMITTED TO MEET THE NEC FOR 230.76 AND 230.79. THIS
 DEVICE DOES NOT MEET THE NEC FOR A MANUAL MEANS OF
 DISCONNECT AND IS NOT RATED FOR THE LOAD SERVED. PLEASE
 KNOW THIS IS NOT ACCEPTABLE FOR USE BY THE NEC OR THIS
 AHJ AND WILL NOT BE PERMITTED IN LIEU OF THE MINIMUM
 REQUIRED PER CODE AND LIFE SAFETY OF INSTALLATION.
 PLEASE ADJUST RISER AND EQUIPMENT BASED ON PREVIOUS
 REVIEW NOTES.
 PLEASE SEE THAT NO MANUFACTURE SPECS/CUT SHEETS WERE
 SUBMITTED FOR THE MTS AND OTHER EQUIPMENT AS PREVIOUSLY
 REQUESTED FOR PROPOSED INSTALLATION.(SHEET FOR A
 DOUBLE THROW SAFETY SWITCH??)
 PLEASE KNOW THAT ANY MTS MUST NOT ONLY MEET CODE
 HOWEVER THE CONNECTION AND DISCONNECT OF A PORTABLE
 GENERATOR WILL ONLY BE PERMITTED BY QUALIFIED
 PERSONNEL.
 PLEASE PROVIDE INFORMATION FOR THE MAIN, DISCONNECT
 LOCATION, EQUIPMENT ON RISER INCLUDING THE PROPOSED
 *CAM-LOCK* BREAKER ENCLOSURE. ALL EQUIPMENT IS TO
 CONTAIN LISTING FOR INTENDED USE AND NEEDS TO BE ON ANY
 SPECS/CUT SHEETS SUBMITTED.
 PLEASE SEE 230.70, 230.72, 225.31-22539, 230.76,
 230.79, 110.3, 90.7, 702.6 ETC.
 FBC 106.1.2 ADMINISTRATIVE SECTION FOR ADDITIONAL
 INFORMATION.
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE MORE INFORMATION FOR MAIN. PLEASE SEE
 THE MAIN WHICH CONTAIN THE MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED PER 230.76 AND 230.79 SHALL
 BE INSTALLED AT A LOCATION WHICH HAS READY ACCESS. AS
 SHOWN ON PLANS THE MAIN IS LOCATED A DISTANCE IN THE
 BUILDING AND BEHIND SEVERAL LOCKED DOORS. PLEASE SEE
 THIS IS A LIFE SAFETY AND PROPERTY HAZARD IN ORDER FOR
 THE FIRE DEPARTMENT OR ANY OTHER PERSON NEEDING TO SHUT
 OFF POWER TO BUILDING. THE USE OF A SHUNT TRIP LOCATED
 OUTSIDE IS NOT PERMITTED AS IT DOES NOT MEET THE ABOVE
 CODE SECTIONS.
 PLEASE SEE A DIRECT ACCESS TO MAIN ELECTRICAL ROOM FROM
 OUTSIDE OR SOME OTHER MEANS TO ACCESS MAIN WILL BE
 REQUIRED. THIS WAS CONFIRMED WITH THE FIRE MARSHALS
 OFFICE.
 230.70, 230.71, 230.72 ETC.
  
 5) NOTE:SAME NOTE AS PREVIOUS REVIEW NOTE #8. PLEASE
 PROVIDE THE MANUFACTURES SPECS/CUT SHEETS FOR THE NEW
 PROPOSED MTS. 90.7, 110.3.
 FBC 106.1.2
  
 6) NOTE:SAME NOTE AS PREVIOUS REVIEW NOTE #9. PLEASE
 SEE THE PLANS SEEM TO CONTAIN MANY AREAS IN WHICH THERE
 IS INFORMATION PRINTED IN *LT GRAY* AND NOT EASILY
 READ. PLEASE SEE ELECTRICAL SHEETS.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTE #12 WHICH REQUESTED
 INFORMATION FOR LIGHT POLES ETC WHICH WAS TO INCLUDE
 CALCULATIONS FOR POLES TO BE REVIEWED AND MEET THE
 MINIMUM WIND LOAD DESIGNS FOR THIS AREA PER THE FBC.
 PLEASE SEE THE RESPONSE WHICH MENTIONS TO SEE *S*
 SHEETS/STRUCTURAL SHEETS FOR INFORMATION HOWEVER THE
 *S* SHEETS DO NOT SEEM TO PROVIDE ANY WIND LOAD
 CALCULATIONS FOR POLES. PLEASE SEE IN FACT THE
 ELECTRICAL SITE LIGHTING PLANS DO NOT INDICATE ANY
 MINIMUM WIND LOAD REQUIREMENTS EITHER.
 THE RESPONSE ALSO MENTIONS TO SEE CIVIL PLANS HOWEVER
 THE CIVIL PLANS INDICATE SOME LOCATIONS OF POLES AND
 LIGHT FIXTURES, HOWEVER NO OTHER INFORMATION. PLEASE BE
 SURE TO COORDINATE ALL SITE POLE LOCATIONS AS THERE ARE
 SOME DIFFERENCES IN LOCATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ANY SITE LIGHTING ELECTRICAL DETAILS.
 PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION FOR
 POLES.
 PLEASE KNOW THESE MAY BE UNDER A SEPARATE PERMIT AT A
 LATER DATE.
 FBC 106.1.2, 106.3
  
 8) NOTE:SAME NOTE AS PREVIOUS REVIEW NOTE #13,. AS
 MENTIONED THIS WOULD B REDLINED HOWEVER WILL REMAIN AS
 THE SHEET REFERENCES THE 2005 IEC.
 PLEASE SEE THE COLOR CODING EVEN THOUGH NOT APPLICABLE
 IN THIS SERVICE SITUATION FOR 277/480V IS BROWN,
 PURPLE, AND YELLOW.
 THIS DOES NOT NEED TO BE CHANGED, AND WILL BE
 REDLINED.
  
 9) NOTE: NO INFORMATION OR PHOTO-METRIC LEVELS FOR BANK
 ATM AREAS. PLEASE SEE FLORIDA STATUTES 655.962. PLEASE
 SEE RESPONSE MENTIONS THIS WILL BE COORDINATED WITH THE
 ARCHITECT HOWEVER NO INFORMATION WAS SUBMITTED.THE
 RESPONSE FROM THE ARCHITECT MENTIONS PLANS MEET THE
 MINIMUM LIGHTING LEVELS HOWEVER PLEASE SEE THE ONLY
 LIGHTING LEVELS/PHOTO-METRICS SUBMITTED ARE THOSE ON
 CIVIL PLANS HOWEVER THEY ARE NOT SPECIFIC TO AREAS AS
 STATED IN THE FLORIDA STATUTES. THESE LEVELS AS SHOWN
 ON CIVIL PLANS DO NOT MEET THE MINIMUM LEVELS AS
 REQUIRED PER THE SECTIONS IN THE FS AS NOTED ABOVE.
 PLEASE PROVIDE COMPLETED PHOTO-METRICS FOR ATM(S) AREAS
 BASED ON THE DISTANCES IN THE FS.
 FBC 106.1.2, 106.3.1 ETC ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 10) NOTE: PLEASE KNOW ONE SET OF ELECTRICAL PLANS AND
 ENERGY CALCULATIONS MAY BE RETAINED BY THIS OFFICE.
  
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET
 SUBMITTED FOR REVIEW AND THE CHANGES WHICH WILL BE
 NEEDED FOR SERVICE A COMPLETE REVIEW CAN NOT BE DONE AT
 THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-22 12:17:062007-09-22 12:17:06
  
 IN ELEC FOR REVIEW: