2007-09-25 16:01:14CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 07050876 BUILDING
 PLAN EXAMINERII PROJECT COMMERCE
 BANK
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 2031 PALM
 BEACH LAKES BLVD
  DATE SEPTEMBER 24, 2007
  
 STRUCTURALPLANREVIEW
  
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY.
 THE PERMITTED SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 PALM BEACH COUNTY ASSESSMENT
 PALM BEACH COUNTY IMPACT FEE ASSESSMENT HAS MOVED TO:
 2300 N JOG ROAD, SUITE 2 WPB 33411
 COMMENT-FOR YOUR INFORMATION
  
  
 NOTE ON COVER SHEET 1
 FBC2004 BUILDING W/ 2005 AND 6 REVISIONS
 FAC 2004CHAPTER 11
 TYPE OF CONSTRUCTION / SPRINKLED / UN-SPRINKLED WIND
 SPEED AND EXPOSURE
 WIND IMPORTANCE FACTOR
 TYPE OF OCCUPANCY
 OCCUPANT LOAD
 GROSS LOAD
 NET LOAD
  
  
 1. FL S S 713.13NOTICE OF COMMENCEMENT
 TO BE FILED WITH THE CLERK OF THE COURT.NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6).
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. COMMENT-
 FOR YOUR INFORMATION
  
  
 2. F.S. 481.219CERTIFICATE OF AUTHORIZATION
 A CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED FOR A
 CORPORATION, LIMITED LIABILITY
 COMPANY, PARTNERSHIP, OR PERSON OPERATING UNDER A
 FICTITIOUS NAME, OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
 COMMENT-INTERARCH C.A. IS MISSING
  
  
  
 3 FBC BUILDINGS 1609.1.4 PROTECTION OF OPENINGS. IN
 WIND-BORNE DEBRIS REGIONS, GLAZING IN BUILDINGS SHALL
 BE IMPACT RESISTANT OR PROTECTED WITH AN IMPACT
 RESISTANT COVERING MEETING THE REQUIREMENTS OF SSTD 12,
 ASTM E 1886 AND ASTM E 1996, ANSI/DASMA 115 (FOR GARAGE
 DOORS AND ROLLING DOORS) OR MIAMI-DADE TAS 201, 202 AND
 203 OR AAMA 506 REFERENCED THEREIN AS FOLLOWS: COMMENT-
 FOR YOUR INFORMATION
  
 4 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE ATWWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG COMMENT-
 FOR YOUR INFORMATION
  
 5 ROOF HATCH
 COMMENT-THE ENGINEER SUBMITTING THE TESTING
 INFORMATION MUST BE A FLORIDA P.E.
 PLEASE SEE THE ATTACHED FLORIDA COMMUNITY AFFAIRSRULE
 9B-72
 THIS WILL GIVE YOU THE DIRECTION TO ACHIEVE LOCAL
 PRODUCT APPROVAL.
 ALSO SEE THE ATTACHED APPLICATION THAT MUST BE
 SUBMITTED FOR THIS APPROVAL
 SYSTEM
  
  
 6.PRODUCT APPROVALALUMINUM LOUVERSAEL-42D-7060
 COMMENT- ONLY ONE COPY WAS SUBMITTED. THIS PRODUCT IS
 ACCEPTABLE FOR USAGE
 PLEASE SUBMIT ADDITIONAL COPY FOR ACCEPTANCE
  
  
 7 PRODUCT APPROVALEXTERIOR INSULATION AND FINISH
 SYSTEM
 COMMENT- ONLY ONE COPY WAS SUBMITTED. THIS PRODUCT IS
 ACCEPTABLE FOR USAGE
 PLEASE SUBMIT ADDITIONAL COPY FOR ACCEPTANCE
  
 8 ENERGY CALCULATIONS
 GROSS AREA DOES NOT MATCH PLAN ALONG WITH OTHER ITEMS
 WHEN REVIEWING PLEASE CHECK PLAN FOR COMPLIANCE
  
 9DRINKING FOUNTAINS.
 WHERE ONLY ONE DRINKING FOUNTAIN IS PROVIDED ON A
 FLOOR, THERE SHALL BE A DRINKING FOUNTAIN WHICH IS
 ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS IN
 ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE TO
 THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. (THIS
 CAN BE ACCOMMODATED BY THE USE OF A "HI-LO" FOUNTAIN;
 BY PROVIDING ONE FOUNTAIN ACCESSIBLE TO THOSE WHO USE
 WHEELCHAIRS AND ONE FOUNTAIN AT A STANDARD HEIGHT
 CONVENIENT FOR THOSE WHO HAVE DIFFICULTY BENDING; BY
 PROVIDING A FOUNTAIN ACCESSIBLE UNDER SECTION 11-4.15
 AND A WATER COOLER; OR BY SUCH OTHER MEANS AS WOULD
 ACHIEVE THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON
 EACH FLOOR.)
  
 10 1503.4.3 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
 COMMENTIN THE EVENT OF CLOGGED DRAINS WHAT MEANS IS
 AVAILABLE TO DISPERSE THE WATER OFF THE ROOF SURFACE
  
 11 A003DETAIL 1
 COMMENTSUBMIT TYPE OF FASTENING AND SPACING FOR TOP
 AND BOTTOM TRACK OF PARTITION
  
 12 A003DETAIL 3
 COMMENTSUBMIT TYPE OF FASTENING AND SPACING FOR
 TRACK
  
 13 A003 DETAIL6
 COMMENTDETAIL THE FASTENING AND SPACING FOR THE
 1-1/2? METAL STUD ON EDGE TO THE CONCRETE CEILING
  
 14 A004DETAIL 3
 COMMENT19/32?PLYWOOD MUST BE SEPARATED FROM
 CONCRETE MASONRY UNITS